ML19326C622

From kanterella
Jump to navigation Jump to search
PNO-I-80-37:on 800309,licensee Scheduled Maint on Fire Protection Sys Due to Cracked & Leaking Valve Body on Sys Supply Header.Fire Protection During Outage Will Be Supplied by Fire Truck Connected to Number 2 Fire Hydrant
ML19326C622
Person / Time
Site: Oyster Creek
Issue date: 03/07/1980
From: Briggs L, Brunner E, Keimig R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
References
PNO-I-80-037, PNO-I-80-37, NUDOCS 8004240221
Download: ML19326C622 (1)


Text

_ _ _ _

76#4 e

PRELIMINARYNOTIFICATION 23 Date:

Marcs 7,1980 PRELIMINARY NOTIFICATION OF EVE.NT OR UNUSUAL OCCURRENCE--PNO-I-80-37 This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or public interest significance.

The Information cresented is as initially received without verification or evaluation and is basicrlly all that is known by IE staff en snis_cate.

Facility:

Jersey Central Power and Light Company Oyster Crcck, Unit 1. DN 50-219 Forked River, New Jersey c

Subject:

TIRE SYSTEM OUT OF SERVICE f

Region I was notified by the licensee that required maintenance on the fire system due to a cracked and leaking valve body un the system supply header would require isolation of the fire system. Maintenance is scheduled to taka place on Sunday, March 9, 1980. The licensee is taking precautions' to insure that both Core Spray systeins remain operable and that an adequate supply of water is available. The fire p-Jtection system will be supplied by a fire truck (pumper) connected to No. 2 fire hydrant. Hre Protection Technical Specifications allow the fire system to be out of service for 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> before a substitute system is required.

The system is expected to be out of service for approximately 8 to 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />.

Fire watches will be assigned per T.S. and the Mode Selector Switch will be locked in the shutdown 2 + 2.

position.

In addition, no work will be performed that could inadvertently lower h.;

reactor water level below 4' 0" above the top of the core.

.. = = -

The maintenance is being planned to prevent the unexpected loss of the fire protectior, system.

Media interest is expected due to close coverage of the facility.

The licensee will report this item to the news media during their weekly news release.

The NRC is not planning a ncets release.

The State oi' New Jersey has been infonned.

Contact:

L. Origgs 488-1306 R. R. Keimig 488-1252 E. J. Brunner 488-1240 DISTRIBUTibN:

(Facsmile Transuission Times Noted)

H ST BLDG MARYLAND NATIONAL IE:X005 Chairman Ah'e'a'ene BANK BUILDING NRC/TMT 'T'echnical Commissioner Kennedy W. J. Dircks. W '

Support Office Ccmissioner Gilinsky C. Michelson, AEOD Conmissioner Bradford J. J. fouchard, PA Region II Comissioner llendrie N. M. Haller, MPA Region III._,_,,

ACR5 R. C. Ryan 05P Region IV S. J. Chilk SECY H. K. Shapar, ELD Region V ~" ',,,,

C. C. Kamerer CA (For Distribution)

WILLSTE DLDC RI Resident Sites J. G. Davis, 104S5

/

PHILLIPS BLOG

5. Levin. RES..._ _

,,,,. /,

15 5 H. R. Denton, NRR E3F R. C. DeYoung, NRR LANDOW BLDG (~ Fax by, H.Q)'

(MAIL)

~

k. J. Mattson, NRR (6 MIN /PAGE) ~" -

R. Minogue, 50 D. Vossalto. NRR J. J. Cunanings OIA IE:X005 D. Fir.enhut, NRK PR LIMINARY NOTIFICATION Region I Forn 83a D,m}D

.y D,9. },

(Rev. January 1980) f$04-Q40%j.

  • h" O

b-

=

.