L==

3 s F

. - =.

(j sei=

s,;

-=(:

DISIRIBlTTION T.1 PDR KGoller

..,_.~,T cal PDR KKniel cket IWassallo FEB 8 s74 LhR 2-3 Rdg ASchwencer GE VAMoore KButler EE Docket No. 50-313 JHendrie JStolz

.ff AKenneke ACRS (16)

T=f:~"

='

DEisenhut 5 extra cps Arkansas Power G Light Cocpany RKKlecker ATIN: Mr. J. D. Phillips OGC a.;i~~E Vice President G R0 (3)

.e=. -

011cf Engineer PMBernero s:-

Sixth and Pino Streets E..Goulbourne Pine Bluff, Arkansas-71601 PMaccary Eri RTedesco EE Gentlemen:

VStello c.

HDenton

[.:.

Eccause we are starting to issue operating licenses with broad possession

~

EE and use limits on radioactive materials, we request that you provide us q.:

with the enclosed informtion by Febntary 28, 1974. Enclostre 1 contains L

the proposed rexlification to the standard operating license for your

=

infornation. Enclosure 2 contains the additional information we are requesting of applicants prior to licensing. Enclosure 3 contains a sarple addition to the Technical Specifications which will be required as Appendix A to the operating licenses.

Sincerely,

.q Edstradb[

Au..'rt saiv enar i :......

A. Schwencer, Chief f'

Light hhter P.cactors Br. 2-3 Directorate of I.icensing

(

Enclosures:

As Stated p

ccs: i:orace Jewc11 i':

llouse,liolts G Jewell i.L 1550 Tower ikiilding

}.

Little P.ock, Ark:msas 72201 g.i

(

!!r. Eillian Cavenaugh, III Production Departrent 5

P. O. Icx 551

==

Littic Rock, Arb nsas 72203 u4.

Lh

,,.eue..

..e.

.e s.4e i e w s m..s.erhemnat Ascheheer-gx u.n.,

3p 2L1.. /74 2 L. f.

/74 o.n ~

uc. n. < r,...

+ 3,.u cx u. <

(

............m..

4,,

'~

s u

ENCIDSURE 1 M]DIFICATICN TO STANDARD LICENSE Substitute in standani license form (RPOP 511) the following in lieu of paragraphs B.(2), B.(3) and B.(4):

B.

(2)

Pursuant to the Act and 10 CFR Parts 30, 40 and 70 to receive, possess and use at any time any byproduct, source and special nuclear material as reactor fuel, sealed neutron sources for reactor startup, sealed sources for reactor instrumentation and radiation monitoring equip-ment calibration, and as fission detectors in amounts as required for reactor operation; (3) Pursuant to the Act and 10 CFR Part 30 to receive, possess and use at any time 100 milli-curies each of any byproduct material without restriction to chemical or physical form, for sample analysis or instrument calibration; (4) Pursuant to the Act and 10 CFR Parts 40 and 70 to receive, possess and use at any time 100 milligrans each of any source or special nuclear material without restriction to chemical or physical form, for sample analysis or instrument calibration.

r_. -,,. _ _ _ _,

. 3 ENCIDSURE 2 AIBITIm AL INF0lH EI m PEQUESTED 1.

Materials Safety Program Describe the program which will be implemented to assure the safe storage, handling and use of sealed and unsealed special nuclear, source and byproduct materials. Sections of the FSAR may be referenced to the degree they are applicable.

2.

Facilities and Equipment Describe the laboratory facilities and equipnent such as hoods, glove boxes, filters, survey and measuring instruments, and 4

monitoring devices. Sections of the FSAR may be referenced to the degree they are applicable.

3.

Personnel and Procedures 4

Describe the experience and qualifications of the key personnel responsible for handling and monitoring the materials.

Identify and sumarize the content of the radiatien safety instructions to working personnel appropriate to the operations to be covered.

Sections of the FSAR may be referenced to the degree they are applicable.

I 4.

Required Materials Provide a listing of isotope, quantity, form and use for all required byproduct, source and special nuclear materials which i

exceed the following limits:

Possession Material Pom and Use Limit 4

A.

Any byproduct, As reactor fuel; as sealed neutron As required for source and special sources for reactor start up; as reactor operaticn t

nuclear material, sealed sources for reactor instru-

)

ment and radiation monitoring equip-ment calibration; and as fission detectors.

B.

Any byproduct, Any form for sample analysis or 100 millicuries 3

source or special instruent calibration.

each isotope; any nuclear material, byproduct materia:

100 milligrams 3 isotope; any source or special nuclear material.

e Q

w

.,,.._,,w,~e,-,..e4

,e-,.w..-

vr.,_.,

,-e,,

4..-,.-

.,,-,, - --,.r e -

~

ENCIDSURE 3 1EQWICAL SPECIPTUTf51 ADDITION ADDITI(NAL SAFEIY RELATED PIANT CAPABILITIES j

(Or elsewhere, as appropriate, in Section 3)

MISCELIANEOUS RADIQACTIVE MATERIALS SOURCES Source Leakage Test Siccification Surveillance Requirement Tie leakage test shall be capable.of detecting the Tests for leakage and/or contamination shall be i

presence of 0.005 microcurie of radioactive material perfonned by the licensee or by other persons i

on the test sample.

If the test reveals the presence specifically authorized by the rammission or an of 0.005 microcurie or more of removable contamina-agreement State, as follows:

tion, it shall imediately be withdrawn from use,

]

decontaminate, and repaired, or be disposed of in 1.

Each sealed source, except startup sources accordance with Comission regulations. Sealed subject to core flux, containing radioactive sources are exempt from such leak tests when the material, other than Ilydrogen 3, with a half-source contains 100 microcuries or less of beta life greater than thirty days and in any form and/or gansna emitting material or 10 microcuries or other than gas shall be tested for leakage and/

less of alpha emitting material.

or contamination at intervals not to exceed six l

months.

i-i j

2.

%e periodic leak test required does not.

j apply to sealed-sources that are stored and i

not being used. % e sources excepted from j

this test shall be tested for leakage prior i

to any use or transfer to another user unless i

they have been leak tested within six months j

prior to the date or use or transfer.

In the i

absence of a certificate from a transferor indicating that a test has been made within l

six months prior to the transfer, sealed source shall not be put into use until tested.

i Bases 3.

Staitup sources shall be leak tested prior to TEc objective of this specification is to assure and following any repair or maintenance and that leakage from byproduct, source, and special nuclear before being subjected to core flux.

radioactive material sources does not exceed allowable limits.

ENCIDSLRE 3 OCNT'D REPORTING REQUIRBfENTS SINI-ANNUAL OPERATING REPORTS Operations Sunenary Results of required leak tests perfonned on sources if the tests reveal the presence of 0.005 microcurie or more of removable contamination.

RECORDS RETENTION

)

A complete inventory of radioattive materials in possession shall be maintained current at all times.

Records required to be maintained for five years:

~

1.

Test results, in units of microcuries, for leak tests performed pursuant to Specification 2.

Record of annual physical inventory ver,ifying accountability of sources on record.

4 4

s l.

\\

I I