Advises That Emergency Cooling Pond Design Mod Required Due to Inadequate Freeboard Allowance for Pond Dike.Measures Other than Raising Dike Height Are Acceptable Since Dike Const Is Complete
ML19326C218
Person / Time
Site: Arkansas Nuclear 
Issue date: 04/23/1973
From: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
To: Phillips J
ARKANSAS POWER & LIGHT CO.
References
NUDOCS 8004220795
Download: ML19326C218 (2)


Text

__

~

3 D'.

p r

(: :w:.

im u:

5 Docket No. 50-313 h

APR 3 1975 If:

~

IE Mr. J. D. Phillips R

Vice President and Chief Engineer R

Arkansas Power and Light Company a

Sixth and Pine Streets i

Pine Bluff, Arkansas 71601 r

Dear Mr. Phillips:

il We have completed our review and evaluation of the design of the raergency Cooling Pond for Arkansas Nuclear One - Unit 1 and have

[

concluded that some modification of the pond design is necessary

!?

before Unit 1 is licensed.

g b:.

The Emergency Pond, in conjunction with the Dardanelle Reservoir, is the ultimate heat sink for this plant. Luring the construction permit t

review for Arkansas Nuclear One - Unit 2 we agreed that the pond could be designed to withstand both the Design Basis Earthquake (DEE) and-the si=ultaneous occurrence of the Operating Basis Earthquake and one-half the local Probable FavNun Precipitation (PMP). Your analysis of this latter conbination of conditions calculated a backwater crest of 350.0 feet MSL, three feet above the top of the spillway (347 feet MSL).

The dike around the pond has its top at 351 feet MSL, affording only a foot of freeboard at the reference condition.

E E The AEC staff independently analyzed the reference condition and calculated a backwater crest of 350.3 feet MSL. thus, there is no significant difference

~

in our calculation of the crest. However, we cust question the taeager freeboard allowance associated with this crest. Our safety concern is that, with a slightly higher backwater crest, the dike can be overtopped.

This is an unsealed earthen darc which can be thereby croded. Erosion could cut away the dike, especially in the area adjacent to the spillway, down to the 341 feet MSL level, completely emptying the pond.

Our standard practice is to require a minimum of three feet of freeboard i

for small dans. For dams whera failure would cause a major hazard to the public, a minimum of five feet of freeboard is standard practice. These in practices are based on providing freeboard to compensate for (1) wind and

[:

h.:

h h

.I '

erricr >

04 220 f$

80 s ow w c >

DATE>I 1

+

nem AEC.31s (Rev. 9-53) AFCM 0240 c'.

    • 8 -51405-1 445cs
  • W v:

(

[-

Mr. J. D. Phillips DE3 l,7:

h wave action estimates, (2) errors in estimating the flood used to F

design the spillway, (3) errors in determining the discharge characteristics of the spillway, and (4) allowing for settlement of the dam over a period of time. These freeboard allowances are based on Corps of Engineers and Bureau of Reclamation criteria with which we t..

concur and which we have consistently applied at other sites.

O References include:

EC 1110-2-27, Policies and Procedures Pertaining to Determination of Spillway Capacities and Freeboard Allowances for Dams, U. S.

Army Corps of Engineers, August 1, 1966.

ETL 1110-2-8, Co=putation of Freeboard Allowances for Waves In Reservoir, U. S. Army Corps of Engineers, August 1, 1966.

Design of Small Dams (Section 136-Freeboard), Bureau of Reclamation,. 1961.

The freeboard allowance is, therefore, a design margin which should not enter into the direct water level calculation.

Tour staff has informed us that the Emergency Pond construction has been completed. This does not alter our conclusion that the present dike is inadequate. Before Unit 1 can be licensed, you will be required to 4

provide additional freeboard allowance by raising the top of the dike M

to at least 353 feet MSL. Since the pond is complete, citernate h

equivalent measures can be acceptable such as erosion sealing the dike or increasing the spilluay capacity. Please infort us within thirty (30) p days of the measures you propose to correct this deficiency.

Sincerely, h.

Cripr.tl f2r.d by R:g:r s.Scyd A. Giambusso, Deputy Director for Reactor Projects Directorate of Licensing DISTRIBUTION

??

cc:

AEC PDR AGianbusso R0 (3)

Eorace Jovell, Esquire Local PDR RCDeYoung RMBernero House. Holms and Jewell Docket JHendrie EGoulbourne 1550 Tover Building PUR-4 Reading AKenneke ASchwencer

[]

Little Rock, Arkansas 72201 RP Reading RWKlecker WGamill L Reading OGC HDenton i.

k,[

b..@.-4

.LISAB. _

..L,1AD/S S,.,,,...

,,L,:.Ap/J,p/'

RBernerd::.g...fepp cmet >

3,,,,,.,L.

1mp _

[

gk' _ Ew} m

(

'4 gav j

AS.C.hWencer[....WGami11 enton_

, RCM R Mr J.

summat >

form ALC-!Ie (Rev.9-53) MICM c240,,,,[ 4f/, e /_73 4],.;f,,/,q,

. I,f_,fgi,,f g,_,4L,f 77t,,,

37 omi. 4/,/[p3 2/,7 3,-,

f

..e en-as-sieu-s us-cs

,