ML19326C199

From kanterella
Jump to navigation Jump to search
Responds to Addl NRC Questions Re Fire Protection at Facilities.Supplements Util 770830,0921 & 1026 Ltrs. Remaining Questions Will Be Forwarded After Responses Completed
ML19326C199
Person / Time
Site: Davis Besse, Arkansas Nuclear  
Issue date: 03/31/1978
From: David Williams
ARKANSAS POWER & LIGHT CO.
To: Reid R, Stolz J
Office of Nuclear Reactor Regulation
References
1-038-18, 1-38-18, NUDOCS 8004210688
Download: ML19326C199 (28)


Text

k i

r.

  • = --

g 4

on g

,so-assMss REGULATORY INFORMATION DISTRIBUTION SYSTEM (RI I

DISTRIBUTION FOR INCOMING MATERIAL 50 j 315--

REC: STOLZ J F ORG: WILLIAMS D H DOCDATE: 03/31/78 NRC I " " " ' '":

DATE RCVD: 04/07/78 DOCTYPE: LETTER NOTARIZED: NO COPIES RECEIVED S'JBJECT:

LTR 3 ENCL 40 FORWARDING ADDL RESPONSES IN ADDITION TO THOSE CONTAINED IN APPLICANT"S LTRS OF 08/30/77, 09/21/77 AND 10/26/77 TO STAFF QUESTIONS ON FIRE PROTECTION CONCERNING BOTH ANO-1 AND ANO-2.

PLANT NAME: C,. ass - uru 1 2 4 E k'4 M 4 i AI REVIEWER INITIAL:

XJM COC:

UNIT i AENAMO O DISTRIBUTER INITIAL: R o**************** DISTRIBUTION OF THIS MATERIAL IS AS FOLLOWS ******************

NOTES:

1.

SEND 3 COPIES OF ALL MATERIAL TO I&E FIRE PROTECTION (PRIOR TO ISSUANCE OF OL).

(DISTRIBUTION CODE BOO 2)

$TC L l2. N A A FOR ACTION:

BR CHIEF kWIEu *W/ ENCL PROJ MGR MLVNCZ ^i:.4*W/ ENCL LIC ASST ef2*

' ONLY IWATDd INTERNAL:

" ' e x x u mc' NRC PDR**W/ ENCL OELD**LTR ONLY I & E**W/3 ENCL M NE M *b M ONLY hsT Nd b bkbC{NLY TEDESCO**W/ ENCL BENAROYA**W/2 ENCL IPPOLITO**LTR ONLY SKOVHOLT**LTR ONLY HELTEMES**W/ ENCL R.

MURANAKA**LTR ONLY HANAUER**W/ ENCL L(tGtO y5 Ef W4 -.

EXTERNAL:

LPDR'S IHis DOCUMENT CO S T.

JOSEPH, MI+ "A/ ENCL TIC **W/ ENCL D POOR QUEITY PAGES NSIC**W/ ENCL F ROSA **W/ ENCL W BUTLER **W/2 ENCL R EISENHUT**LTR ONLY V STELLO**LTR ONLY P COLLINS **W/ ENCL ACRS CAT B**W/16 ENCL DISTRIBUTION:

LTR 46 ENCL 36 CONTROL NBR:

c of SIZE: 1P+24P Sf 000********************************

THE END 8004210 [ M

C' O

OES$$I3.I[COS$[? R!E ARKANSAS POWER & LIGHT COMPANY POST OFFICE BOX 551 UTTLE ROCK, ARKANSAS 72203 (501)371-4000 March 31, 1978

",. V.\\j b v

1-038-18

'V

",.t 2-038-36 r

r, Director of Nuclear Reactor Regulation V b ** ",...

C3

~

ATTN:

Mr. J. F. Stolz, Chief g

Light Water Reactors Branch #1 w

U. S. Nuclear Regulatory Commission

.N iM Washington, D. C.

20555

1,

'a3 hb M

c;.'

Director of Nuclear Reactor Regulation

~S EE!

A1TN:

Mr. R. W. Reid, Chief U

N Operating Reactor Branch #4 0'

U. S. Nuclear Regulatory Commission Washington, D. C.

20555

Subject:

Arkansas Nuclear One-Units 16 2 License No. DPR-51 Docket Nos. 50-313/50-368 Fire Protection Questions (File:

2040, 1510, 2-2040, 2-1510)

Gentlemen:

Enclosed please find additional responses to staff questions on Fire Protection concerning both ANO-1 and ANO-2 These are in addition to those provided in our August 30, September 21, and October 26, 1977, letters. Responses to the few remaining ques-tions are being prepared and will be forwarded to you shortly.

Very. truly yours, c( v - I ?(

i ' t <:; _

Daniel H. Williams Manager, Licensing DHW:DAV:nf

@lg qD,4W 59 MEMBEA MICOLE SOUTH UTIUTIES SVSTEM

o o

I'1T H 2 Describe the separation of redundant safety-related cables, cable trays, and conduits.

Identify areas where redundant safety-related cables, cable trays, and conduits have non-safety-related cables interposed between these redundant groups in such a manner as to jeopardize both redundant groups by the same fire. Describe what means will be provided to prevent a fire from involving both redundant groups.

RESPONSE

(ANO-1 6 2)

A complete description of both physical and electrical separation criteria for safe-related cables, cable trays, and conduits within ANO-1 is provided in Section 8.2.2.8 of the ANO-1 FSAR.

Information concerning the physical separation criteria, regarding Fire Protection, is detailed in Section 8.3.1.4.2.2.2 of the ANO-2 PSAR. 1he remaining information requested has been provided as part of our ANO-1 and ANO-2 Fire Hazard Analysis Studies.

e 9

e o

--,-----.,-,,e--

,ey--

~ ~ -

b.

~

Item 4a Provide information that entablinhen the fire resistance

/

rating of ~ the fire barrier penetration seals to prevent the spread of smoke and fire through the barrier.

The infor-mation should.show the ef fectiveness of pipe penetrations, l.

fire doors with metal panels above the door frames, and ventilation ducts and dampers in preventing the spread of smoke and fire through the barrier.

Describe the manner in which fire and smoke are prevented from spreading from area to area-via the normal and emergency ventilation systems in all parts of the auxiliary building, fuel storage-building and reactor building.

Describe the location, actuation method and fire rating of dampers used for fire and smoke control ~in both air supply and return air systems.

Describe the details of interlocks for ventilation system shutdown or mode change that can be utilized for fire and smoke control.

Response

(ANO-1) l Materials used in fire barrier penetration seals are cellular concrete, Flamemastic 71A, Marinite 36, or Flamastic 71A mixed with Kaowool.

Cellular concrete has been approved by NEL-PIA (1973) for use in sealing penetrations in

.3-hour l

fire barriers.

Flamemastic 71A has undergone extensive testing i

and manufacturer's published information indicates that it has "... passed Factory Mutual ru+ irements and is approved

[

y for the protection of grouped insulated cables against self-l spreading fire originating within the cables or from exposure j

to an external ignition source of moderate intensity."

Mar-inite-36 carries the Underwriters Laboratories Label (Service

'Guido No. 40 U8.13) with the following Fire Hazard Classifica-tion (based on 100 for untreated Red Oak): Plame Spread... 0; Fuel Contributed... negligible; Smoke Developed... O.

Per the Interim Summary of " Interim Report, Materials Flammability Testing for Nuclear Regulatory Commission" dated April 10, 1975, Marinite-36 has also passed the specific fire tests to which it was subjected.

Kaowool is a ceramic fiber material and is used as a furnace refractory material.

Its melting point is 3200*F and it has been demonstrated to have excellent fire retardant characteristics.

l The transom panel above the door frame is a sandsich panel constructed of 2-la gauge steel face sheets with 1/4" asbestos mill board between the' face sheets and was furnished as an integral part of the fire door assembly which along with the fire door bears.the Class A label of Underwriters Labora-l tories, Inc.

-All ventilation ducts penetrating any fire barrier in the

-plant are equipped with UL listed fire dampers of the same fire rating as the fire ~ barrier.

The fire dampers are either curtain, guillotine or trap door type actuated by fusible

.d links that are designed to melt at 165'F.

On closure of the fire dampers, fire and smoke will be contained in the areas

'where~the fire occurs and prevented frsm spreading to other areas'via the ventilation system.

es

~.

,~

  • o.

. 3 All fire dampers are located in the ducts a t the penetrations through the fire barriers.

}

The fuel handling floor is served by itc own ventilation system consisting of supply and exhaust fans.

This ventila-tion system maintains a preferred direction of air flow into the fuel handling area thus preventing the spread of smoke to other areas.

The reactor building is normally isolated with limited accessibility.

Smoke spreading f rom one area to another

.within the building is not considered hazardous once the fire is put out.

The smoke may be purged out of the building by operating the purge supply and exhaust fans.

In some areas in the auxiliary building, e.g. the con-trol room, battery room, and diesel generator rooms, exhaust systems are provided which can be used to remove smoke generated in the space to the outside of the building.

The control room smoke removal is actuated by interlocks with the smoke detectors in the ventilation ducts.

The battery room exhaust f ans are operating continuously during normal operation.

The other exhaust systems are actuated manually upon alarms by smoke detectors within the r.ooms.

Response

(ANO-2)

Penetration seal materials include only those materials that have been previously tested to meet the requirements of the NEL-PIA /MARRP standard method of f ire tests of cable and pipe penetration fire stops.

Materials are exposed to the standard time-temperature curve found in ASTM E-119 for a minimum of three hours.

Tests included

-the hose stream and Materials Hazard Analysis Test.

Attached are copies of NEL-PIA letters of approval and Southwest Research Institute fire test reports which establish the three hour fire resistance rating of the seals and shows the effec-tiveness of the pipe penetration seals.

Penetration seal materials are installed in NEL-PIA approved typical confi-gurations using NEL-PIA approved proccdures.

The transom panel above the door frame is a sandwich panel constructed of 2-18 gauge steel face sheets with 1/4" asbestos mill board between the face sheets and was furnished as an in-tegral part of the fire door assembly which along with the fire door bears the Class A label of Underwriters Laboratories, Inc.

All ventilation ducts penetrating any fire barrier in the plant are equipped with UL listed fire dampers of the same fire rating as the fire barrier.

The fire dampers are either curtain, guillotine or trap door type actuated by fusible links that are designed to melt at 165*F.

On closure of the fire dampers, fire and smoke will be contained in the areas where the fire occurs and prevented f rom spreading to other areas'via the. ventilation system.

All fire dampers are located in.the ducts at the penetrations through the fire barriers.

  • +

"-v4 N4

G The fuel handling floor is served by its own ventilation system consistir.q of supply and exhaunt fans.

This ventila-tion system maintains a pref erred direction of air flow into the fuel handling area thus preventinq the spread of smoke to other areas.

Item 4b Describe the methods which would be employed for heat and smoke removal using either fixed or portable air handling equipment for each area.

Describe how exhaust and make-up air would be provided to achieve adequate air movement.

Where portable ducts are utilized, describe the route that would be used to reach the outside, the reduction in rated fan capacity because of the duct length, time required to place units in operation, and the ability of the equipment to handla high temperature gases and particulates.

Response

(ANO-1)

Smoke exhaust f ans are provided to purge smoke from the control room and computer room with ample fresh air supplied f rom adjacent areas.

The ESF pump rooms are provided with a perman fnt air purge damper arrangement to exhaust radioactive air bor ne particulate or smoke via the building ventilation exhaust system.

Automati: smoke and heat vents are provided in the turbine building roof with a minimum ratio of I sq. ft. of venting area to each 100 sq. ft. of floor area in compliance with NEL-PIA recommendations.

The emergency diesel generator rooms ventilation system as described in FSAR Section 9.7.2.1 is designed such that rapid heat and smoke removal capabilities are provided without degrading the equipment involved.

The containment building air purge, radwaste and aux il iar y building, fuel handling areas, and auxiliary building ex-tention ventilation

.haust systems remove ventilation air f rom all of their r espective essential building areas.

These filtered exhaust systems consisting of PRE, HEPA, and charcoal filter banks are provided primarily to remove airborne radioactive particulate and also to provide adequate heat and smoke removal capabilities.

The PRE-and HEPA filters are of a high temperature non combustible quality and prevent air-borne sparks from reaching the charcoal filters.

Any smoke or heat generated in any one area of the plant would be mixed with sufficient air from other areas to preclude a temperature condition at the filters in excess of their rating.

In the unlikely event that enough smoke is generated such that the filters would load up with enough combustion particulate to prevent complete smoke removal, the system can be shut down momentarily and filter modules removed to provide an open path for continued smoke exhaust. Fresh air is supplied via the building's ventilation supply air system.

De-

,S RESPONSE (ANO-2)

Smoke exhaust fans are provided to purge smoke from the control room and computer room with ample fresh air supplied from adjacent areas.

The cable spreading room is provided with a separate smoke exhaust fan system with an equivalent capability of 300 cfm per sq. ft. of gravity venting area in accordance with NEL-PIA requirements.

The ESF pump rooms are provided with a permanent air purge damper arrangement to exhaust radioactive air borne particulate or smoke via the building ventilation exhaust system.

Automatic smoke and heat vents are provided in the turbine building roof with a minimum ratio of 1 sq. ft. of venting area to each 100 sq. ft. of floor area in compliance with NEL-PIA recommendations.

The emergency diesel generator rooms ventilation system, as described in FSAR Section 9.4.2.4 is designed such that rapid heat and smoke removal capabilities are provided without degrading the equipment involved.

The containment building air purge, radwaste and auxiliary building, fuel handling areas, and auxiliary building extention ventilation exhaust systems remove ventilation air from all of their respective essential building areas. These filtered exhaust systems consisting of PRE, HEPA, and charcoal filter banks are provided primarily to remove airborne radioactive particulate and also to provide adequate heat and smoke removal capabilities. The PRE and HEPA filters are of a high temperature non combustible quality and prevent airbone sparks from reaching the charcoal filters. Any smoke or heat generated in any one area of the plant would be mixed with sufficient air from other areas to preclude a temperature condition at the filters in excess of their rating.

In the unlikely event that enough smoke is generated such that the filters would load up with enough combustion particulate to prevent complete smoke removal, the system can be shut down momentarily and filter modules removed to provide an open path for continued smoke exhaust.

Fresh air is supplied via the building's ventilation supply air system.

1 y

<s Item 4c Discuss the potential fire hazard for all types of air filters

'd including charcoal, pre-filter, high efficiency and HEPA, and describe the fire detection and suppression capability and fire prevention measures.

Analyze the effects'of a filter fire in terms of heat, smoke generation, radiation release, and damage to safety-related equipment.

For filters inside containment, analyze the potential effects of complete combus-tion on containment atmosphere and resultant effects on safety-related equipment.

Response

(ANO-1)

A detailed description of the ANO-1 plant ventilation filtra-tion systems consisting of pre-filters, HEPA filters, and charcoal filters is contained in FSAR sections 6.5 and 9.7.

Pre-filters are qualified as U.L. Class I.

All HEPA filters are of non-combustible construction.

Each HEPA filter is f abricated by pleating a continuous sheet of molded glass medium back and forth over itself and enclosing it in a steel frame.

The filter medium is a fire resistant glass fiber which meets the requirements of Military Specification MIL-F-51079A.

The charcoal filters are housed in heavy gauge metal enclosures.

During normal operation of any of the filter trains, the air flow is suf ficient to dissipate decay heat and prevent the charcoal from reaching the ignition temperature (approximately C) 680*F).

The ventilation air from the fuel handling, radwaste, and other potentially contaminated areas in the auxiliary building is exhausted through multi-filter units comprising two vane axial type fans each, one of which serves as standby, a visual tem-perature indication, and motor operated isolation dampers at each end of the filter train.

The standby exhaust fan provides reliability by ensuring continuous ventilation of the areas, and air flow through the filters to ptevent overheating of the charcoal.

The ventilation exhaust air from the fuel handling and radwaste areas is monitored for gaseous and particulate radioactivity as described in FSAR section 11.24.6.

The radiation levels are indicated, recorded and alarmed in the control room.

In the event of high radiation the operator can stop the respective ventilation system and isolate the multifilter unit by means of control switches located in the control room.

Any radioac-tivity products of combustion can then be contained within the filter housing.

Additional multi-filter units are used in the containment purge system, in the control room emergency air filter system, in the penetration room ventilation system and in the hydrogen

,)

purge exhaust system.

(~'

e The purge system ( for containment accessibility) is similar to that of the fuel handling and radwaste areas except that it has only one exhaust fan and is not normally in operation.

Filtration of the air inside the control room is accomplished by an emergency air filtering system consisting of two redundant filter trains with Alison Controls line type thermal detectors as an integral component of the charcoal filter.

Line type thermal detectors are dual set point alarming at abnormal tem-perature and also excessive temperature rise prior to reaching the ignition temperature of the charcoal.

Upun alarm indicating abnormal temperature, the operator can stop the respective filter system and isolate the multi-filter unit by means of control switches located in the control room.

Under these conditions the standby emergency filtering system will be started.

Air leakage into each of the penetration rooms is discharged to the containment flute (vent) through a pair of multi-filter units (one standby) containing Alison Controls line type thermal detectors as an integral component of the charcoal filter.

Line type thermal detectors are dual set point alarm-ing at abnormal temperature and also excessive temperature rise prior to reachina the ignition temperature of the char-coal.

Upon alarm indicating abnormal temperature, th'e operating system can be shut down and isolation valves on the inlet and outlet of the filter unit closed.

The standby syste' will then be started and a normally closed valve opened t; allow

)

adequate cooling air from the operating unit to bypass through the idle filter unit to prevent reaching the ignition temper-ature of 680*F.

The hydroger. purge system exhausts the containment building atmosphere 3 days af ter a LOCA through a non-combustible HEPA filter and an impregnated charcoal adsorber via a Nash water ring vacuum pump.

Any heat and/or smoke generation is absorbed in the vacuum pump water. seal ring to minimize radiation re-lease.

These multifilter units are isolated by shutoff valves during normal plant operation.

In the event of a power failure to any of the air filter system fans, the associated filter train will be isolated automatically.

In the unlikely event of a fire resulting from charcoal ignition, the affected air filter system can be isolated, thus confining the fire to within the housing.

How-ever, the fire propagation within the charcoal filter will be extremely slow if not retarded since charcoal has rather poor thermal conductivity, and is tightly packed in the filter beds.

Additionally, those streams from the wet stand pipe

' fire protection systems can be used to control propagation of the fire and to provide ultimate extinguishment.

J m

~

p Inside the containment, the containment cooling systems are equipped with pre-fi.cers.

There are no other air filters q'j in the containment.

The pre-filters are UL Class I qualified and will not support combustion.

The potential effects of combustion on containment atmosphere or resultant effects on safety-related equipment are therefore negligible.

Response

(ANO-2)

A detailed description of the ANO-2 plant ventilation filtr a-tion system consisting of a pre-filter, a HEPA filter, and a charcoal filter is contained in FSAR sections 6.5 and 9.4.

All pre-filters are qualified as UL Class I.

All HEPA filters are of non-combustible construction.

Each HEPA filter is f abricated by pleating a continuous sheet of molded glass medium back and forth over itself and enclosing it in a steel frame.

The filter medium is a fire resistant glass fiber which meets the requirements of Military Specification MIL-F-51079A.

The charcoal filters are housed in heavy gauge metal enclosures.

During normal operation of any of the filter trains, the air flow is sufficient to dissipate decay heat and prevent the charcoal from reaching the ignition temperature (approximately 680*F).

The ventilation air from the fuel handling, radwaste, and other potentially contaminated areas in the auxiliary building is exhausted through.multifilter units comprising two vane axial type f ans each, one of which serves as standby, a visual tem-perature indication, and motor operated isolation dampers at each end of the filter train. The standby exhaust fan provides reliability by ensuring continuous ventilation of the areas and air flow through the filters to prevent any overheating of the charcoal.

The ventilation exhaust air from the fuel handling and radwaste areas is monitored for gaseous and particulate radioactivity as discussed in FSAR Section 11.4.

The radiation levels are indicated, recorded and alarmed in the control room.

In the event of high radiation, the operator can stop the respective ventilation system and isolate the multi-filter unit by means of control switches located in the control room.

Any radio-active products of combustion can then be contained within the filter housing.

Additional multi-filter units are used in the containment purge system, in the control room emergency air filter system, in the penetration room ventilation system and in the hydrogen purge exhaust system.

]

p The purge system or containment accessibility is'similar to that of the fuel handling and radwaste areas except that it j

has only.one exhaust fan and is not normally in operation.

Filtration of the air inside the control room is accomplished by an emergency air filtering system consisting of two redun-dant filter drains with Alison Controls line type thermal detectors as an integral component of the charcoal filter.

Line type thermal detectors are dual set point, alarming at abnormal temperature and also excessive temperature rise prior to reaching the ignition temperature of the charcoal.

Upon alarm indicating abnormal temperature, the operator can stop the respective filter system and isolate the multi-filter unit by means of-control switches located in the control room.

Under these conditions the standby emergency filtering system will be started.

Air leakage into each of the penetration rooms is discharged to the containment flute (vent) through a pair 'of multi-filter units (one standby) containing Alison Controls line type thermal detectors as an integral component of the charcoal filter.

Line type thermal detectors are dual set point alarming at abnormal ~ temperature and also excessive temperature rise prior to reaching the ignition temperature of the charcoal.

Upon alarm indicating abnormal temperature, the opera' ting system can be shut down ;and isolation valves on the inlet and outlet of the filter unit closed.

The standby system will

.d then be started and a normally closed valve opened to allow adequate cooling air'from the operating unit to bypass through the idle filter unit to prevent reaching the ignition tem-perature of 680*F.

The hydrogen purge system exhausts the containment building atmosphere 3 days after a LOCA.

These multi-filter units are isolated by shutoff valves during normal plant operation.

The ANO-Unit 2 hydrogen purge system utilizes a non-combustible HEPA filter and a non-combustible Silver Zeolite adsorber to remove radioactive contaminants.

In the event of a power failure to any of the filter system fans, the associated filter train will be isolated automatic-ally.

In the unlikely event of a fire resulting from charcoal ignition, the'affected filter system can be isolated, thus con-fining the fire to within the housing.

However, the fire pro-pagation within~the-charcoal filter will be extremely slow if not retarded since charcoal has rather poor thermal conduc-tivity, and is tightly packed in the filter beds.

Additionally, those streams from the wet stand pipe fire protection systems can be used to control propagation of the fire and to provide ultimate extinguishment.

J y

.-.. -. :~ - n

. - - - - ~.

=

.m Inside the containment, the containment cooling systems are equipped with pre-filters.

There are no other air filters in the containment.

The pre-filters are UL Class I qualified and will not support combustion.

The potential effects of combustion on containment atmosphere or resultant effacts on safety-related equipment is therefore negligible.

.n

~ - - - - ~ ' -

'~*

~~

Item 9b I-Describe 'the location of detectors in the control room ceiling space and the air flow patterns to show the adequacy of these detectors to detect fires in the control cabinets open to the ceiling space.

Response

(ANO-1)

There are five ionization and two heat actuated detectors equally. spaced above the suspended ceiling to detect any fire in that space.

A fire barrier is located just above the sus-pended ceiling which isolates the cable area from the control room below.

The ceiling space is not ventilated.

However, for control cabinets that are opened to the ceiling, exhaust ducts are connected directly to the cabinets for normal cooling.

A smoke detector is located in the exhaust duct to detect any fire that may occur in the cabinets.

Response

(ANO-2)

There are six ionization type detectors located in the space above the suspended ceiling, three on the west side and three on the east side, to detect electrical fire in that space.

All electrical cables located in the space are run through covered cable trays and enclosed conduits.

No ventilation is provided in the ceiling space.

For control cabinets that are opened to the ceiling, exhaust ducts are connected directly to the cabinets for normal cooling.

Two smoke detectors are located in the exhaust duct to detect any fire that may occur in the cabinets.

.._n,.,

-r n

... ~.

G r,

ITEM 10 A Identify all areas not provided with detection and automatic sprinkler protection:

1) where both safety related equipment and open cable trays exist, or 2) where there are safety related cables in open cable trays.

In these areas, justify the lack of detection and automatic sprinkler suppression.

RESPONSE ANO-1 6 2 These areas are identified in the Fire Hazards Analysis Supporting Information submitted on February 28, 1978. The justification for the lack of detection and/or autcmatic sprinkler protection is based on the acceptability criteria applied to the redundancies involved or the total lack of redundant circuits.

ITIM 10(b)

Justify the lack of automatic fixed sprinkler suppression in the switch-gear rooms to protect exposed safety related cables and cables of both redundant divisions.

~

RESPONSE ANO-1 North and South switchgear room - Zone 99-M, 100-N The heat load in these zones is low and most all circuits are in conduit.

The possibility of a fire damaging redundant circuits is remote, however, due to the consequences of loss, from an equipment protection standpoint, modifications have been proposed for these zones.

p

^

l'ITJ! 12 (a)

Describe the routing of all piping containing flammable or combustible liquids or gases and evaluate the potential hazard to safety related equipment.

RESPONSE ANC-1 The following are the types of combustible liquids and gases at ANO-1:

hydrogen, lube oil, and diesel fuel oil. Ilydrogen and lube oil are used in the turbine and turbine auxiliary buildings.

In these areas there are no potential hazards to safety related equipnent.

Inside the reactor auxiliary building, the pipe routing of hydrogen to the reactor coolant makeup tank is through areas containing the emergency feedwater pumps and the primary makeup pumps.

The only potential ha urd will be when the hydrogen supply line is being pressurized. An operator will be available to isolate the line if the pressure were.to change indicating a line rupture. Normally once a day hydrogen is supplied on a batch basis at 20 to S0 psi and when the desired pressure is reached, the hydrogen manifold is isolated. Due to the small amount of hydrogen that would be in the supply line and the ventilation in the area, the probability of an explosion is very small.

Although the primary makeup pumps are in the vicinity of the waste gas decay tanks which normally contain some amount of hydrogen, the tanks are regularly monitored to control the amount of oxygen to prevent an explosive mixture from developing.

The diesel fuel oil supply to the emergency diesel generators is routed underground to the diesel generator rooms. The lines do not pass through other areas of the plant.

If one of the fuel oil supply. lines were to rupture neither, the redundant diesel generator nor any other safety related equipment would be affected.

RESPONSE ANO-2 The following are the types of combustible liquids and gases at ANO-2; hydrogen, lube oil, and diesel fuel oil. Ilydrogen and lube oil are used in the_ turbine building.

Lube oil is also used in the turbine auxiliary build-ing.

In these areas there are no potential hazards to safety related equip-ment.

!!ydrogen is piped into the reactor auxiliary buidling for use in the volume control tank. The hydrogen is not of a potential ha:ard to safety related equipment where it is piped.

There is a possibility of hydrogen buildup in the waste gas decay tanks.

The tanks are monitored to. prevent the accumulation of oxygen that could cause an explosive mixture.

-~

,. - - -.. +

4.

a p

~

The diesel fuel oil supply to the emergency diesel generators is routed underground to the diesel generator rooms. The lines do not pass through other areas of the plant.

If one of the fuel oil supply lines were to rupture, the redundant diesel generator would not be affected nor would

- any other safety related equipment be affected.

I h.

o E

9 k

4 4

1 e

e 9

.-c.

...mv" r wr n -

--*-e--r-e-

-=--w' m-----

  • i~yv--e r'

'-- - -' e

-++ *w v

. ('\\,

'~

r ITEM 12(b)

Describe the hydrogen system used to scavenge oxygen from the main coolant.

Also, describe: (1) frequency of use; (2) provisions for inerting; (3) alarms or indications on loss of flow or pressure; (4) hydrogen detection or a ventilation monitoring system for the make-up tank roon; (5) the routing and protection of hydrogen lines to minimize susceptibility to damage; and (6) the provisions to cut off hydrogen flow.

RESPONSE ANO-1 6 2 Hydrogen bottles feed into a header which is piped to the Reactor Coolant Makeup Tank (on Unit 2 named the Volume Control Tank) for a hydrogen blanket on the primary coolant systen. The blanket is maintained by a batch basis of hydrogen supply when the pressure becomes low.

Usually, this occurs up to once a day. A removable spool must be inserted to allow nitrogen supply to the makeup tank (or VCT) for inerting of the tank blanket space. This is required to prevent inadvertant nitrogen addition rather than hydrogen during operation of the plant. The hydrogen piping is generally routed well above the floor to prevent damage from passing traffic.

With the hydrogen being supplied on a batch basis, an operator opens a valve at the hydrogen bottle manifold and allows the pressure to the. makeup tank (or VCT) to reach a desired pressure (usually 20 to 50 psi). Once this pressure is reached, the hydrogen bottle manifold is isolated. Check valves are provided at the makeup tank ( and VCT) which will prevent the flow of hydrogen away from the tank if the supply line were to rupture. There fore,

due to the small volume of hydrogen that would be released from the hydrogen supply line if it ruptured, there is no potential ha:ard to safety related equipment.

1 i

L_

u m~s as-,

v.

+w

= - - -

,m

)

ITEM 17a a)

Provide an analysis of the potential for a fire to disable both service water systems. The analysis should include postulated fires in the following area:

(1) inside the intake structure where pumps, valves and cables are located; (2) in the cable

. tunnels leading to the intake structure (these tunnels contain cable in PVC conduit); and (3) in the auxiliary building where the cable runs from the tunnel to the switchgear rooms.

RESPONSE (ANO-1)

The analysis requested was performed in the Fire Hazards Analysis.

The results indicated the possibility of loss of both SW trains in the mentioned areas to be small.

ITEM 17b b)

Drawings indicate a cross-over between the two tunnels at the intake structure.

Provide an analysis of the potential for a single fire to damage cables in both tunnels at this cross-over.

RESPONSE (ANO-1)

To our knowledge, there is no cross over between the two tunnels at the intake structure.

~ _ _... _.

t

}

l ITEM 20a a)

' Describe the routing of redundant safety-related electrical wiring between the cable spreading room and the switchgear rooms. Provide an evaluation of the potential for a fire in one switchgear room cabling to both redundant safety divisions.

RESPONSE (ANO-1)

The. routing of redundant safety-related electrical wiring between the cable spreading room and the switchgear rooms is shown on the attached electrical drawing E669. The requested analysis has been perfonned and submitted with the Fire Hazards Information.

i G

4 l

gg ITEM 23-Provide a list of all areas containing equipment essential for safe shutdown which do not have fire detection and justify the lack of

-fire detection.

RESPONSE ANO-1 6 2 All areas of ANO have been analysed as requested and the results of that analysis has been subritted as part of our Fire Hazards Information.

For these areas acceptable without fire detection, the lack of detection is justifable by the acceptance criteria applied to each zone and the

. extremely low probability of fire destroying redundant trains.

7 1

1 1

i 1

1 i

~.

~

~

( -)

ITEM 24 The air compressor room adjacent to the turbine building contains some cables of both redundant divisions; no fire detection or

- automatic suppression means have been provided.

Describe the effect on safe shutdown capability of a fire in this room.

RESPONSE (ANO-1)

An analysis has been performed in this~ area and results and justification I

have been submitted with our fire hazards information.

4 4

Y

{

e i

t

-.m 4+ = -

-me.ep

()

IE M 26 Provide the basis for your statement in IV b.1(d) of your submittal that insulation, shielding and sound-proofing materials are non-combustible.-

RESPONSE

(ANO-1)

All insulating, shielding and sound-proofing materials used within ANO-1 have been fabricated from ncn-combustible materials as detailed below. Pipe insulation is either calcium silicate or fiberglass with an aluminum or stainless steel protective jacket. Shielding materials are either lead, concrete or steel. All sound-proofir, materials with-in the plant consist of either gypsum board or epithesa mineral fiber.

l

l'

'. )

Item 34 e r g i Item IV.C.2(a) states that NFPA 24 was used as a guide in designing and installing the fire protection water supply system.

identify NFPA requirements which are not met by the fire protection water supply system, and justify not meeting these requirements.

Response

(ANO 1 & 2)

An underground yard fire main loop consisting of 12" cast iron pipe internally lined (in accordance with ANSI A21.4),

with approved sectional valves, hydrants and hose houses was put in service after it had been tested and met the applicable requirements of NFPA 24, " Standard for Outside Protection", and was accepted by the Nuclear Energy Liability -

Property Insurance Agency.

I ITEM 35a a)

State whether inside hydrants, hose couplings and stand pipe risers are compatible with those of local fir'- departments.

RESPONSE ANO-1 6 2 Inside hydrants, hose couplings and stand pipes are compatible with the equipment used by the Russellville Fire Department.

ITEM 35b b)

Describe the provisions for equipping the hose houses on the plant yard loop with 2-inch lined fire hose.

RESPONSE ANO-1 4 2 All hose houses on the ANO-1 plant yard loop are equiped with 2 inch fire hoses. All hose houses on the ANO-2 plant yard loop are or will be equiped with 2 inch fire hoses.

3 e-m eA

<em--

--*+g,-


.----.-.w.

=_

m-w -*- - +

C ITEM 44 Assuming a fire at the penetration areas inside of the Reactor Building, identify the potential consequences on safe shutdown, decay heat removal, and containment.

RESPONSE: ANO-1 6 2 H e requested analysis was performed in the Fir: "azards Analysis. The consequences were determined to be acceptable. In addition, each of the areas is protected by an automatic sprinkler system.

^

ITEM 46 Provide a specific analysis of the potential for and consequences of a fire in the safety-related pump, reactor fuel storage, and radwaste areas. You may reference specific portions of your response to the NRC letter of 10/21/76 if the areas above have been discussed in detail in that resonse.

RESPONSE ANO-1 6 2 The requested analysis-was performed in our Fire Hazards Analysis and has been submitted. 'Ihe potential and consequences of a fire was determined r.:ceptable.

t 5

^ * ' ~ * ~ ^ ' *

  • ':" ' ^

~

^.'"

^

.s IT11M 60 Identify areas containing significant quantities of combustibles in which a fire could affect safety-related equipment and also cause the manual hose stations for these areas to be inaccessible due to smoke and heat.

Show that these areas can be reached with an alternate hose.

RESPONSE: ANO-2 1he combustibles located in each fire zone have been identified in the Fire Hazards Analysis and have been submitted. No credit was taken in the Fire Hazards Analysis for use of r manual hose stations.

e O

I i

l

-~

m,

^

)

ITEM 63

'l Describe the potential for a fire in the Core Protection Calculators I

dausing the loss of capability to trip the reactor manually or from other automatic input than the Core Protection Calculators.

i RESPONSE ANO-2 h e manual initiation of a reactor trip via the Reactor Protective j

System (RPS) is independent of the Core Protection Calculators (CPC's).

herefore, a fire in the 2C15 cabinets (Core Protection Calculators) i l

would not degrade the manual trip capabilities of the Reactor Protective System (RPS).

I O

+ amo es

.. - ~.

}

ITEM 71 Identify the quantity of emergency breathing units, number of spare air bottles, and capacity of the recharge capability to be available onsite.

RESPONSE

(ANO-2)

There are normally 29 emergency breathing units and 18 spare air bottles onsite at all times. Recharge capability is provided by ten 300 cubic foot breathing air cylinders. Additionally, a portable breathing air compressor with a capacity of 7.5 cubic feet per minute at 2200 psi is available to charge the spare air cylinders.

This portable' compressor is capable of being moved to the Emergency Control Center where power will be available to it should it's normal power source not be available.

ITEM 72 Verify that fire dampers will be located in all ventilation duct penetrations of fire barriers.

RESPONSE

(ANO-2)

A study has been conducted for ANO-2 to verify that fire dampers are provided for all ventilation ducts penetrating a fire barrier.

The results indicated a small number of cases where fire dampers had not been specified.

In each case, a fire damper will be provided prior to fuel load so that every ventilation duct penetrating a fire barrier will be provided with a fire damper.

s

__?_

~--

~-

... _....