ML19326A096

From kanterella
Jump to navigation Jump to search
Responds to AEC Re Violations Noted in Insp Rept 50-346/74-07,supplementing Util .Corrective Actions:Grounding Sys for Cable Tray Carrying Class 1E Circuits Subj to Insp
ML19326A096
Person / Time
Site: Davis Besse 
Issue date: 01/23/1975
From: Roe L
TOLEDO EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML19326A091 List:
References
NUDOCS 8001310661
Download: ML19326A096 (1)


Text

.

n U

(b

\\

TV1EDO EDISON January 23, 1975 Donket No. 50-346 Mr. James G. Keppler Regional Director, Region III Directorate of Regulatory Operations Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Mr. Keppler:

We have further reviewed your letter of December 3,1974, concerning findings of site inspection and my letter reply of January 6, 1975, and hereby amend my letter as follows:

p-s Item A Instructions or procedures for final inspection of cable tray activities - Criterion V.

4 The installed grounding system for cable tray carrying class lE circuits will be subject to completion inspection in accordance with i

approved inspected procedures and inspection documentation.

This inspection will include verification of proper ground cable, cable continuity, proper use and installation of cable-tray connections and proper connection of ground cable to building steel and/or station ground system.

If ycu have any questions concerning this matter, we will be glad to discuss them with you.

1 Yours truly, I

A L. F. Roe Vice President - Facilities Development LER/jy O

8001310fs/

U i

THE TCLEDO EDISON COMPANY EDISON PLAZA 300 MADISON AVENUE TOLEDO. OHIO 43552