05000219/LER-1980-018-03, /03L-0:on 800507,during Monthly Surveillance Testing of Reactor High Pressure Scram sensors,RE03D Found to Be Less Conservative than Specified.Caused by Sensor Repeatability.Sensor Reset

From kanterella
(Redirected from ML19323H658)
Jump to navigation Jump to search
/03L-0:on 800507,during Monthly Surveillance Testing of Reactor High Pressure Scram sensors,RE03D Found to Be Less Conservative than Specified.Caused by Sensor Repeatability.Sensor Reset
ML19323H658
Person / Time
Site: Oyster Creek
Issue date: 06/05/1980
From: Ross D
JERSEY CENTRAL POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19323H655 List:
References
LER-80-018-03L, LER-80-18-3L, NUDOCS 8006160021
Download: ML19323H658 (3)


LER-1980-018, /03L-0:on 800507,during Monthly Surveillance Testing of Reactor High Pressure Scram sensors,RE03D Found to Be Less Conservative than Specified.Caused by Sensor Repeatability.Sensor Reset
Event date:
Report date:
2191980018R03 - NRC Website

text

a.no a

LICENSEE EVENT REPORT 00r.TactaLocoi l

l l

l

]@

(PLE ASE PRINT oR TYPE ALL REQU RED INFORMATION)

{c i t l l NI JI O l C ! P i l l@l 0101 -l O I 0 l 0 I O 10 l-Io lo l@l k l 1111 i l l l

l@

8 7 L.:Efd3EE :::(

to IS 61CEN5t Nwwe ta 25

6 usetN54 TYPt 43 57
a7 54 cc n't Ioitl

,D*jlL @!015!010 10 12 11 9 }@l01510171310 }@l016101gI310l@

?

8 60 4:

ocxgT Nyug ge 68 69 EVENTATg 14 75 REPCRT CATE 8J EVEN T DESCAIPTION AND 8AC8ASLE CONSECUENCES h

!: i: i I On May 7, 1980, while cerformina monthly surveillance testino of the l

60 3,

I reactor high oressure scram sensors, RE030 was found to be less conserv-I i3 ij i ative than specified in the Technical Specifications. The safety I

j e is; ;

significance of this event is considered minimal since RE030 would have i

actuated, but rt a pressure 9 psig higher than the crescribed value of l

ge,a,

1066 psig. A redundant sensor in the same system would have actuated at

[

the desired pressure.

l

,3,,,

i:

g 9 C

=0MP.

VALVE su.ALSI Sv5T E M AUSE e:::

,.e,:Nsm ::::

sus::::

i: i9i i s i s l@ lx i@ lZ l@ l il Ni si r; R lu l@ l sl@ j Zl@

3 13 11 12 1

18 f9

0 St OU E NT! AL OC LaAENet At* AT
  • EVISicN
,g s ac f VENT vf A4 4 tP RT NC.
E TYPE N O.

Q),(tag l:, S l o f l_l l 0! 113l l/l 10 l 3 l lLl l_l l0l 2:

2
4 a
r
s
s
o si 2:

a:*':N su' Vat isat:*

Sau?:CWN AT*A:HMENT N880 4 881ME C:MP.

MPCNENT T24:9 *: :09
NetANT vame:
- cuas suewT scau ws.

suessi ta vaNusa: Tune =

l E }gl34Z ig l;5Z g l26Zl@ l 0] O! 0 l

l Y lg l2 Yl g lX lg l S l 016 l 9 [g-41 40 al 4

43 44 47 AU$i CESOAl8TICN ANC CO A AECTiVE A0TICNS @

j iail The cause of switch RE03D tricaine at 1075 osia is attributed to sensor I

l.ij i repeatabliity. The reactor high oressure scram senser was reset to trio with-t

,,,,j l in the prescribed 1imits.

l

!1 43i !

l 1!

lii 4 so 7

8 3 MEWCD OF a acitiry

$7 Afb 5

  • 4*C*lm QTwf R STATUS Dise:v E A Y
i$c VERY:ES:miPT!ON

.2 NA l

lBI@l Monthly surveillance Test l

li i s l lH l@ lO!0l0l@l 80 AhviTv C NTENT atLEAst P M E'.t AJ E AMcVNT of A TIVtTV LCCAftCN CF RELEASE liisJlZl@: 12!@l l

l NA 1

NA 7

8 9 to it 44 45 go egal:NNEL EXPC5yngs Nuv8E4 Tvee

gs mip7
q -

l lt i7i l 01 01 0 l@l Z l@l NA

  • ta50NNELINJua t$

NLvsta OtsR:PTICN u

l [iiu.! 10 10 10 l@l 7

6 9 11 12 go lot $ # 04 QAvaCE TO FAC&LITY Q Tvet OESAseT'CN

%./

NA

]

l t i 91 l Z l@l f

e 9 1:

go IS:($* pip *lON

,gg7g I

ve.u v %.-

=e m I

!Iiiiiii!Iii I?

l::al 1 G8 69 gg.

s a g 10 hgg-879h

[

Donald A. Ross

,wONE:

s o o n s o odVE OF **E8AAE A N

i 3

Jersey Central Power & Ught Cornpany F

Mad: son kvenLe at PurCrecM Pead Morns:Cwn New Jersey 07360 201 539-6111 OYSTER CREEK NUCLEAR GENERATING STATION Forked River, New Jersey 08731 Licensee Event Report Recortable Occurrence No. 50-219/80-18/3L Recort Date June 5, 1980 Occurrence Date May 7, 1980 identification of Occurrence Reactor High Pressure Sensor RE030 trip setting was discovered to be greater than 1060 PSI.

This event is cons:dered to be a reportable occurrence as defined in the Techni-cal Specifications, paragraph 6.9.2.b.1.

Conditions Prior to Occurrence The plant was shutdown for a refueling / maintenance outage.

The reactor cavity was flocded.

The reactor was subcritical.

The reactor mode switch was locked in the SHUTDCWN position.

Descriotion of Occurrence On Wednesday, May 7, 1980, at approximately 0117 hours0.00135 days <br />0.0325 hours <br />1.934524e-4 weeks <br />4.45185e-5 months <br />, while performing mc.'thly surveillance testing of the reactor high pressure scram sensors, RE030 was f ound to be less conservative than that specified in the Technical Specifications.

Tests on all reactor high pressure switches revealed the following data:

Pressure Switch Desired Desionation Set Point As Found As Left System 1 RE03A 1068 1066 1066 RE03C 1066 1066 1066 System 2 RE038 1068 1068 1068 RE030 1066 1075 1066 Jersey Ce-trai Power & Lg-t Ccmea y s a vem:er cf " e Gereal muche '.;tir es System

r O

Repor' table Occurrence No. 50-219/80-18/3L Page 2 June 5, 1980 Aooarent Cauce of Occurrence The cause of switch RE030 tripping at 1075 PSIG is attributed to sensor repeat-ability.

Analysis of Occurrence RE03D pressure switch would have actuated but at a pressure 9 PSIG greater than it's prescribed value of 1066 PSIG. The only safety significance of this event was the loss of redundancy in the pressure switch actuation at the prescribed set point.

j

Corrective Action

Reactor high pressure sensor RE030 was reset to trip within the prescribed limits.

i Failure Data Barksdale Pressure Actuated Switch Switch #82T-Al2SS Proof 1800 PSI l

Adjustable Range 50-1200 PSI i

l i

e