RO 50-219/80-20-1P:on 800605,following Insp of Fire Barrier, Several Penetrations Found in Degraded Condition.Caused by Delay in Performing Further Fire Watches Attributed to Personnel Error.Fire Watch Being Conducted
ML19323H266
Person / Time
Site: Oyster Creek
Issue date: 06/06/1980
From: Quintenz T
JERSEY CENTRAL POWER & LIGHT CO.
To:
Shared Package
ML19323H263 List:
References
NUDOCS 8006120297
Download: ML19323H266 (2)


Text

Initicl Tolephone Cate of Report Date:

June 5. 1980 Occurrence:

June 5.1980 Initial Writtan Time of Report Date:

June 6,1980 C -. e..r.e:

1400 O

oysTtR cRetx.oanna sEns Tn.G STATIM FORKED RIVER, NEM JERSEY 08731 Reportable Occurrence Report Es. 3>-219/80-20-l P 2

~

IDENTIFICATItN Violation of the Tecturical Specfficatfons, paragrek112.E.1_

CF nrr m war *:

and 3.12,E,2 when it was discovered fire barriers protecting safety related areas were not intact.

This event is considered to' be a reportable occurrence as defined in the Technical Specifications, paragraph 6.9.2.a.2 conoITicus PRIOR Steady state Power Routine Shutdomm TO nerm o w r-Hot Standby Operation Cold Shutdote Load Changes During X

Refueling Shutdous Routine Power O Routine Startup Other (Specify)peration Operation PTant si for refueling operations.

DESCRIPTI(M On Thursday, June 5,1980, following inspection of fire.

OF nrrtme M :

barriers pentacting safety related areas, it tes reported that several gpirations were found in a degraded condition.

The -

purpose of the inspection was to formulate a survefilance pr~ % for the inspection of the necessary fire barriers.

The condition of the barriers which raised concern was:

1)

One conduit penetrating the barrier beemeer the

, cable spreading room and the control roca had not heen sealed around its exterfor.

2)

Several conduit prestrations had not been sealed at the open and is the control roomt where wires entered the panels.

3)-

A cable penetration of the C Eattery Rcan was found not to be sealed.

Am iaspe: tion of all areas of concern was completed at apprartmetely 1430 hours0.0166 days <br />0.397 hours <br />0.00236 weeks <br />5.44115e-4 months <br /> following the df-+

The newt tospectfan of the areas was not conducted until 1120 hours0.013 days <br />0.311 hours <br />0.00185 weeks <br />4.2616e-4 months <br /> on June 8,1980.

Fire etch patrols were, therefore, not conducted every 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> as required by the Tech. Specs.

1 i

8006120 N S

l Reportchle Occurrence Page 1 Report No. 50-419/80-20-1P APPARENT CAUSE Design P m cadure y nrrt wesurr.

Maserfecture Unusual Service l

Candities Installation /

Inc. Esytrasmientel' i

Construction Campanent Failure I

Operator X

Other (Specffy) l The casse of this occurrence is under investigaties.

l l

The delv fa perfonsiisc further fire ustches fa the areas of concern can be attr'buted to personnel error.

ANALYSI5 F Degraded fire horriers reises the concorr. of the passible nrrransary.

spread of a fire fr se one area to ancther. The panels to.

the control reen costeining safet;y related agaipment would be of special concam. Adagssta manuaT1y operstad fire suppression ogs1puent is aveflaiele to contain a fire should it develop.

t 7.

1 CIERECTIVE Corrective action cancerning the conduit penetredens and ACTIIM:

the cable penetration of the bettery man will he pursued as appropriate. A fire match of the areas of concera is betag l

conducted until the barriers are either rapstred cm a condition that.is acceptable, or their condities is qualfff ad as meeting the appropriate ragsfreensts.

g g

x

^.

FAIL!stE DEtk mot applicable.

,[