e T:I: phone 6l7 366-90ll Q

DG 710-300-0729 YANKEE ATOMIC ELECTRIC COMPANY UN'-s2 20 Turnpike Road Westborough, Massachusetts 01581

.Yamnus

.bne 5, 1980 United States Nuclear Regulatory Commission Washington, D.C. 20555 Attention:

Division of Licensing Mr. Dennis M. Crutchfield, Chief Operating Reactors Branch #5

References:

(a) License No. DPR-3 (Docket No. 50-79)

(b) USNRC Letter to YAEC, dated March 28, 1980 (c) YAEC Letter to USNRC, dated February 28, 1978 (d) YAEC Letter to USNRC, dated February 14, 1979 (e) USNRC Letter to YAEC, dated February 15, 1980 (f) YAEC Letter to USNRC, dated May 1, 1980 (g) YAEC Letter to USNRC, dated September 12, 1973 (h) USNRC Letter to YAEC, dated April 18, 1980

Dear Sir:

Subject:

Environmental Qualification of Electrical Equipment In reference (b), each SEP license was asked to perform a review of their safety related electrical equipment against the guidelines furnished in that letter. YAEC has already completed an extensive review of its safety related equipment and submitted this review in Reference (c). The review was subsequently updated and resubmitted in Reference (d). We have not received any comments from the NRC on the contents of this report and feel that it had adequately addressed all the concerns for environmental qualification of electrical equipment and met the guidelines provided.

In response to the request of Reference (e), we have reviewed the previously submitted equipment list using the new guidelines furnished in Reference (e).

Enclosure A is the new master equipment list which takes into account the new guidelines for identifying electrical equipment and incorporates equipment added or changed as a result of system modifications made at the Yankee Rowe Plant since the earlier submittals. Equipment added strictly in response to TMI Lessons Learned Short Term Requirements and audited by the TMI review team has not yet been listed but will be included in the next revision.

In reference (f), we submitted the data necessary for the calculation of the containment pressure and temperature decay time as requested in Enclosure 2 of Reference (b). Enclosure 3 of Reference (b) requested information necessary for review of plant spccific containment analyses. This information is provided in Enclosure B of this letter. This scoping analysis is being used in determining the service environments for equipment inside the containment until a more detailed analysis is performed as discussed in Enclosure B.

8 0 0 6110 / ~)'i)

~

U. S. Nuciccr R:gultt:ry Commiccion Juna 5,1980 i

Att:nticna Mr. Dennis M. Crutobrisld, Chict Paga 2 For high energy line breaks (HELB) outside the containment, we have submitted in Reference (g) a supplementary report on the effects of pipe breaks outside the containment. This report did not address the environmental effects of such breaks. To address these effects, our approach is to identify the breaks that can affect the safety related equipment required to mitigate the consequences of the break from an environmental viewpoint. In such cases, we are planning to implement localized leak detection in conjunction with in service inspection to give advanced warning of impending pipe breaks. This would allow the plant operators sufficient time t6 bring the plant to a stable condition prior to a possible line break. This el'iminates the need to perform a detailed analysis of the environmental effects of a line break outside containment and to qualify electrical equipment to withstand the effects of this environment.

We have obtained the service of two outside consultants to assist us in evaluating the ability of the electrical equipment listed in Enclosure A to withstand the doses from recirculating fluids outside the containment after a LOCA and to evaluate the effects of aging on electrical equipment. We are analyzing the effects of the doses to mechanical equipment from recirculating fluids as noted in Reference (h). We have obtained preliminary schedules from these consultants for the time required to perform this work. According to these schedules, the analysis of in-containment equipment will be completed in September 1980, based on timely completion of the consultant's work, adequate and timely response from manufacturers, and YAEC review of the results. For equipment outside containment, we expect the analysis to be completed in December,1980, again based on the timely completion of the consultant's work, adequate and timely response from manufacturers and YAEC review of the results.

We trust you will find this information satisfactory.

However, if you have any questions, please contact us.

Very truly yours, s_l\\

D. E. Vandenburgh Senior Vice Presid t MJAlsec COMMONWEALTH OF MASSACHUSETTS)

)ss COUNTY OF WORCESTER

)

Then personally appeared before me, D. E. Vandenburgh, who, being duly sworn, did state that he is a Senior Vice President of Yankee Atomic Electric Company, that he is duly authorized to execute and file the foregoing request in the name and on the behalf of Yankee Atomic Electric Company, and that the statements therein are true to the best of his knowledge and belief.

/Q,,s"""h * * * *" *..

Robert H. Groce '

Notary Public

,/,, 4

". $ [,

My Commission Expires September 14, 1984 vn a

[

6 ; m..,. e ;,.9 us

,y

i J

~

I f

i ENCLOSURE A I

)

FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.:

50-29 PAGE 1 OP 17 EQUIPMENT LIST SYSTEM: Component Cooling Tag Number Description Location References P-20-1 Motor, Component Cooling Pump PAB CC-1 P-20-2 Motor, Component' Cooling Pump PAB CC-1 SYSTEM: Main Steam Tag Number Description Location References PIT-MS-403 Pneumatic Pressure Transmitter SG TB PIT-MS-404 Pneumatic Pressure Transmitter SG PIT-MS-405 Pneumatic Pressure Transmitter SG PIT-MS-406 Pneumatic Pressure Transmitter SG SYSTEM: Charging and Volume Control Tag Number Description Location References P-15-1 Motor, Charging Pump PAB CH-1 P-15-2 Motor, Charging Pump PAB CH-1 P-15-3 Motor, Charging Pump PAB CH-1

=

FACILITY: YANKEE ROLiE ENCLOSURE A DOCKET No.: 50-29 PAGE 2 0F 17 EQUIPMENT LIST SYSTEM: Containment Isolation Tag Number Description Location References e

K-CI-9 Relay, Containment Isolation Actuation SWGR K-CI-10 Relay, Containment Isolation Actuation SWGR K-CI-ll Relay, Containment Isolation Actuation SWGR K-CI-12 Relay, Containment Isolation Actuation SWGR K-CI-13 Relay, Containment Isolation Actuation MCR CI-l K-CI-14 Relay, Containment Isolation Actuation MCR CI-l K-CI-15 Relay, Containment Isolation Actuation MCR CI-l K-CI-16 Relay, Containment Isolation Actuation MCR CI-l PS-CI-230 Pressure Switch, Cont. Iso. Actuation PAB CI-2 PS-CI-231 Pressure Switch, Cont. Iso. Actuation PAB CI-2 PT-CI-227 Transmitter Vapor Container Pressure PAB CI-3 SOV-CI-801-820 Containment Isolation Solenoid Operated Valves PAB CI-4 SOV-CI-901-920 containment Isolation Solenoid Operated Valves PAB CI-5 LOR-CI-A Lockout Relay PAB LOR-CI-B Lockout Relay PAB K-CI-21 Auxiliary Relay PAB K-CI-22 Auxiliary Relay PAB Switch Cont. Iso. Switch Pnl.

PAB/MCR K-CI-40 through 69 Relays, Cont. Iso. Reset Sys A MCR K-CI-70 through 99 Relays, Cont. Iso. Reset Sys B MCR

_p 1

FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.: 50-29 PAGE 3 0F 17 EQUIPMENT LIST SYSTEM: Service Water Tag Number Description Location References P-6-1 Motor, Service Water Pump SCRN SW-1 P-6-2 Motor, Service Water Pump SCRN SW-1 P-6-3 Motor, Service Water Pump SCRN SW-1 SYSTEM: Main Coolant Tag Number Description Location References K1 Relay, Main Coolant Flow Scram Sys A SWGR K2 Relay, Main Coolant Flow Scram Sys A SWGR K3 Relay, Main Coolant Flow Scram Sys A SWGR K4 Relay, Main Coolant Flow Scram Sys A SWGR Ki Relay, Main Coolant Flow Scram Sys B SWCR K2 Relay, Main Coolant Flow Scram Sys B SWGR K3 Relay, Main Coolant Flow Scram Sys B SWGR K4 Relay, Main Coolant Flow Scram Sys B SWGR TD-MC-A Time Delay Relay, 200 ms, Flow Scram SWGR TD-MC-B Time Delay Relay, 200 ms, Flow Scram SWGR TD-MC-5 Relay, Main Coolant Flow Scram Sys A SWGR TD-MC-6 Relay, Main Coolant Flow Scram Sys A SWGR

=

FACILITY: YANKEE ROWE DOCKET NO.: 50-29 ENCLOSURE A PAGE 4 0F 17 EQUIPMENT LIST SYSTEM: Main Coolant (Continued)

Tag Number Description Location References TD-MC-5 Relay, Main Coolant Flow Scram Sys B SWGR TD-MC-6 Relay, Main Coolant Flow Scram Sys B SWGR K-MC-1A Relay, Main Coolant Flow Scram Sys A SWGR MC-1 K-MC-1B Relay, Main Coolant Flow Scram Sys A SWGR MC-1 K-MC-2A Relay, Main Coolant Flow Scram Sys A SWGR MC-1 K-MC-2B Relay, Main Coolant Flow Scram Sys A SWGR MC-1 K-MC-3A Relay, Main Coolant Flow Scram Sys A SWGR MC-1 K-MC-3B Relay, Main Coolant Flow Scram Sys A SWGR MC-1 K-MC-4A Relay, Main Coolant Flow Scram Sys A SWGR MC-1 K-MC-4B Relay, Main Coolant Flow Scram Sys A SWGR MC-1 K-MC-1A Belay, Main Coolant Flow Scram Sys B SWGR MC-1 K-MC-lC Relay, Main Coolant Flow Scram Sys B SWGR MC-1 K-MC-2A Relay, Main Coolant Flow Scram Sys B SWGR MC-1 K-MC-2C helay, Main Coolant Flow Scram Sys B SWGR MC-1 g.'

K-MC-3A Relay, Main Coolant Flow Scram Sys B SWGR MC-1 K-MC-3C Relay, Main Coolant Flow Scram Sys B SWCR MC-1 K-MC-4A Relay, Main Coolant Flow Scram Sys B SWGR MC-1 K-MC-4C Relay, Main Coolant Flow Scram Sys B SWGR MC-1 Current Transformer, Main Coolant Pumps SWGR FT-MC-8 Differential Pressure Detector MC Loop Flow VC MC-2 FT-MC-10 Differential Pressure Detector MC Loop Flow VC MC-2 FT-MC-ll Differential Pressure Detector MC Loop Flow VC MC-2 FT-MC-12 Differential Pressure Detector MC Loop Flow VC MC-2

=

.. =...,

O FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.: 50-29 PACE 5 0F 17 EQUIPMENT LIST SYSTEM: Main Coolant (Continued)

Tag Number Description Location References PT-MC-6 Pressure Detector Pressurizer VC MC-3 PT-MC-9 Pressure Detector MC VC MC-3 Recorder, LTOP Pressure MCR

.PT-MC-712 Pressure Xaitter LTOP VC MC-4 PWR-MC-712 Power Supply, LTOP Pressure MCR MC-MOV-301 Main Coolant Inlet / Outlet Valve VC MC-5 MC-MOV-302 Main Coolant Inlet / Outlet Valve VC MC-5 MC-MOV-309 Main Coolant Inlet / Outlet Valve VC MC-5 MC-MOV-310 Main Coolant Inlet / Outlet Valve VC MC-5 MC-MOV-318 Main Coolant Inlet / Outlet Valve VC MC-5 MC-MOV-319 Main Coolant Inlet / outlet Valve VC MC-5 NC-MOV-325 Main Coolant Inlet / Outlet Valve VC MC-5 MC-MOV-326 Main Coolant Inlet / Outlet Valve VC MC-5

FACILITY: YANKEE ROWE ENCLOSJRE A DOCKET No.: 50-29 PACE 6 0F 17 EQUIPMENT LIST SYSTEM: Pressurizer Tag Number Description Location References CH-PR-3 Comp. Ion Chamber (IR)

VC PR-1 CH-PR-4 Comp. Ion Chamber (IR)

VC PR-1 CH-PR-5 Comp. Ion Chamber (IR)

VC PR-1 CH-PR-6 Ionization Chamber (PR)

VC PR-2 CH-PR-7 Ionization Chamber (PR)

VC PR-2 CH-PR-8 Ionization Chamber (PR)

VC PR-2 LD-PR-6 Level Detector Pressurizer Level (NR)

VC PR-3 LD-PR-8 Level Detector Pressurizer Level (WR)

VC PR-3 SOV-PR-90 Power Operated Relief Valve VC PR-MOV-512 Block Valve for PR-PRV-90 VC

~

SYSTEM: Purification l

Tag Number Description Location References PU-MOV-541 Motor Operated Valve, Containment Isolation PAB I

t' FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.: 50-29 PAGE 7 0F 17 EQUIPMENT LIST i

t SYSTEM: Feed Water t.

o Tag Number Description Location References LI-FW-1001 Ind. Steam Generator Level (WR)

MCR FW-1 LI-FW-1101 Ind. Steam Generator Level (WR)

MCR FW-1 LI-FW-1201 Ind. Steam Generator Level (WR)

MCR FW-1 LI-FW-1301 Ind. Steam Generator Level (WR)

MCR FW-1 LT-FW-1001 Transsitter Steam Generator Level (WR)

VC FW-2 LT-FW-1101 Transmitter Steam Generator Level (WR)

VC FW-2 LT-FW-1201 Transmitter Steam Generator Level (WR)

VC FW-2 LT-FW-1301 Transmitter Steam Generator Level (WR)

VC FW-2 LI-FW-1003 Ind. Steam Generator Level (NR)

MCR FW-3 LI-FW-1103 Ind. Steam Generator Level (NR)

MCR FW-3 LI-FW-1203 Ind. Steam Generator Level (NR)

MCR LI-FW-1304 Ind. Steam Generator Level (NR)

MCR FW-3 FW-3 LT-FW-1003 Transmitter Steam Generator Level (NR)

VC FW-4 LT-FW-1103 Transmitter Steam Generator Level (NR)

VC FW-4 LT-FW-1203 Transmitter Steam Generator Level (NR)

VC FW-4 LT-FW-1303 Transmitter Steam Generator Level (NR)

VC FW-4 SEV-FW-1000 Pneumatic Control Station FW Flow MCR

]

SEV-FW-1100 Pneumatic Control Station FW Flow MCB FW-5 SEV-FW-1200 Pneumatic Control Station FW Flow MCB FW-5 SEV-FW-1300 Pneumatic control Station FW Flow MCB FW-5

4 FACILITY: YANKEE ROWE ENCLOSURE A DOCKET No.: 50-29 PAGE 8 0F 17 EQUIPMENT LIST i.

SYSTEM: Feed Water (Continued)

I Tag Number Description Location References LR-FW-3-1 Level Recorder, E/P SG Level SWGR LR-FW-3-2 Level Recorder, E/P SG Level SWGR LR-FW-3-3 Level Recorder, E/P SG Level SWGR LR-TW-3-4 Level Recorder, E/P SG Level SWGR

'P/S-FW-1003 Power Supply Steam Generator Level (NR)

SWGR P/S-FW-1103 Power Supply Steam Generator Level (NR)

SWGR P/S-FW-1203 Power Supply Steam Generator Level (NR)

SWGR P/S-FW-1303 Power Supply Steam Generator Level (NR)

SWGR SYSTEM: Hydrogen Vent

_~

Tag Number Description Location References HV-SOV-1 Post a:cident H Vent Valve VC HV-1 HV-SOV-2 Post-Accident H Vent Valve VC HV-1 CA-HV-1 Hydrogen Analyzer SWGR

e FACILITY: YANKEE ROWE DOCKET No.: 50-29 ENCLOSURE A PACE 9 OF 17 EQUIPMENT LIST SYSTEM: Radiation Monitoring Tag Number Description Location References GC-RM-1 Emergency Rad. Monitor /High Range TB/MCR RM-1 RD-RM-112 Emergency Rad. Monitor /High Range TB RM-2 RI-RM-112 Emergency Rad. Monitor Indicator MCR RM-3 SYSTEM: Miscellaneous Tag Number Description Location References FN18-1 Post-Accident Recire. Fan VC FN18-2 Post-Accident Recire. Fan MIS-1 VC MIS-1 FN18-3 Post-Accident Recire. Fan VC MIS-1 i

i l

4

FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.:

50-29 PACE 10 0F 17 EQUIPMENT LIST F

SYSTEM: Safety Injection Tag Number Description Location References LI-SI-1 Level Indicator SI Tank Level MCR SI-l LT-SI-1 Level Transmitter SI Tank Level Under SI Tank SI-2 LS-SI-l Level Switch SI Accumulator Low Water Level PAB SI-3 LS-SI-2 Level Switch SI Accumulator Low Water Level PAB SI-3 LS-SI-3 Level Switch SI Accumulator Low Water Level PAB SI-3 LS-SI-4 Level Switch SI Accumulator Low Water Level PAB SI-3 SI-PP-LPl Motor, Low Prese"'s SI Pump PAB SI-4 SI-PP-LP2 Motor, Low Pressure SI Pump PAB SI-4 SI-PP-LP3 Motor, Low Pressure SI Pump PAB SI-4 ST-PP-HP-1 Motor, High Pressure SI Pump PAB SI-5 SI-PP-HP-2 Motor, High Pressure SI Pump PAB SI-5 SI-PP-HP-3 Motor, High Pressure SI Pump PAB SI-5 PS-SI-14 Pressure Switch, VC Pressure /SI Initiation Ckt.

VC SI-6 l

PS-SI-238 Pressure Switch, SI Initiation Ckt.

PAB SI-7 PS-SI-239 Pressure Switch, SI Initiation Ckt.

PAB SI-7 Switch Auto - Manual Bypass Ch A&B MCR SI-MOV-1 SI Accumulator Outlet Valve PAB SI-8 P/S-SI-1 Power Supply, SI Tank Level MCR R

I FACILITY: YANKEE ROWE ENCLOSURE A DOCKET No.: 50-29 PACE 11 0F 17 EQUIPMENT LIST SYSTEM: Safety Injection (Continued)

Tag Number Description Location References LSX-SI-l Aux. Relay Vent Accumulator MCR LSX-SI-2 Aux. Relay Vent Accumulator MCR LSX-SI-3 Aux. Relay Vent Accumulator MCR LSX-SI-4 Aux. Relay Vent Accumulator MCR MOV-CS-533 LPSI Path Isolation Valve VC SI-9 MOV-CS-535 LPSI Path Isolation Valve VC SI-9 MOV-SI-22 SI Loop #4 Isolation Valve VC SI-9 MOV-SI-23 SI Loop #3 Isolation Valve VC SI-9 MOV-SI-24 SI Loop #2 Isolaticn Valve VC SI-9 MOV-SI-25 SI Loop #1 Isolation Valve VC SI-9 MOV-SI-46 HPSI Header Throttle Valve PAB SI-8 FT-SI-l Flow Transmitter SI Loop 1 VC FT-SI-2 Flow Transmitter SI Loop 2 VC FT-SI-3 Flow Transmitter SI Loop 3 VC FT-SI-4 Flow Transmitter SI Loop 4 VC MOV-SI-48 HPSI Recirculation Valve PAB SI-8 MOV-SI-49 HPSI Recirculation Valve PAB SI-8 MOV-SI-514 HPSI to Charging Hdr. Iso. Valve PAB SI-8 s

MOV-SI-515 IIPSI to Charging Ildr. Iso. Valve PAB SI-8

l FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.:

50-29 PAGE 12 OP 17 EQUIPMENT LIST SYSTEM: Safety Injection (Continued)

Tag Number Description Location References MOV-SI-516 Containment Sump Isolation Valve PAB SI-8 MOV-SI-517 Containment Sump Isolation Valve PAB SI-8 MOV-SI-518 SI Tank Discharge Valve PAB SI-8 SOV-SI-45 Accumulator, Actuator for TV-608 PAB SI-10 SOV-SI-46 Accumulator, Actuator for TV-604, 605, 606 PAB SI-10 SOV-SI-47 Accumulator, Actuator for TV-604, 605, 606 PAB SI-10 F0V-SI-56 Safety Valve Accumulator PAB SI-11 SOV-SI-57 Safety Valve Accumulator PAB SI-il SOV-SI-639 Safety Valve Accumulator PAB SOV-SI-640 Safety Valve Accumulator PAB WL-SI-l Relay, SI Initiation Ckt.

MCR WL-SI-1-1 Relay, SI Initiation Ckt.

MCR TDC-PR-1 Relay, Pressurize Accumulator MCR TDC-PR-2 Relay, Pressurize Accumulator MCR TDC-PR-3 Relay, Pressurize accumulator MCR TDC-PR-4 Relay, Pressurize Accumulator MCR TDC-SI-l TD Relay Accumulator MCR TDC-SI-2 TD Relay Accumulator MCR TDC-SI-3 TD Relay Accumulator MCR TDC-SI-4 TD Relay Accumulator MCR

FACILITY: YANKEE ROWE DOCKET NO.: 50-29 ENCLOSURE A PAGE 13 0F 17 EQUIPMENT LIST SYSTEM: Safety Injection (Continued)

Tag Number Description Location References X-SI-1-1 Relay Multiplier MCR X-SI-1-2 Relay Multiplier MCR K-CI-7 Lockout Relay, Diverse Cont. Isolation MCR K-CI-8 Lockout Relay, Diverse Cont. Isolation MCR K-31 Auxiliary Relay MCR K-32 Auxiliary Relay MCR K-SC Relay, Operates WL-SI-1-1 MCR SIAS-A Lockout Relay MCR SIAS-B Lockout Relay MCR SYSTEM: Reactor Protection Tag Number Description Location References TC-RP-420 Thermal Conv. Permissive 15 MWe MCR RP-1 TC-RP-423 Thermal Cony. Permissive 15 MWe MCR RP-1 BS-RP-420 Bistable 15 MWe MCR PP-2 BS-RP-423 Bistable 15 MWe MCR RP-2 K-20-RS Relay, Scram Aux.

MCR

=

4 FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.: 50-29 PAGE 14 0F 17 EQUIPMENT LIST SYSTEM: Reactor Protection (Continued)

Tag Number Description Location References 62-CS Relay, Trip BFP MCR RPS Reactor Protection System (Westinghouse)

MCR BK-1 Circuit Breaker, Rod Scram SWGR BK-2 Circuit Breaker, Rod Scram SWGR t,

9 FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.:

50-29 y

PAGE 15 OF 17 I

EQUIPMENT LIST 1

SYSTEM: Electrical Equipment For All Systems i:

- Tag Number Description Location References Emergency Diesel Gen. 1,2,3 PAB J1 i

LT-DG-1 Level Transmitter Level Control Day Tank PAB J2 LT-DG-2 Level Transmitter Level Control Day Tank PAB J2 LT-DC-3 Level Transmitter Level Control Day Tank PAB J2 SOV-DG-1 SOV Diesel Gen. Day Tank Fill Valve PAB J3 SOV-DG-2 SOV Diesel Cen. Day Tank Fill Valve PAB J3 SOV-DG-3 SOV Diesel Gen. Day Tank Fill Valve PAB J3 LIC-1 Level Receiver Level Control Day Tank PAB J4 LIC-2 Level Receiver Level Control Day Tank PAB J4 LIC-3 Level Receiver Level Control Day Tank PAB J4 4

No. 1 Battery SWGR JS No. 2 Battery SWGR J5 No. 3 Battery PAB J6 No. 1 Battery Charger - MG Set SWGR J7 No. 2 Battery Charger - MG Set SWGR J7 No. 3 Battery Charger - Static PAB J8 No. 1 Battery Switchboard SWGR J9 No. 2 Battery Switchboard SWGR J9 No. 3 Battery Switchboard PAB J10 No. 3A Battery Switchboard PAB-J10 No. 3B Battery Switchboard PAB J10

}-

FACILITY: YANKEE ROWE ENCLOSURE A DOCKET No.: 50-29 PAGE 16 0F 17 EQUIPMENT LIST SYSTEM: Electrical Equipment For All Systems (Continued) i Tag Number Descri ption Location References 480 Volt Emergency Bus 1 PAB J11 480 Volt Emergency Bus 2 PAB J11 Connector Coaxial VC J12 480 Volt Emergency Bus 3 PAB J11 I

480 Volt Emergency MCC 1 SWGR J13 480 Volt Emergency MCC 2 PAB J14 Vital Bus Inverter (M-G Set)

SWGR J15 Vital Bus Distribution Cubicle SWGR J16 Terminal Block 12 Point VC J17 Terminal Block 12 Point VC J18 Penetration Assembly VC J19 t

Control Switch MCR Relay over/Under Voltage (CV-7)

MCR l

l Relay Voltage (SV)

MCR

{

Relay Auxiliary (Various)

MCR f

ENCLOSURE A FACILITY: YANKEE ROWE DOCKET NO.: 50-29 PACE 17 0F 17 EQUIPMENT LIST SYSTEM:

Electrical Equipment For All Systems (Continued)

Tag Number Description Location References a

Relay, Reverse Power (CRM-1)

MCR Relay, Time Delay TDPU 2.5-50 Sec.

MCR Selector Switch for MOV MCR Cable Mineral Insulated VC J20 Cable Polyethylene /PVC VC J21 Cable Butyl Rubber /PVC VC J22 J23 Cable Silicone Rubber / Asbestos VC Cable XLP/ Neoprene (or Hypalon)

VC J24 Cable PVC Shielded VC J25 Cable Coaxial VC J26

-l 1

e

D W

e If I

{

ENCLOSURE B i