g 8005140197 APPENDIX A NOTICE OF VIOLATION Virginia Electric and Power Company License No. NPF-4 North Anna Based on the NRC inspection February 12-15, 1980, certain of your activities were apparently not conducted in full compliance with NRC requirements as indicated below. These items have been categorized as described in correspondence to you dated December 31, 1974.
A.
As required by Section 6.4.2 of the Technical Specifications, fire br'igade training sessions and drills shall be held at least once per 92 days.
Contrary to the above, the last recorded fire brigade drill is September 24, 1979, which exceeds the snaximum time of 115 days permitted between drills by the Technical Specifications (92 days plus 25% extension allowed by Section 4.0.2.a of the Technical Specifications).
This is an infraction.
B.
As required by Section 4.7.14.3 of the Technical Specifications, the cylin-ders for the carbon dioxide fire protection system for the fuel oil pump house are required to be demonstrated operable at least once per 6 months by verifying the carbon dioxide tank (cylinder) weight.
Contrary to the above, the carbon dioxide cylinders for the fuel oil pump house were weight checked on November 22, 1978, with the next weight check conducted on August 10, 1979. The time between these weight tests was 8 months and 18 days which exceeded the maximum time of 7.5 months permitted by the Technical Specification (6 months plus 25% ext: 1sion allowed by Section 4.0.2.a of the Technical Specifications).
This is an infraction.
C.
As required by Section 4.7.14.5 of the Technical Specifications, the fire hose stations within safety related areas shall be demonstrated operable at least once per 31 days by visual inspection of the station to assure that all required equipment is at the station.
Contrary to the above, the hose st.ations within the safety related areas were not inspected within the allowable time on two inspection periods between September 7, 1978 and January 31, 1980. A total of 47 days existed between the September 7,1978 and the October 24, 1978 inspections and 42
~
days existed between the March 8, 1979 and' the April 19, 1979 inspections which exceeded the maximum time of 38.75 days permitted _by the Technical Specifications (31 days plus 25% extension allowed by Section 4.0.2.a of the Technical Specifications).
This is an infraction.