ML19323B753

From kanterella
Jump to navigation Jump to search
Notice of Deviation from Insp on 800212-15
ML19323B753
Person / Time
Site: North Anna  
Issue date: 03/03/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19323B737 List:
References
50-338-80-03, 50-338-80-3, 50-339-80-03, 50-339-80-3, NUDOCS 8005140191
Download: ML19323B753 (2)


Text

G 8 0052 40 gm APPENDIX B NOTICE OF DEVIATION Virginia Electric and Power Company License No. NPF-4 North Anna Based on the results of the NRC inspection conducted on February 12-15, 1980, certain of your activities appear to deviate from your commitments to the Com-mission as indicated below.

A.

Response to Question 31 in Supplement 3 to the licensee's " Fire Protection Systems Review for North Anna Power Station - Units 1 and 2" dated October 1, 1978, states in part that the fire protection administrative procedure at North Anna comply with the Commission's supplementary guidance contained in NRC's document entitled " Nuclear Plant Fire Protection Functional Responsi-bilities, Administrative Controls and Quality Assurance".

I Contrary to the above, the administrative fire protection procedures as promulgated in the licensee's document " North Anna Power Station - Fire Protection Program" (FPP) dated December 21, 1979 do not fully comply with the NRC guidelines in the following areas:

1.

The FPP does not require fire brigade members to pass a physical examination for performing strenuous activities and does not list the qualifications for brigade members as required by Section 2.b of Attachment I to the NRC's fire protection guidelines.

2.

The FPP does not designate the areas within the plant in which smoking is prohibited and does not restrict smoking in safety related areas to designated areas as required by Section 4 of Attachment 4 to NRC's fire protection guidelines.

3.

The FPP does not require the responsible foreman or supervisor to physically survey the area in which welding, open flame ~ or grinding operations are to be conducted ' prior to these operations to assure that adequate safety procedures will be followed as required by Section 2 of Attachment 4 to NRC's fire protection guidelines, l

4.

The FPP does not require all brigade members to participate in at least one practice session per year involving an actual fire extin-Suishment activity and in the use of emergency breathing apparatus under strenuous conditions as required by Section 2 of Attachment 2 to NRC's fire protection guidelines.

5.

The FPP does not require that the brigade for each shift be drilled during a back shift at least once per year and at least one drill for each brigade to be unannounced each year as required by Section 3.f of to NRC's fire protection guidelines.

smuun

...m.

Eh..-..

Virginia Electric and Appendix B Power Company Notice of Deviation 6.

The FPP does not require that fire brigade drills at three year inter-vals be critiqued by qualified individuals independent of the utility's staff, as required by Section 3.f of Attachment 2 to NRC's fire protec-3 tion guidelines.

7.

The FPP does not require records of training provided to each brigade member, including site classroom training, drills and practice sessions to be recorded in each brigade member's training record as required by Section 4 of Attachment 2 to NRC's fire protection guidelines. This data is needed to assure that each member receives training in all parts of the brigade training program.

8.

The FPP does not identify the leaders of the fire brigade (" scene leaders") and the organizational structure of the brigade does, not provide sufficient guidance to assure that a brigade leader will be on duty at the site at all times as stipulated by Section 1.f of Attachment I to the NRC's fire protection guidelines.

B.

Section IV.B.3.c of the Fire Protection Systems Review for North Anna Power Station - Units 1 and 2 (TPSR) dated April 1,1977 states in part that "only flame-retardant wood is allowed in safety related areas of the plant".

Contrary to the above, portions of the scaffolding in the cable tunnel and vault and emergency switchgear rooms consisted of combustible wood planking.

C.

Section IV.E.3.b of the FPSR states in part that all valves in the fire protection system which are not electrically supervised are placed in correct position, sealed with tamper proof seals and inspected weekly.

Contrary to the above, many control valves in the fire protection system are inspected monthly in lieu of weekly.

i

  • s+

6

.