_ _ _ _ _ _

DUKE POWER COMPANY Powra Buttonwo 422 Sourn Ciruncis Sruzzr, Gnuat.ortz, N. C. 2a24a,

WILLIAM O. PA R M E R, J R.

TELgewoNt; AntA 704 Vict Pats otut 373-4083 se tae. PmOOwCTio%

May 14, 1976 Mr. Norman C. Moseley, Director U. S. Nuclear Regulatory Commission Suite 818 230 Peachtree Street, Northwest Atlanta, Georgia 30303 Re:

IE:II:TNE 50-269/76-2 50-270/76-2 50-287/76-2

Dear Mr. Moseley:

1 My letter dated April 8, 1976 responded to OIE Inspection Report 50-269,

-270, -287/76-2. Item I.A.1 stated that high background readings seen on diation monitors RIA-33 and RIA-34 presently precluded a correlation of laboratory results and expected monitor readings.

In the interim until these background effects can be eliminated, beginning June 1, 1976, a redundant valve lineup check of the ef fluent pathway will be performed prior to each liquid effluent release.

In addition, a redundant sample and gross beta analysis will be performed prior to each liquid effluent release.

With regard to item I.A.3 concerning the interim waste build'ng vent gas monitor RIA-52, a daily check is being conducted to assure ins operability until the station modification providing an alarm is completed.

V y truly yours,

/

/

fN a.tL Lb. O William O. Parker, Jr.

MST:mmb 7912050779 i