Text

.

t

^

O.

~

APPENDIX A Notice of Violation Based on results of the NRC inspection on June 20-21, 1977, it appears that certain of your activities were not conducted in full compliance with NRC regulations and the conditions of your NRC Facility License This item is categorized Nos. DPR-38, DPR-47 and DPR-55 as indicated below.

as an infraction.

Appendix B Technical Specification 1.2 requires that the pH of water released from the Waste Water Treatment System shall not exceed the range limits of 6.0-9.0 defined in Table 1.2-1.

Contrary to the above, the maximum pH limit of 9.0 was exceeded as indicated below; a.

On April 18, 1977, the Waste Water Treatment System discharge pH was as high as 9.7.

pH of the discharge exceeded the 9.0 limit for approximately 2.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />.

On May 1, 1977, the Waste Water Treatment System discharge exceeded b.

The maximum pH the 9.0 pH limit for approximately 1.75 hours8.680556e-4 days <br />0.0208 hours <br />1.240079e-4 weeks <br />2.85375e-5 months <br />.

recorded during this period was 9.2.

oso 77fr nu

.