ML19322B598

From kanterella
Jump to navigation Jump to search
Ro:On 760211,yard Drain Sample Ph Reading Was 9.2.Caused by Shut Lower Settling Basin Discharge Valve.Corrective Actions:Procedure for Waste Water Collection Basins Revised & Faster Monitoring Equipment to Be Installed
ML19322B598
Person / Time
Site: Oconee  Duke Energy icon.png
Issue date: 02/19/1976
From: Parker W
DUKE POWER CO.
To:
References
NUDOCS 7912040626
Download: ML19322B598 (1)


Text

~

bUKE Powid# C6MPANY Pows 0 Buttmwo 422 Sourn Cauncu Srazzr, CaAa:.orre, N. C. aeba 0

1 wiwam o. araxca. sa.

February 19, 1976 VsCE PetSiDENT TELEPMonc AREA 704 SrE4.* Pacoucwoe.

373-4083

.3

/$

'N, -

Mr. Norman C. Moseley, Director

<f/.

U. S. Nuclear Regulatory Commission

,].h b=1 Suite 818 i

wi C' b

  • G 230 Peachtree Street, Northwest c.@'

,y hl 4

Atlanta, Georgia 30303 uA wnm g

cowagm GG r.o A

Re:

Oconee Nuclear Station' e

Docket Nos. 50-269, -270, -287 b

[

y c)

Dear Mr. Moseley:

Oconee Nuclear Station Appendix B Technical Specification'l.2 B requires that ali gater M eeharzad fv a rha pinne c4t= wa n on beruoan 6.0 nna 8 5.

On February 12, 1976 a routine sample of the yard drains indicated a pH reading of 9.2.

The following is a description -)f the events leading to this condition.

On February ll, 1976. from 0830 to 11'to. the lower settling basin level was decreased in order to provide capacity for the storage of water resulting I

from the drainage of the Oconee Unit 1 steam generators.

Commercing at 2000, this water was pumped to the lower settling basin. At 0830 on February 12, 1976, a sample of the yard drains indicated a pH of 9.2.

Inves-tigation revealed that the lower settling basin discharge valve was shut, the basin was receiving constant inlet flow and the water was overflowing the spillway. At 1150 the inlet valve to the upper basin was opened and the inlet valve to the lower basin was closed.

Subsequent samples of the yard drains indicated a decreasing pH trend with the yard drains becoming l

in specifications at 0830, February 13, 1976. This incident had no observable effect upon the environment.

In order to prevent recurrence, the operating procedure for the waste water collection basins will be revised. The settling basins will be operated in such a manner that the weir valve will remain open and the pH of the basin controlled such that the resulting pH of water leaving the site will remain between 6.0 and 8.5.

This will allow much greater reserve capacity in the settling basins to accommodate plant discharges which are out of normal.

These changes will be instituted by March 18. 1976.

In addition, in-line pH monitoring of the yard drains and the outlet of the lower settling basins with a remote readout capability in the water treatment room will be installed.

This will provide much faster indication of an abnor a1 pH condition.