j BOSTON EDISON COMPANY DOCKET NO. 50-293 PILGRIM NUCLEAR POWER STATION UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 35 License No. DPR-35 1.

The Nuclear Regulatory Comission (the Comission) has found that:

j A.

The submittals by Boston Edison Company (the licensee) dated March 6, May 4, July 10 and September 22, 1978, comply with the standards and requirements of the Atomic Energy act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in confomity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The. issuance of this amenchent is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

79010400$

' 2.

Accordingly, the license is amended by changes to thc Technical Specifications as indicated in the attachment to this license amendment, and by changing paragraph 3.B and adding paragraph 3.F to read as follows:

3.8 Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 35, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

I 3.F Fire Protection The licensee may proceed with and is required to complete the modifications identified in Paragraphs 3.1.1 through 3.1.19 of the NRC's Fire Protection Safety Evaluation (SE), dated December 21, 1978 for the facility. These modifications will be completed in accordance with the schedule ir Table 3.1.

In addition, the licensee shall submit the additional information identified in Table 3.2 of this SE in accordance with the schedule contained therein.

In j

the event these dates for submittal cannot be met, the licensee shall submit a report, explaining the circumstances, together with a revised schedule.

The licensee is required to implement the administrative controls identified in Section 6 of the SE.

The administrative controls shall be in effect by December 31, 1978, 3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

/

Tho Chief Operating Reactors Branch #3 Division of Operating Reactors

Attachment:

Changes to the Technical Specifications Date of Issuance: December 21, 1978

O e

ATTACHMENT TO LICENSE AMENOMENT NO. 35 FACILITY OPERATING LICENSE NO. OPR-35 DOCKET NO. 50-293 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by Amendment number and contain vertical lines indicating the area of change.

PAGES 206 206a 206c 206d 206e Add page 206e-1 206f 206h 3

1 l

l j

l LIMITINd CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS 3.12 FIRE PROTECTION 4.12 FIRE PROTECTION A.

Fire Detection Instrumentation A.

Fire Detection Instrumentation j

The fire detection instrumentation 1.

Each of the fire detection for each fire detection zone shown instruments noted in Table in Table 3.12-1 shall be OPERABLE.

3.12-1 including the NFPA Code 72A supervised circuitry shall APPLICABILITY:

be demonstrated OPERABLE by a functional test at least once At all ttnes when equipment in that per 6 months.

fire detection zone is required to be OPERABLE.

2 The fire detection instrumenta-tion supervised circuitry ACTION:

associated with detector alarms, shall be demonstrated OPERABLE With the number of OPERABLE fire at least once per 2 months.

detaction instruments less than required by Table 3.12.1; a.

Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, establish a fire watch patrol to inspect the zone with the inoperable instrument (s) at least once per hour; and b.

Restore the inoperable instru-ment (s) to OPERABLE status within 14 days, or prepare and submit a report to the Commission within the next 30 days outlining the action taken, the cause of the malfunction and the plans for restoring the instru-ment (s) to OPERABLE status.

B.

Fire Suppression Water System B.

Fire Suppression Water System The FIRE SUPPRESSION WATER SYSTEM 1.

The FIRE SUPPRESSION WATER shall be OPERABLE with:

SYSTEM shall be demonstrated OPERABLE:

1.

Two (2) fire system pumps with their discharge aligned to the a.

at least once per 7 days fire suppression header, by verifying the water supply volume.

2.

Separate water supplies con-taining a minimum of 240,000 b.

at least once per month gallons each.

1) on a staggered test 3.

An OPERABLE flow path capable of basis by starting each taking suction from Tank 107A pump and operating it and Tank 107B and transferring for 20 minutes on re-the water through distribution circulation flow.

I Amendment No. /, 35 206

LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS piping with OPERABLE section-

2) by verifying that each alizing control or isolation valve (manual, power valves to the hydrant post operated or automated) indicator valves and the in the flow path is in front valve ahead of the its correct position.

water flow alarm device on each sprinkler, hose stand-c.

at least once per year by pipe or spray system riser.

cycling each testable valve in the flow path through 4.

Automatic initiation logic at least one complete for each fire pump.

cycle of full travel.

APPLICABILITY: At all times.

d.

at least once per operating cycle ACTION:

1) by performing a system a.

With less than the above re-functional test which quired equipment, restore the includes simulated inoperable equipment to automatic actuation of OPERABLE status within 7 days the system throughout its or prepare and submit a operating sequence and report to the Commission verifying that the fire within the next 30 days pump diesel engine starts outlining the plans and pro-from ambient conditions cedures to be used to provide on the auto-start signal for the loss of redundancy in and operates for at this system.

least 20 minutes while loaded with the fire b.

With no FIRE SUPPRESSION WATER pump.

SYSTEM OPERABLE, within 24 hrs.

2) by verifying that each 1

1.

Establish the backup Fire pump starts and delivers Suppression Water System.

at least 2000 gpm while maintaining a system 2.

If the requirement of b.1 pressure of at least above cannot be met, an 125 psig.

orderly shutdown of the reactor shall be initi-

3) by verifying that each ated and the reactor automatic (deluge) valve shall be in the cold in the flow patch actuates

{

shutdown condition with-to its correct position.

in 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

4) by cycling each valve in 3.

Notify the Commission the flow path that is not and prepare and submit testable during plant a report to the operation through at Commission within the least one complete cycle next 14 days outlin-of full travel.

ing the cause of the mal-functions, the action taken, and the plans for restoring the system to OPERABLE status.

Amendment No.,26$ 35 206a i

LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS

2) at least once per 3 months by verifying that the specific gravity is appropri-ate for continued service of the battery.
3) at least once per operating cycle by verifying that the batteries, all plates, and battery racks show no visual indication of physical damage or abnormal deterioration and the battery-to-battery and terminal connections are clean, tight, free of corrosion, and coated with anti-corrosion material.

C.

Spray and/or Sprinkler Systems C.

Spray and/or Sprinkler Systems The spray and/or sprinkler systeme The spray and/or sprinkler systems located in the following areas shall shall be d' snstrated to be OPERABLE:

be OPERABLE:

1.

At least once per 12 months 1.

Diesel Generator Day Tanks by cycling each testable valve in the flow path through 2.

Diesel Fire Pump Day Tank at least one complete cycle of full travel.

3,.

Auxiliary Boiler Room 2.

At least once per cycle:

4.

Recire. Pump MG Set Room 5.

St--dby Gas Treatment System a.

By performing a system functional test which includes simulated 6.

Hydrogen Supply 011 Unit automatic actuation of the system and verifying 7.

Turbine Basement Addition that the automatic (deluge) valves in the flow path APPLICABILITY:

actuate to their correct positions.

At all times when equipment in the spray / sprinkler protected b.

By inspection of spray area is required to be OPERABLE.

headers to verify their integrity, c.

By inspection of each nozzle to verify no blockage, d.

By cycling each valve in the flow path that is not testable t-l during plant operations L

through at least one complete cycle.

Amendment No.,)(', ' 35

)

3.

At least once per 3 years by per-forming a flow test through each

'206c

LIMITING CONDITION FOR OPERATION SURVLILLANCE REQUIREMENTS ACTIONS.

pen head spray / sprinkler header and verifying each open a.

With a spray and/or sprinkler head spray / sprinkler nozzle is un bst m ted.

system inoperable, establish a continuous fire patrol with backup fire suppression equip-ment for the unprotected area (s) within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

b.

Restore the system to OPERABLE status within 14 days or pre-pare and submit a report to the Coinnission within the next 30 days outlining the action taken, the cause of inoperability and the plans for restoring the system to OPERABLE status.

D.

CO2 SYSTEM D.

CO SYSTEM 2

The following CO2 systems shall The CO2 System shall be demonstrated be OPERABLE with a minimum level of OPERABLE:

60% and a minimum pressure of 275 psig in the associated storage 1.

At least once per 7 days by tank (s).

verifying the CO2 storage tank level and pressure.

1.

Cable Spreadin am s

2.

At least once per cycle by 2.

37' elevation switengear room verifying the system valves and associated ventilation 3.

23' elevation switchgear room dampers actuate automatically and manually to a simulated APPLICABILITY:

actuation signal. A brief flow test shall be made to At all times when the equipment in verify floi from each nozzle.

the area is required to be OPERABLE.

(" Puff Test").

ACTION:

I a.

With a CO2 system inoperable, establish a continuous fire patrol with backup fire suppression equipment for the unprote cted area (s) within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

b.

Restore the system to 0'ERABIE status within 14 days c p"/. ore and submit a report to et*

Cottmission within the neit h days outlining the action taken, the cause of inoperability and the plans for restoring the system to OPERABLE status.

Amendment No.

35 206d w

LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS E.' Fire Hose Stations E.

Fire Hose Stations The interior fire hose stations shown Each interior fire hose station shall in Table 3.12-2 shall be OPERABLE.

be verified to be OPERABLE:

APPLICABILITY:

1.

at least once per month by visual inspecticn of the At all times when the equipment station to assuru,11 equip-

+

in the area protected by the fire ment is availa';1a.

hose station is required to be operable.

2.

at least once per cycle by removing the hose for inspec-ACTION:

tion, replacing degraded coupling gaskets, and re-racking.

With a hose station inoperable, route an additional equivalent 3.

at least once per 3 years by capacity hose to the unprotected area from an OPERABLE hose station a.

partially opening each hose within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

station valve to verify valve operability and no blockage.

b.

by conducting a hydrostatic test of each hose

1) at a pressure 50 psig greater than the maximum available pressure at that hose station, or
2) annually at the applicable service test pressure as listed in Table 821 of the

" Standard for Care, Main-l tenance and Use of Hose,"

NFPA No. 198-1972, or c.

by replacing each hose with a new or used hose which has been hydrostatically tested in accordance with the tressures specified in 4.12.,

E.3.b.

F.

Penetration Fire Barrier F.

Fire Barrier Penetration Fire Seals All fire barrier penetration fire 1.

Penetration fire barriers shall seals protecting safety related be verified to be functional l

areas shall be functional.

by a visual inspection at least once per operating cycle and APPLICABILITY: At all times subsequent to any installation, modification, or maintenance.

ACTION:

With a penetration fire barrier not functional, a continuous j

fire patrol shall be' established j

Amendment No.,p(( 35 20te

LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS

' on at least one side of the affected penetration within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

G.

Dry Chemical Systems G.

Dry Chemical Systems The fixed dry chemical systems Each dry chemical system shall located in the following areas be verified to be OPERABLE:

shall be OPERABLE:

A.

At least once per 6 mor.ths by 1.

Diesel Generator Room "A".

checking all stored dry chemical containers by pressure and 2.

Diesel 3enerator Room "B".

weight against the required minimums.

APPLICABILITY:

B.

At least once per 18 months by:

At all time.i when equipment in the protected area is required 1.

Verifying the system actuates to be operable, manually and automatically, upon receipt of a simulated ACTION:

test signal, and With a dry chemical system 2.

Performance.of a flow test inoperable, establish a continuous through Fr2ders and nozzles fire patrol with backup fire to assure o blockage, suppression equipment for the unprotected areas within one hour; restore the system to OPERABLE status within 14 days or prepare and submit a Special Report to the Commission within the next 30 days outlining the action taken, the c,ause of the inoperability and the plans for restoring the system to OPERABLE status.

H.-

Yard Hydrants and Exterior Hose H.

Yard Hydrants and Exterior Hose Houses Houses The yard hydrants and exterior hose Each hydrant shall be verified houses shown in Table 3.12-2 shall OPERABLE:

be OPERABLE.

)

1.

At least once per month by a APPLICABILITY: At all times visual inspection of the hose house to assure all equipment ACTION:

is available.

With a yard hydrant inoperable, 2.

At least twice per year (once in within one hour have a sufficient the fall and once in the spring) by number of additional lengths of inspecting each outdoor fire hydrant.

2 1/2" diameter hose located in an adjacent OPERABLE hydrant's 3.

At least once per year by performing hose house to provide service surveillance requirement E.3.b or c.

to the area protected by the inoperabl. hydrant.

Amendment No.,pf( 35 206e-1

g TABLE 3.12-1

=

FIRE DETECTION INSTRUMENTS r*

INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT SMOKE g

1.

Cable Spreading N/A 9

2.

Computer Room N/A 1

3.

Switchgear Room Elevation 37' N/A 9

Elevation 23' N/A 11 4.

Station Battery Rooms Elevation 37' N/A 2

Elevation 23' N/A 2

5.

Diesel Generator A

1 1

B 1

1 6.

Safety Related Pumps RCIC N/A 1

HPCI N/A 1

7 Recir. M. G. Sets A

N/A 3

B N/A 3

y 8.

A.O.C.

N/A 4

R

r TABLE 3.12-2 (Cont.)

FIRE HOSE STATIONS Retention Building me P

Sta. #

101 Retention Building, El. 23' 102 Retention Building, El. 6' Radwaste Area Sta. #

18 Outside Radwaste Control Room, El.

-l' 34 Monitor Tank Pump Area, El.

-l' 35 Radwaste Area North Corner, El. -l' 45 Radwaste Stairway to Turbine Bldg., El.

-l' Warehouse #2 North End Section -1 Center Section North End Section -2 Yard Hose Cabinets Sta. #

1

, North Side of Screen House 2

N. E. Area at Machine Shop S$

!P

. _