Notice of Violation from Insp on 800514-15
ML19321A210
Person / Time
Site: Braidwood  Constellation icon.png
Issue date: 06/09/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML19321A208 List:
References
50-456-80-04, 50-456-80-4, 50-457-80-04, 50-457-80-4, NUDOCS 8007230006
Download: ML19321A210 (1)


Text

3(V Appendix A NOTICE OF VIOLATION Commonwealth Edison Company Docket No. 50-456 Docket No. 50-457 Based on the inspection conducted on May 14 and 15, 1980, it appears that one of your activities was in noncompliance with NRC requirements, as noted below. This item is an infraction, and is applicable to both Units 1 and 2.

10 CFR 50, Appendix B, Criterion III, states, in part, that " Measures shall be established to assure that applicable.... design basis...for those structures, systems, and components....are correctly translated into specifications,. drawings, procedures, and instructions".

Commonwealth Edison Company Topical Report CE-1-A, " Quality Assurance Program for Nuclear Generating Stations", Revision 9, dated July 16, 1979, states in Paragraph 3.1 that "The fundamental vehicle for design control involves multi-level review and/or evalation of design documents by individuals or groups other than the original designer or designer's immediate supervisor whose authority and responsibility are identified and controlled by written procedures. The design documents include, but are not limited to, design and construction specifications, equipment specifications, and process drawings. Review of and evaluation by the Architect Engineer will ensure that designs and materials will conform to the ASME Code and other applicable codes, standards, regulatory require-ments, SAR commitments, and appropriate quality Standards as applicable.

Contrary to the above, it was determined that CECO did not ensure that Sargent and Lundy adequately translated the requirements in paragraphs 6.2.1.6 and 3.8.2.6.1 of the Braidwood PSAR and the requirements in Table 302.4 of S&L Specification 2831 4to S&L Specification No. 2815 for eletrical cable tray hanger supports in that corrosion protection was not specified for the exposed carbon steel material and exposed

-spot welds " sed in the installation of seismic Category I electrical cable tray hanger supports.

.80 0723 00C4'