$31 PARK AVENUE KING OF PRUS$4 A, PENNSYLVANI A 19404 June 24, 1980 Docket No. 50-208 Columbia University ATTN: Mr. John M. Harding Resident University Counsel 110 Low Memorial Library New York, New York 10027 Gentlemen:
The enclosed IE Circular No. 80-14, " Radioactive Contamination of Plant Demin-eralized Water System and Resultant Internal Contamination of Personnel," is forwarded to you for information.
No written response is required.
If you desire additional information regarding this matter, please contact this office.
Sincerely, y e H. Grier Director
Enclosures:
1.
IE Circular No. 80-14 2.
List of Recently Issued IE Circulars CONTACT:
P. J. Knapp (215-337-5291) cc w/encls:
Dr. W. W. Havens, Jr., Director of Nuclear Engineering I
l 8007160 N o
ENCLOSURE 1 SSINS.: 6830 UNITED STATES Accession No.:
NUCLEAR REGULATORY COMMISSION 8005050074 0FFICE OF INSPECTION AND ENFORCEMENT n
WASHINGTON, D. C.
20555 D
ow
.a S
IE Circular No. 80-14 Date:
June 24, 1980 Page 1 of 2 RADI0 ACTIVE CONTAMINATION OF PLANT DEMINERALIZED WATER SYSTEM AND RESULTANT INTERNAL CONTAMINATION OF PERSONNEL This circular describes an event which occurred at a nuclear power facility; however, the generic implications may be applicable to research reactors, and fuel cycle facilities.
On March 17, 1980, a licensee informed the NRC resident inspector that portions of the plant demineralized water (DW) system were found to be radioactively contaminated.
A temporary hose used to add demineralized water to the spent fuel pool was the pathway for the cross contamination.
After this fuel pool makeup was completed on March 14, the temporary DW line (still connected to the DW header) was inadvertently left submerged in the fuel pool.
Since the DW header pressure at the point of supply was relatively low (a DW booster pump had been secured), a siphoning action occurred, resulting in radioactive contamination of portions of the DW header.
On March 17, 1980, while 3erforming routine secondary system chemical analyses, thelicenseediscoveredt1atthedemineralizedwatertapin_$hechemistrylab contained high levels of boron and had activity of 1.5 x 10 uCi/ml (mainly Cs-134, Cs-137, Co-58, Co-60 and Mn-54).
It was subsequently discovered that demine:alized water from the chemistry laboratory supply tap had been used to make five (5) pots of coffee.
The remaining coffee was confiscated and the twenty-three (23) individuals who had consumed this coffee were whole-body counted.
All involved individuals showed no intake greater than an e9ui alent 0.01 MPC-HRS. Analysis performed by the licensee's radiation consultanz bt ad on the maximum concentration of radioactivity found in the coffee, indic.e u that the resultant 50 year dose commitment to an individual drinking eight ounces of this coffee would be less than 1 millirem.
Further licensee investigation revealed that the non-radiological chemistry DW supply tap was the only DW supply point outside the Auxiliary Building controlled area.
This DW supply tap was tagged prohibiting human consumption to prevent a similar event in the future.
It is recommended that you review your facilities use of demineralized water (DW) via temporary connections and give attention to the foliowing:
1.
Provisions should be made to assure that radioactive materials are not use of temporary connections. your facility's DW system via the improper inadvertently introduced into A temporary cross connection between contaminated systems and the DW system without adecuate physical controls to prevent cross-contamination should be prohibitec.
m
,ey-y yy--wrv
IE Circular No. 80-14 June 24, 1980 Page 2 of 2 2.
In addition to some physical means of preventing backflow into the DW system, appropriate administrative controls should be established to ensure tha' the DW supply valve is secured and temporary hosing is disconnected from the DW supply header after use.
3.
Use of plant-supplied DW for human consumption should be prohibited.
The potable water system should be the only authorized source of water for human consumption.
4.
Examine potable and demineralized water systems to determine if pathways exist allowing or having the potential to allow contamination of these systems including temporary connections whereby siphons could cause situations described above.
No written response to this Circular is reguired.
Your review of this matter to determine its applicability to your facility and any corre:tive and preven-tive actions taken or planned, as appropriate,. will be reviewed during a subsequent NRC inspection.
If you desire additional information regarding this matter, contact the Director of the appropriate NRC Regional Office.
1 l
4-+
-P IE Circular No. 80-14 June 24, 1980 RECENTLY ISSUED IE CIRCULARS Circular Subject Date of Issued to No.
Issue 80-13 Grid Strap Damage in 5/28/80 All holders of a Westinghouse Fuel Assemblies Power Reactor Operating License (OL) or Construction Permit (CP) 80-12 Valve-Shaft-To-Actuator Key 5/14/80 All holders of a May Fall Out of Place When Power Reactor Mounted Below Horizontal Axis OL or CP 80-11 Emergency Diesel Generator 5/13/80 All holders of a Power Lube Oil Cooler Failures Reactor OL or CP 80-10 Failure to Maintain 4/29/80 All holders of a Environmental Qualification Power Reactor of Equipment OL or CP 80-09 Problems With Plant Internal 4/28/80 All holders of a Power Communications Systems Reactor OL or CP 80 BWR Technical Specification 4/18/80 All holders of a Power Inconsistency - RPS Response Reactor OL for a General Time Electric BWR 80-07 Problems with HPCI Turbine 4/3/80 All holders af a Power Oil System Reactor OL or CP 80-06 Control and Accountability 4/14/80 Medical licensees in Systems for Implant Therapy Categories G and G1 Sources 80-05 Emergency Diesel-Generator 4/1/80 All holders of a Power l
Lubricating Oil Addition and Reactor OL or CP Onsite Supply 80-04 Securing of Threaded Locking 3/14/80 All holders of a Power Devices on Safety-Related Reactor OL or CP Equipment 80-03 Protection from Toxic Gas 3/6/80 All holders of a l
Hazards Power Reactor OL 80-02 Nuclear Power Plant Staff 2/1/80 All holders of a l
Work Hours Reactor OL, including research and test reactors, or CP
.