ML19320A166

From kanterella
Jump to navigation Jump to search
Forwards ROs 50-313/76-15,50-313/76-16 & 50-313/76-18
Date released: 11/30/2019 Download: ML19320A166


RO 50-313/76-18:on 760716,hydrogen Purge Inlet Fan,Filter Bleed Valve & Penetration Room Ventilation Sys Fan Breakers Tripped.Caused by Abnormally Hot Environ & Low Thermal Overload Setting.Overload Setting Increased & Dampers Reset
ML19320A175
Person / Time
Site: Arkansas Nuclear 
Issue date: 08/03/1976
From: Mardis D
ARKANSAS POWER & LIGHT CO.
To:
References
Download: ML19320A175 (4)
RO 50-313/76-16:on 760712,sodium Thiosulfate Tank T-9 Found Below 37,500 Lb Tech Specs Limit.Caused by Suspected Leak Into Reactor Bldg Spray Sys.Addl Sodium Thiosulfate (956 Lb) Added on 760713.Efforts Made to Reduce Leakage
ML19320A169
Person / Time
Site: Arkansas Nuclear 
Issue date: 08/03/1976
From: Mardis D
ARKANSAS POWER & LIGHT CO.
To:
References
Download: ML19320A169 (4)
RO 50-313/76-15:on 760707,cracked Weld Discovered in Valve CZ-65 Heat Affected Zone.Caused by Improper Welding During Installation.Weld Removed & Replaced w/3 Ft Schedule 10 Piping
ML19320A168
Person / Time
Site: Arkansas Nuclear 
Issue date: 08/03/1976
From: Mardis D
ARKANSAS POWER & LIGHT CO.
To:
References
Download: ML19320A168 (4)
Forwards ROs 50-313/76-15,50-313/76-16 & 50-313/76-18
ML19320A165
Person / Time
Site: Arkansas Nuclear 
Issue date: 08/03/1976
From: Phillips J
ARKANSAS POWER & LIGHT CO.
To: HOWARD E M
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19320A165 (1)