Responds to NRC Re Violations Noted in IE Insp Rept 50-302/77-24.Corrective Actions:Emergency Procedure EM-206 Reviewed & Updated W/Insertion of Appropriate Personnel Names & Current Phone Numbers
ML19319D007
Person / Time
Site: Crystal River 
Issue date: 02/21/1978
From: Stewart W
FLORIDA POWER CORP.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19319D003 List:
References
NUDOCS 8003040934
Download: ML19319D007 (4)


Text

____ __________________________ _ ____

O cc%.

e

,y c.yx 3

~

/: ') lC T. C ( '.

(G) e t ( 'V.t;-

r e(

%.} [., '

Florida P

21 February 1978 co. o

,a 3-0-3-a-2 CS-78-52 Mr. J. P. O'Reilly, Director Docket No. 50-302 Office of Inspection & Enforcement License No. DPR-72 U.S. Nuclear Regulatory Commission REF: RII-GTG 230 Peachtree St. N.W., Suite 818 50-302/77-24 Atlanta, CA 30303

Dear Mr. O'Reilly:

We offer the following responses to the apparent items of noncompliance in the referenced Inspection Report. As noted in your report, corre ctive steps were taken for items B, C, and F during the Inspector's visit.

Therefore, the response to these items will include the corrective steps to be taken to avoid further noncompliances only.

~Before discussing the specific items contained in the Notice of Violation, we would like to address significant action which will be taken to enhance the management control systems governing the Emergency Plan. The Euer-gency Plan contained in the FSAR is an historical document describing the Emergency Plan as it existed at the time of licensing.

Since that time, numerous changes in personnel and implementing procedures have been effected. Because the Emergency Plan has not been part of the Plant Operating Quality Assurance Manual (P0QAM), it has received less attention than warranted.

Ihe current Emergency Plan will be incorporated in P0QAM via review by the Plant Review Committee and approval of the Nuclear Plant Manager, to assure attention and action by appropriate plant management. This incorporation will be completed by 1 June 1978.

A.

Emergency Plan Section 3.1.1 states the Emergency Co-ordinator shall call appropriate individuals or agencies listed in the Emergency Roster.

Section 4.5.4.c of the Emergency Plan specifies action to be initiated when an unplanned release exceeds 1.2 x 10-7 pCi/ce.

Contrary to the above:

1.

Emergency Procedure EM-206, " Emergency Plan Roster and Notification" did not have current Emergency Roster Call List telephone numbers on December 5,

/^N 1977.

\\j 2.

Emergency Procedure EM-203, " Classification of Emer-gencies and Criteria for Evacuation," did not implement 800304o 3p General Office 320i Tn.ny founn sneer soum. p o som 14o42. s. Peteesburo. Florca 33733 813 - 866-5851

=

J. P. O'Reilly

)

REF: RII/GTG/50-302/77-24 l

.s Page 2 Section 4.5.4.c of the Emergency Plan, A-1 Response: As noted in Details 1.5.b.(2), the next annual review of the Emergency Plan is due in March 1978. This review would have provided necessary input to correctly update telephone numbers within the re-quired time frame. This annual review was considered an acceptable interval by a previous inspector. At the time of Inspection 77-24, an update of Emergency Procedure EM-206 was in progress to reflect additions and changes to Fire Brigade and Offsite Support Group membership.

Corrective steps which were taken include review and update of EM-206 with insertion of appropriate personnel and current phone numbers.

Corrective Action to prevent further noncompliance has been taken by issuance of a directive from the plant manager to Section Heads, in-forming them of their responsibility to notify the Plant Manager's Secretary of any changes within their sections which affect personnel or phone numbers listed in EM-206. The Secretary will then issue the housekeeping change within one week of such notification.

The annual review will be continued to assure compliance.

Full compliance has been achieved as of this date.

A-2 Response: We believe that this item does not constitute a noncompliance, but rather points up an inconsistency between Section 12B of the FSAR 4

and Technical Specifications. In addition to this inconsistency, the wording of Section 4.5.4.c of the Emergency Plan is obviously in error as, in discussing release rate, the value given is in concentration (pCi/cc). Guidance given us in the past by the NRC indicates that where conflicts exist, the Tech Spec must take precedence.

Emergency Procedure EM-203, and other appropriate Emergency Procedures, do reference, and are consistent with appropriate Sections of Tech Specs.

In light of our plans to incorporate the Emergency Plan in P0QAM, and our Admiaistrative Control of procedures therein, assurance is given that appropriate safety analyses will be made of implementing procedures.

l B.

Emergency Plan Sections 1.0.4.6.2.7.c, 6.1 and 6. 3 specify equipment and applicable. materials to be available at the Emergency Assembly Center (EAC), Fossil Plant Control Room, and Fossil Plant Water Laboratory.

Contrary to the above, on December 6,1977, the following required equipment and applicable materials was not avail-able:

1.

Emergency Assembly Center (EAC)

N a) Copy of Emergency Plan.

b) Base Radio Station for communication on channel 1, with oil ba.ge tugboats.

1 r,

e ww e

a

's J. P. O'Reilly REF: RII-GTC/50-302/77-24 Page 3 c) Portal monitor, d) Decontamination kit.

e) Emergency Environmental Survey Team Vehicle during backshift ope ration.

f) Monitoring kit 1 - High Range Inr,trument.

2.

Fossil Plant Control Room - Copy of Emergency Plan.

3.

Fossil Plant Water Laboratory - Copy of applicable Emergency Procedures.

B. Response: The incorporation of the Emergency Plan into the Plant Operating Quality Assurance Manual with rinview and audits should preclude recurrence.

C.

Section 3.2.8 of the Emergency Plan specifies that the Crystal River Fire Brigades shall be self-reliant, requiring no offsite support, Emergency Procedure EM-216, " Duties of the Nuclear Plant Fire Brigade", Section 3.4 states that each Fire Brigade should consist of persons who have received specified training.

i Section 1.2 states the Nuclear Plant Fire Brigade will im-s_,/

plement actions to effectively handle the fire emergency.

Contrary to the above, on December 5-8, 1977, backshift staffings of the Fire Brigade were composed of two shifts where only one Fire Brigade member was present onsite.

C. Response: Technical Specifications incorporating the fire protection func-tions within the plant have been issued and will be in force 5 March 1978.

J Additional members of the plant staff are currently being trained for qualification as fire brigade members. This training of sufficient numbers l

of personnel vill assure that required fire brigade manning levels are met prior to the imposition of applicable Tech Specs.

j D.

Section 2.2.3 of the Emergency Plan requires an Environmental Survey Team and a Radiation Survey Team. Section 7.2 of the Emergency Plan states that, through training, the personnel shall maintain a high proficiency in radiation protection including emergency monitoring.

Contrary to the above, on December 14, 1977, only one techni-cian was present onsite during backshift on weekends, to staff the Environmental Survey Team and Radiation Survey Team, and periodically this technician position was staffed with an individual whom had not completed training in Emergency Pro-cedures EM-208 and EM-210.

D. Response: Since the me of the inspection, all Chem / Rad technicians have been trained as reouired. At least two of these technicians are present during backshifts, one of whom is the responder for Radiation Survey Team action. The Environmental Survey Team is not intended to be onsite at all e

wv

-w+

-~

- > + +

m M

fy J. P. O'Reilly (V).

REF:

RII-GTG/50-302/77-24 Page 4 times, but members of this team are subject to fast re-call should their action be required. These actions have not only resolved the item, but also, they preclude recurrence.

Full compliance has been achieved.

~

Emergency Plan Sections 7.3.b and 7.3.c.1 require quarterly E.

medical drills and semi-annual Class A and B drills.

J Contrary to the above, the licensee has not performed these drills since issuance of the operating license.

E. Response: The quarterly medical drills and semi-annual Class A & B Emergency drills will be conducted prior to the end of the First Quarter 1978 and as required thereafter. The Training Coor'dinator will factor these exercises into his training cycle to preclude recurrence. This action will be com-Pleted prior to 1 April 1978.

F.

Technical Specification 6.8.1.a requires written procedures j

to be implemented for the procedures recommended in Appendix 1

A of Regulatory Guide 1.33.

Appendix A, of Regulatory Guide l

1.33, Section J, specifies radiochemical laboratory instru-mentation calibration procedures shall be established.

Crystal River Surveillance Procedure SP-707, Section 6.2, i

requires weekly resolution determinations of the GeLi j

gamina spectroscopy system Contrary to the above, resolution determinations of the GeLi gamma spectroscopy system was not performed during the weeks of October 31 and November 15, 1977.

F. Response: As noted by the inspector during his visit, previous and subsequent resolution determinations demonstrated the adequacy of the system during the time periods in question.

Corrective steps to avoid further noncompliance were taken on 9 December 1928 with the issuance of Follow-up Report #77-360, which detailed the deficiency and pointed up the necessity for strict adherence to procedures and schedules.

This Follow-up Report was read and understood by all appropriate individuals in the Chem / Rad Section and initia11ed by them.

Further, an effort is currently underway to consolidate the scheduling of Chem / Rad surveillances, calibrations, and other routine activities.

This should assist in the prevention of lapses by providing better continuity.

This consolidation should be complete by 1 May 1978.

If there are further questions, please contact us.

Very truly yours, V]

d.

14 0 0

W. P. Stewart Director, Power Production DWP/rc Nuclear Plant Manager

.