4 og TABLE 3.3-4 SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION TRIP SETPOINTS C

FUNCTIONAL UtilT TRIP SETPOINT ALLOWABLE VALUES C*

INSTRUMENT STRINGS

~

a.

Containment Radiation

< 2 x Background at RATED

< 2 x Background at illERMAL POWER liATED THERMAL POWER, b.

Containment Pressure - liigh 1 18.52 psia #

1 18.4 psia Containment Pressure - liigh-liigh c.

1 38.52 psia #

1 38.4 psia d.

RCS Pressure - Low

> 1620.75 p'sig 1 1615.75 psig#

e.

RCS Prossure - Low-Low

> 420.75 psig

> 415.75 psig#

f. ' BWST Level

> 49.5 and 1 55.0 in.110

> 48.3 and 2

1 6.7 in.11 0, 5

2 CD SEQUENCE LP"IC CilANNELS Essential Bus Feeder Breaker Trip (90%)

o a.

p 2 3744 volts for

> 3558 volts for P,3 7 + 1.5 see for 7 + 1.5 sec#

l g

b.

Diesel Generator Start, toad Shed on C

Essential Bus (59z)

> 2071 and < 2450 volts

> 2071 and < 2450 for 0.5 + 0.1 sec volts for _

~

INTERLOCK CilANNELS 0.5 + 0.1 sec, a.

Decay lleat Isolation Valve

< 530 and > 413 psig

< 535 and > 408 psig#

Allowable Value for CllANNEL FUNCTI0tlAL TEST and CilAtlNEL CALIBRATI0ti.