ML19317F896
| ML19317F896 | |
| Person / Time | |
|---|---|
| Site: | Rancho Seco |
| Issue date: | 03/14/1977 |
| From: | Mattimoe J SACRAMENTO MUNICIPAL UTILITY DISTRICT |
| To: | |
| Shared Package | |
| ML19317F893 | List: |
| References | |
| NUDOCS 8002210622 | |
| Download: ML19317F896 (1) | |
Text
_ _ _ _. _. _ __
_,~
UCENSEE EVENT REPOf t,
CONTROL BLOCX:l l
l l l l )
(pLEASE PRINT ALL REQUIRED INFORMATION) 1 6
Auf UCENSE NUMBER TY E j C l A l Rl SlS ll'l l0 l0 l l 0l0 l0 l0 l0 l_ l 0 l 0 l l4l1l1l1l1l l0 l1l 7 89 14 15 25 26 30 31 32 CATEGORY TYP AC OCCKET NUMBE.,
EVENT DATE REPCAT CATE 01 CONT l P l I l l Ll lL l l0 l 5 l 0 l-l 0 l 3l1 l2 l l 0 l 2 l 1 l 8 l 7 l7 l l0 l3 l0 l9 l 7 l 7l 7 8 57 58 59 60 61 68 69 74 75 80 EVENT DESCRIPTION gg l During normal rounds on February 19, 1977, an Operator discovered the steam drive to l
7 89 80
.A Q l auxiliary feedpump P-318 tripped. The reduz.Jant auxiliary feedpump P-319 was out of l Ei 7 89 80 '
$ l service the previous day, so during that period no auxiliary feedwater flow was l
7 89 80 -
h I wnfinhie on safety features.
(R0 77-2) l 2
7 39 80 bl l
7 89 80 mE
$COE CCMPONENT CCCE SUPPLf.R M
VOLADCN RE l Hl 5l W l P l Ul Ml Pl X l X l lAl l Bl 0] 1l0 l lN l 7 89 10 11 12 17 43 44 47 48 g-CAUSE DESCAPTION ry gg l P-318 was tested' prior to taking P-319 out of service. When stopping P-318.by l
7 89 80 ~
gg l manual trip, an Operator failed to properly reset the trip.
Special training will. l 7 89 80 c l assure all Operators know the proper method of resetting the pump.
l -,'
'T
% POWEA GTHER STATUS dis CVERY OSCOVERY OESCRipTCN
[E l l1 l0 l 0 l l NA l
l NA l
1 7 8 9
10 12 13 44 45 48 SO AYL^ SED n
[2j OFdEASEl AMOUNT OF ACTMTY LOCATCN OF AELEASE NA l
l NA f,
l 7 8 9
10 11 44 45 80,
PERSONNEL EXPOSURES NUMBER TYpf CESCAIATON M l0 l0 l 0 l J l NA l
7 89 11 12 13 80 PERSONNEL INJUAIES NUMBER CESCAW37CN M l0l0l0l l NA l
7 89 11 12 80 OFFSITE CONSEQUENCES gg l Minimal to None l
7 89 80 LOSS CA DAMAGE TO FAC:UTY Tvpf CESCAN37CN
~
@ [Zj l NA l
7 89 10 80 PUBUCITY DE I tocal newsoaoers noti =ted 2/22/77 and 2/24/77 l
7 89 80 AGOITIONAL FACTORS
{ ]89l While neither pu=p was available on safety features, Pump P-318 also has a motor l
i j
80
'^~
drive which Could have been canually actuated had auxiliary feedwater flow been needed g
7 89 R. W. Colombo /F. T. Eisenhuth PHONE;(916) 452-3211 NAM E:--
GPO 881 667 8 0 02 210 $ M
,