Responds to 740715 Memo Requesting Review of Intent of Tech Spec 3.2.2.,High Pressure Injection & Chemical Addition Sys
ML19317E892
Person / Time
Site: Oconee  
Issue date: 07/26/1974
From: Sniezek S
US ATOMIC ENERGY COMMISSION (AEC)
To: Thornburg H
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML19317E894 List:
References
NUDOCS 8001070693
Download: ML19317E892 (1)


Text

$ v$

/

1 6

E G 1974 H. D. Thornburg, Chief, Field Support and Enforcowent Branch, RD DUEF. POWER COMPANY - OCONEE 1 AND 2. INTENT OF TECHNICAL SP j

3.2.2, RO:II MEHORANDUM DATED JULY 15, 1974 (F0#93HI)

In accordance with your request in PU 93H1, we have reviewed the subject nectorindum and have the following cocunents:

i Eased on a review of Facility Technical Specifications for Unita 1 and 2, we have concluded that the Concentrated Boric Acid Storage Tank System (CBAST) at a shutdown unit can be used to satisfy the requiras.ents of paragraph 3.2.2. of the i

j technical specifientions at the operatint unit provided:

1.

The. activity at the operating unit which required an auditional CBAST system had been proplanned.

1 2.

The activity at the operating unit, i.e., maintenance, testing, etc., will be perfomed in accord =ce with approved proceduros that require licensee personnel to i

verify that the shutdown unit CBAST system is aligned r

for the operating unit prior to initiating the activity.

3.

The procedures have been reviewed and approved as required t

by the technical specifications.

t

'!c believe this completes the action requested by IV 93Hl.

a Orig:# Lgru in F.f.Nolen J. H. Sniezek, Acting Chief Facility Inspection Branch Directorate of Regulatory Operations t

i t

cc:

B. H. Grier, R0 (CD 548)

L. McDonough, DL l

C. Upright, RO:II e

,1 l

RO: FIB

[ RO: FIB kg orrec e >

FNolan:1b JHSnieg[

l j:

7/25/75 7/25/74 Foran ABc.)lt (Rev. !P.53) ARCM 0240 ll',

4 wI W u. s. nova==nesur reinvene orrects sere.sas.see E