L. I Oconae Unit 1 DATE 7/9/75 1

DOCKET NO. 50-269 PREPARED BY M. S. 'Iuckman OPERATING STATUS l

1.

REPORTING PERIOD: June 1, 1975 THROUGH June 30, 1975 f

GROSS HOURS IN REPORTING PERIOD:

720.00 2.

CURRENTLY AUTHORIZED POWER LEVEL (MWt): 2568 NET CAPABILITY I

(MWe-Net):

871 3.

POWER LEVEL TO WHICH RESTRICTED (IF ANY):(MWe-Net)

None j

4.

REASONS FOR RESTRICTION (IF ANY) hiis Month Year to Date Cumulative j

5.

NUMBER OF HOURS THE REACTOR WAS i

CRITICAL 713.5 2742.3 12542.9 l

i 6.

REACTOR RESERVE SHUTDOWN HOURS 7.

HOURS GENERATOR ON-LINE 693.6 2536.8 10791.2 8.

UNIT RESERVE SHUTDOWN HOURS 9.

GROSS THERMAL ENERGY GENERATED (MWH)1736812 5801035 24038545 l

10.

GROSS ELECTRICAL ENERGY GENERATED (MWH) 606280 2041200 8359900 11.

NET ELECTRICAL ENERGY GENERATED (MWH) 578396 1922597 7875616 I

12.

REACTOR SERVICE FACTOR 99.1 63.1 73.1 13.

REACTOR AVAIIABILITY FACTOR 98.6 59.3 64.2 14.

UNIT SERVICE FACTOR 96.3 58.4 62.9 15.

UNIT AVILABILITY FACTOR 96.3 58.4 63.1 16.

UNIT CAPACITY FACTOR (Using Net 92.2 50.8 52.7 i

Capability) 17.

UNIT CAPACITY FACTOR (Using Design Mwe) 90.6 49.9 51.7 18.

UNIT FORCED OUTAGE RATE 3.7 41.1 21.3 19.

SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE & DURATION OF EACH:)

20.

IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP' REACTOR SERVICE FACTOR = HOURS REACTOR WAS CRITICAI X 100 llOURS IN REPORTING PERIOD REACTOR AVAILABILITY FACTOR = Hot?HS RTACTOR UAS AVAIIALLP TO Oi'ERATE X 100 110URS IN REPORTING PERIOD UNIT SERVICE FACTOR

= HOPPS CTEERATOR ON 1.lNE HOURS IN REPORTING PERIOD UNIT AVAIIABILITY FACTOR = liOURS UNIT WAS AVATIABLE TO GENERATE X 100 HOURS IN FEPORTING PERIOD UNIT CAPACITY FACTOR

= NET ELECTRICAL P0tlER CENERATED (Nat C.ipability or Design (Mag-Net)1 X 110UltS IN Rf','OhdNh.

f PERIOD'

,5 h}$}gQ p

UNIT FORCED OUTACE RATE = FORCEILOUTAGE_JJ0JJRS X 100 HOURS GENEILATOR ON 1.INE + FORCED OUTAGE HOURS

DdCKET NO.

50-269 Oconee Unit 1 UNIT SHUTDOWNS UNIT NAME DATli 7/9/75 REPORT MONTil __ June, 1975 TYPE METHOD 0; F FORCED DURATION SHUTTING DOWfl I

NO.

DATE S SCHEDULED (HOURS)

RE ASON (1)

THE REACTOR (2)

CORRECTIVE ACTIONS / COMMENTS 9

750608 F

16.5 A

3 Turbine tripped due to low turbine control oil pressure 10 750609 F

9.9 G

3 Unit tripped during restart due to high.

RC pressure while in manual control (1) REASON (2) METilOD A -EQUIPMENT F AlLUME (EXPLAIN) 1-MANUAL B-M AINT. OR TEST.

2-MANUAL D-REGULATO!tY RESTRICTION 3-AUTOM ATIC

_ )

C-MLl L'ELING SCR AM E-OPERATOR 1 RAINING AND SCRAM LICENSE EXAMINATION F-A DMINIST R ATIVE G-OPl.R A1:ON AL LRROR (LXPLAIN)

Il-OlllLR (EXP1 AIN) s

SUMMARY

Unit operated base loaded during the month.

n l

l

\\

DOCKET NO. 50-269 oconee Unit 1 UNIT DATE 7/9/75 AVERAGE DAILY UNIT POWER LEVEL June 1975 MONTH AVERAGE DAILY POWER LEVEL AVERAGE DAILY POWER LEVEL DAY (MWe-net)

DAY (MWe-net) 850 862 17 1

861 18 849 2

849 864 jg 3

848 4

864 20 851 5

864 21 6

865 22 852 7

866 23 852 8

146 24 820 g

297 25 854 755 2d; 854 10 762 27 853 11 8 17 28 849 12 848 852 29 13 851 30 851 14 847 31 15 849 16 DAILY UNTT POWER LEVEL FORM INSTRUCTIONS On this form, list the average daily unit power level in MWe-net for each day in the reporting month.

Compute to the nearest whole megawatt.

These figures will be used to plot.i graph for each reporting month. Note that by using maximum dependable capacity for the net electrical rating of the unit there may be occasions when the daily average power level exceeds the 1007o line (or the restricted power lesel line). In such cases the average daily unit power output sheet should be footnoted to explain the apparent anomaly.