Responds to NRC Re Violation Noted in IE Insp Rept 50-269/74-05.Corrective Actions:Process Monitors Being Modified According to Schedule Given
ML19317E477
Person / Time
Site: Oconee 
Issue date: 02/14/1975
From: Thies A
DUKE POWER CO.
To: Moseley N
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19317E472 List:
References
NUDOCS 7912180724
Download: ML19317E477 (2)


Text

.

DUKE PowEre COMPANY i

i Powen Betustwo 422 SouT2r Casuncit STnEET, CatAnr.oTTE.N. C. ascot i

A. C. Tra r es P. Ol. Box cuo Steios W:c Pets ct=r F#C9vCf 44 seso ?#as$m,,Sw)=

February 14, 1975 hk. Norman C. Moseley, Director U. S. Nuclear Regulatory Commission Suite 818 230 Peachtree Street, Northwest Atlanta, Georgia 30303

Subject:

Oconee Nuclear Station RO Inspection Report 50-269/74-5

Dear Mr. Moseley:

In response to your letter of August 14, 1974 which transmitted RO 50-269/74-5, my letter of September 9, 1974 Inspection Report identified target dates for resolution of problems associated with Monitors RIA-33 and -34 process monitors at Oconee Nuclear Station.

were to be moved to the turbine building floor prior to November 15, However, due to unavailability of proper materials, this modifi-1974.

cation could not be completed prior to November 15, 1974.

Materials have been received and work is currently underway to move the The modification is expected to be completed prior to monitors.

April 1, 1975.

stainless steel Monitors RIA-37 and -38 were modified by installing collinators prior to the Nove=ber 15, 1974 target date mentioned in our response of September 9,1974.

However, test results indicate that this modification was unsuccessful in reducing the large gamma It is anticipated that field and additional testing is in progress.

this additional testing will be complete prior to April 1, 1975.

The prefilters in RIA-44 and RIA-48 have not yet been relocated dueA to unavailability of required parts to be provided by the vendor.

station modification report has been initiated to modify these process monitors and will be completed as soon as appropriate parts are It is anticipated that these codifications will received on site.

be coeplete prior to April 1, 1975.

With regard to monitors RIA-43 and RIA-47, my letter of November 27, 1974, which responds to your request for additional _ infor=ation in

?

.y l W, 3 912180 77h'

s

' Mr. Norman C. Moseley

(~h Page 2 February 14, 1975 Inspection Report 50-269/74-9, it was stated that a test program would be initiated to resolve problems with the stack effluent monitors.

Appropriate modifications have been cade to the monitors for Oconee Unit 1, and the test and evaluation period required will co=cence when unit operation resumes following its refueling outage.

After approximately one month of testing and provided the results are favorable, the other monitors will be modified within six weeks.

Very truly yours, kb A. C. Thies ACT:vr 0

.