Forwards IE Circular 80-11, Emergency Diesel Generator Lube Oil Cooler Failures. No Written Response Required
ML19316A876
Person / Time
Site: Davis Besse 
Issue date: 05/13/1980
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Crouse R
TOLEDO EDISON CO.
References
NUDOCS 8005280015
Download: ML19316A876 (1)


Text

/'g3 CRCvg#'o UNITED STATES TIC

[ 'Y,,,,

P g NUCLEAR REGULATORY COMMISSION g

'c e

REGION lli o,

f 799 ROOSEVELT ROAD b

GLEN E LLYN, ILLINOls 60137 o

    • ..+

'WAY 13 880 Docket No. 50-346 Toledo Edison Company ATTN:

Mr. Richard P. Crouse Vice President Nuclear Edison Plaza 300 Madison Avenue Toledo, OH 43652 Gentlemen:

The enclosed IE Circular No. 80-11 is forwarded to you for informa-tion. No written response is required. Should you have any questions related to your understanding of the recommendations on this matter, please contact this office.

Sincerely, SY, James G. Kepp er Director

Enclosure:

IE Circular No. 80-11 cc w/ enc 1:

Mr. T. Murray, Station Superintendent Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Harold W. Kohn, Power Siting Commission Helen W. Evans, State of Ohio 80052800 F

/

SSINS No.: 6830 Accession No.:

UNITED STATES 8002280662 NUCLEAR REGULA")RY COMMISSION D

, D ns 0FFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 JJ b

,o May 13, 1980 IE Circular No. 80-11 EMERGENCY DIESEL GENERATOR LUBE OIL COOLER FAILURES Description of Circumstances:

Within a two week per'ad (August 27 to September 11,1979), the tube sheets failed in the lube o'I coolers of both emergency diesel generators for Arkansas Nuclear One (ANO) Urit No. 1.

The introduction of water into the diesel lube oil system resulted in trips of both diesels during surveillance testing.

The diesels were not crasidered capable of sustained operation.

These events were previously identif.ed to all operating license and construction permit holders by Information Nr. ice 79-23, Emergency Diesel Generator Lube Oil Cooler on September 25, 19~9.

The emergency diesel generators involved were manufac-tured by the Elrctro-Motive Division (EMD) of the General Motors Corporation and the failurei occurred on engines 71-Al-1117 and 71-Al-1130.

The failed lube oil coolei; were manufactured by the Young Radiator Company.

An analysis of the failed coolers performed by EM9 resulted in the conclusion that the failures were caused by severe corrosion of the solder which sealed the tubes to the tube sheets. The corrosion inhibitor in use at ANO was Calgon CS, a borate-nitrite type inhibitor. The manufacturer of this type of inhibitor has recommended the use of hard solder in CS treated systems.

EMD does not recommend the use of Calgon CS since the puddle solder used in EMD radiators and oil coolers is considered to be soft solder of a lead-tin composition.

Recommended Action for Licensees' Consideration:

Based on the above, it is recommended that licensees:

1.

Verify that the corrosion inhibitor used in cooling water systems of the emergency diesel generators is-compatible with all materials wetted by the cooling water and the engine manufacturer's specific recommendations.

Also, by means c' the engine maintenance history, verify that the system corrosion inhibitcr has been properly monitored and maintained at the recommended concentration.

2.

If Item 1 cannot be successfully performed, the affected components should be inspec'.d in accordance with the manufacturer's recommendations.

No written response to this Circular is required.

If you desire additional information regar6ing this matter, contact the Director of the appropriate NRC Regional Office.

1

e IE Circular No. 80-11 Enclosure May 13, 1980 RECENTLY ISSUED IE CIRCULARS Circular Subject Date of Issued to No.

Issue 80-10 Failure to Maintain 4/29/80 All holders of Reactor Environmental Qualification OLs and cps of Equipment 80-09 Problems With Plant Internal 4/28/80 All holders of a power Communications Systems reactor OL or CP 80-08 BWR Technical Specification 4/18/80 All General Electric Inconsistency - RPS Response BWR's holding a power Time reactor OL 80-07 Problems with HPCI Turbine 4/3/80 All holders of a power Oil System reactor OL or CP 80-06 Control and Accountability 4/14/80 Medical licensees in Systems for Implant Therapy Categories G and G1 Sources 80-05 Emergency Diesel-Generator 4/1/80 All holders of a power Lubricating Oil Addition and reactor OL or CP Onsite Supply 80-04 Securing of inreaded Locking 3/14/80 All holders of a power Devices on Safety-Related reactor OL or CP Equipment 80-03 Protection from Toxic Gas 3/6/80 All holders of a Hazards power reactor OL 80-02 Nuclear Power Plant Staff 2/1/80 All holders of Reactor Work Hours Ols, including research and test reactors, and cps 80-01 Service Advice for GE 1/17/80 All licensees of Induction _ Disc Relays nuclear power reactor operating facilities and holders of nuclear power reactor cps l