ML19316A272

From kanterella
Jump to navigation Jump to search
Responds to NRC Ltr Re Violations Noted in IE Insp Repts 50-269/77-02,50-270/77-02 & 50-287/77-02 Supplementing 770412 Resonse.Corrective Action:Procedure Being Developed for Counting,Evaluating & Applying Ratio Method by 770601
ML19316A272
Person / Time
Site: Oconee  
Issue date: 04/26/1977
From: Parker W
DUKE POWER CO.
To: Moseley N
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19316A270 List:
References
NUDOCS 7912050843
Download: ML19316A272 (2)


Text

.

DUKE POWER COMPANY Powzn Buttotwa 422 Socin Caracu Srazzr. Crunt.orTz. N. C. mea 4a wtLLeAM O. pa m m t m, s (

VsCE PetOOtut TELt*=0NC Anga 704 Seca Peooveica 37>4oe3 April 26, 1977 Mr. Norman C. Moseley, Director U. S. Nuclear Regulatory Commission Suite 818 230 Phachtree Street, Northwest Atlanta, Georgia 30303 Re:

IE:II:CEA 50-269/77-2 50-270/77-2 50-287/77-2

Dear Mr. Moseley:

My letter of April 12, 1977 provided a response to Item 1 contained in IE Inspection Report 50-269, -270, -287/77-2.

The following information is provided to supplement that response.

As stated in the response a detailed analysis on liquid waste samples will be performed monthly to assure that sensitivity j

limits are met for those gamma emitters of low energy and abundance contained in certain mixtures of gamma emitting nuclides. This will be performed until a proposed technical specification amendment is approved by the NRC.

Currently, a procedure is being developed for the counting, evaluating, and applying the ratio method to ease the requirements on routine samples.

Testing is being accomplished in which three liters of effluent (combined from laundry, condensate monitor, and condensate test tanks) will be ion exchanged with 55 cc i

of mixed resin. The resin and eluate will both be counted to determine minimum detectable activity (MDA's) for those radio-nuclides not routinely identified in effluent samples.

These MDA's will be ratioed to radionuclides routinely identified.

1 The ratios of routinely identified radionuclides in the (ion exchanged) samples will be compared to similar ratios for several effluent releases to verify uniform applicability of this method. This method will be repeated monthly to t

i 1

^

---. ~ ~ -

e i

)

Mr. Norman C. Moseley Page 2 April 26, 1977 assure that the ratios are not changing or to document changing ratios.

This procedure should be completed by June 1, 1977.

Very truly yours, W L e.ALL + p William O. Parker, Jr.

MST:vr i

e o.

. ;s.> >

v.) 36

. c e o