Text
.
k 4
O APPENDIX A Washington Public Power Supply System P. O. Box 968 Richland, Washington 99352 Docket No. 50-460 Construction Permit No. CPPR-134 NOTICE OF DEVIATION Based on the results of an NRC inspection conducted during the period of March 1-31, 1980, it appears that one of your activities was not conducted in full conformance with your commitments to the Commission as indicated below:
Contrary to the licensee's commitment in paragraph 5.2.3.1 and Table 5.2-5 of the PSAR that weld material specification SFA-5.5 would govern the i
special E-7018 welding electrodes used for reactor coolant pressure boundary welds, welding electrodes qualified under specification SFA-5.1 rather than SFA-5.5 were used for welding the pipe-to-steam generator reactor coolant pressure boundary welds, l
i 1
..