ML19310A584

From kanterella
Jump to navigation Jump to search
Forwards Request for Addl Info Re High Range Monitors to Continue Review of Fsar.Requests Submittal by 800615
ML19310A584
Person / Time
Site: North Anna 
Issue date: 05/31/1980
From: Dromerick A
Office of Nuclear Reactor Regulation
To: Ferguson J
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
References
NUDOCS 8006200302
Download: ML19310A584 (4)


Text

_ - - -_ _____

T/C p#" "'4[*

UNITED STATES h.

NUCLEAR REGULATORY COMMISSION 3,, I 5'.

g WASHWGTON, D. C. 20555

  • h)#%,',,, #)

o MAY 311980 Docket No. 50-339 Mr. J. H. Ferguson Executive Vice President - Power Operations Virginia Electric & Power Company P. O. Box 26666 Richmond, Virginia 23261

Dear Mr. Ferguson:

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW 0F THE NORTH ANNA POWER STATION, UNIT 2 FINAL SAFETY ANALYSIS REPORT (FSAR)

As a result of our continuing review of the North Anna FSAR, we find that we need additional information to complete our evaluation. The specific infor-mation required is listed in the enclosure.

Our review schedule is based on the assumption that this additional information will be available for our review by June 15, 1980.

If you cannot meet this date, please inform us within seven days after receipt of this letter so that we may revise our schedule accordingly.

Please contact me (Telephone - 301-492-7100) if you desire any discussion or clarification of the enclosed request.

Sincerely,

' f

!M ur Alexander W. Dromerick, Project Manager Licensing Branch No. 1 Division of Licensing

Enclosure:

Request for Additional Information cc: w/ enclosure See next page s

8006200301 f

i

~

T Mr. J.

H., Ferguson Executive Vice President - Power Operations Virginia Electric & Power Company P. O. Box 26566

. Richmond, Virginia 23261 cc:

Mr. Anthony Gambaradella Clarence T. Kipps, Jr., Esq.

Office of the Attorney General 1700 Pennsylvania Avenue, N.W.

11 South 12th' Street - Room 308 Washingtun, D. C.

20006 Richmond, Virginia 23219 Carroll J. Savage, Esq.

Richard M. Foster, Esq.

1700 Pennsylvania Avenue, N.W.

Musick, Williamson, Schwartz Washington, D. C.

20006 Leavenworth & Cope, P. C.

P. O. Box 4579 Mr. James C. Dunstan Boulder, Colorado 80306 State Corporation Comission Comonwealth of Virginia Michael W. Maupin, Esq.

Blancon Building Hunton, Williams, Gay & Gibson Richmond, Virginia 23209 i

P. O. Box 1535 Richmond, Virginia 23212 Alan S. Rosenthal, Esq.

Atomic Safety and Licensing Appeal Board Mrs. June Allen U.S. Nuclear Regulatory Comission 412 Owens Drive Washington, D. C.

20555 Huntsville, Alabama 35801 Michael C. Farrar, Esq.

Mrs. James Torson Atomic Safety and Licensing Appeal Board 501 Leroy U.S. Nuclear Regulatory Comission Socorro, New Mexico 87801 Washington, D. C.

20555 Mrs. Margaret Dietrich Dr. John H. Buck Route 2, Box 568 Atomic Safety and Licensing Appeal Board Gordonsville, Virginia 22942 U.S. Nuclear Regulatory Comission Washington, D. C.

20555 William H. Rodgers, Jr., Esq.

Georgetown University Law Center Atomic Safety and Licensing Board Panel l

600 New Jersey Avenue, N. W.

U.S. Nuclear Regulatory Comission Washington, D. C.

20001 Washington, D. C.

20555 Mr. Peter S. Hepp Mr. Michael S. Kidd Executive Vice President U.S. Nuclear Regulatory Comission Sun Shipping & Dry Dock Company P. 0. Box 128 P. O. Box 540 Spotsivania, Virginia 22553 Chester, Pennsylvania 19013 i

Dr. Paul W. Purdom Mr. R. B. Briggs Department of Civil Engineering Associate Director Drexel University 110 Evans Lane Philadelphia, Pennsylvania 19104 Dak Ridge, Tennessee 37830 j

s.

T Mr. J. H. Ferguson cc: Dr. Lawrence R. Quarles Apartment No. 51 Kendal-at-Longwnod Kennett Square, Pennsylvania 19348 Mr. Irwin B. Kroot Citizens Energy Forum P. O. Box 138 McLean, Virginia 22101 James B. Dougherty, Esq.

Potomac Alliance 1416 S Ctreet, N.W.

Washington, D. C.

20009 W. R. Cartwright, Station Manager P. O. Box 402 Mineral, Virginia 23117 W. L. Stewart, Manager P. O. Box 315 Surry, Virginia 23883 i

e-d REQUEST FOR ADDITIONAL INFORMATION ENCLOSURE NORTH ANNA POWER STATION, UNIT 2 DOCKET N0.

50-339 NUREG-0578 - Item 2.1.8.b Provide a description of the two high range containment monitors required by our letter of November 9,1979, implementing the lessons Learned item 2.1.8.b of NUREG-0578, and specify the location of these monitors inside containn.ent. The description of the monitcrs should include:

a. type of radiation measured;
b. the range or ranges of the monitors.

If two or more monitors are required to span the range in Table 2.8.1.b.3 of our 8

7 November 9,1979 letter (10 rad /hr total radiation or 10 R/hr photons only), the ranges of the subsystem monitors must overlap (i.e., upper value/ lower value of overlap) by at least a factor of 10;

c. location of and type of readout (continuous and recording);
d. energy response (sensitive 60 kev);
e. calibration frequency and methods (refueling frequency);
f. verification that the monitors are powered separate vital instrumental buses;
g. Verification that the monitors will be operational by full power;
h. verification that the moniors meet the seismic qualification of Regulatory Guide 1.100 (Seismic Category I) and are environ-mentally qualified to survive an in-containment LOCA in 1

accordance with Regulatory Guide <1.89.

The location of the monitors should be shown on plant layout drawings.

The monitors should be 1bcated in a manner as to provide a reasonable assessment of radiation levels inside containment.

Monitors should not be placed in areas which are protected by massive shielding.

_ _ _.