cx j

ff Io UNITED STATES g

y

,m g

NUCLEAR REGULATORY COMMISSION E

WASHINGTON, D. C. 20555 I

May 23, 1980 Docket No. 50-70 Mr. R. W. Darmitzel, Manager Irradiation Processing Product Section

(

Vallecitos Nuclear Center j

General Electric Company l

P. O. Box 460 Pleasanton, California 94565

Dear Mr. Darmitzel:

On September 27, 1979 the NRC staff issued its position regarding the proper geologic and seismic design bases for the General Electric Test Reactor (GETR).

In that report the staff stated that a surface offset of two and a half meters could occur beneath the GETR and specified maximum vibratory ground motion in terms of acceleration peaks at the free field surface.

Based on our review of additional information regarding thi subject, including probability analyses, the staff is modifying its previous p _ition as discussed in the enclosed Safety Evaluation. The staff now concludes that a surface offset of one meter beneath the GETR is an appropriate design basis and maximum vibratory ground motior.S are specified in terms of acceleration values anchoring the Regula-tory Guide 1.60 response spectra. The design bases specified by the staff are summarized on Section C, page 2 of the enclosed evaluation.

As noted in Section C we must complete our review of the reports recently submitted before we can make a judgment on the adequacy of the modified GETR's seismic design.

Based on the results of that review additional structural analysis may be necessary.

Also, as noted in Section A, you must provide the results of your landslide investi-gation before we can complete our review of the GETR geologic and seismic design bases. You are requested to provid your schedule for submitting these results.

incerely, T

b

,,t[

Darrell G.

igen u,'

r i

Division of Operating Reactors Office of Nucle 3r Reactor Regulation

Enclosure:

j Safety Evaluation l

cc w/ enclosure:

See next page THIS DOCUMENT CONTAINS P00R QUAUTY PAGES 8006060ki$ S L.

\\

..=: -

G:neral Electric Company ec w/ enclosure (s):

California Department of nealtn ATTN:

Chief, Environmental Radiation Dr. Harry Foreman, Member Control Unit Atomic Safety and Licensing Board Radiologic Health Section Box 395, Mayo 714 P Street, Room 498 University of Minnesota Sacramento, California 95184 Minneapolis, Minnesota 55455 Honorable Ronald V. Dellums Ms. Barbara Shockley ATTN: Ms. Nancy Snow 1890 Bockman Road General Delivery, Civic Center San Lorenzo, California 94580 Station Oakland, California 94604 Advisc / Committee on Reactor Safrguards Friends of the Earth U. S. Nuclear Regulatory Commission ATTN:

W. A.1dree Baldwin, Esquire Washington, D. C.

20555

~

Legal Director 124 Spear Street San Francisco, California 94105 Jed Somit, Esquire 100 Bush Street Suite 304 San Francisco, California 94104 Herbert Grossman, Esq., Chairman Atomic Safety and Licensing Board U. 5. Nuclear Regulatory Commission Washington, D. C.

20555 Mr. Gustave A. Linenberger, Member Atomic Safety and Licensing Board U. S. Nuclear Regulatory Commission Washington, D. C.

20555 George Edgar Esquire Morgan, Lewis & Bockius 1800 M Street, NW Washington, D. C.

20036

%