ML19309H779
| ML19309H779 | |
| Person / Time | |
|---|---|
| Site: | Columbia, Washington Public Power Supply System, Satsop |
| Issue date: | 05/08/1980 |
| From: | Engelken R NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V) |
| To: | Strand N WASHINGTON PUBLIC POWER SUPPLY SYSTEM |
| References | |
| NUDOCS 8005190706 | |
| Download: ML19309H779 (1) | |
Text
-
['
%'o,,
soo3,OU 7c%
7TD UNITED STATES
!*i NUCLEAR REGULATORY COMMISSION o
REGION V c
o, g
1990 N. CALIFORNIA BOULEVARD e"
SUITE 202, WALNUT CREEK PLAZA e,,,o WALNUT CREEK, CALIFORNI A 945%
i May 8, 1980 Docket Nos. 50-397, 50-460, 50-508 50-509, 50-513 t
Washington Public Power Supply System P. O. Box 968 3000 George Washington Way Richland, Washington 99352 Attention: Mr. N. O. Strand Managing Director Gentlemen:
The enclosed Information Notice provides early notification of an event that may have safety significance. Accordingly, you should review the Information Notice for possible applicability to your facility.
No specific action or response is requested at this time; however, contingent upon the results of further staff evaluation, a Bulletin or Circular recommending or requesting specific licensee actions may be issued.
If you have questions regarding this matter, please contact me.
Sincerely, Jmd&
R. H. Engelken Director
Enclosures:
1.
IE Information Notice No. 80-20 2.
List of Recently Issued IE Information Notices cc w/enciasures:
M. E. Witherspoon W. C. Bibb 1
J. P. Thomas W. J. Talbott G. C. Sorensen
+,
m
SSIlls flo. : 6870 UNITED STATES Accession No.:
NUCLEAR RECULATORY COMMISSION 8002280671 0FFICE OF INSPECTION AND EllFORCEMENT WASHIflGTON, D. C. 20555 May 8, 1980 IE Information Notice 80-20 LOSS OF DECAY HEAT REf10 VAL CAPABILITY AT DAVIS-BESSE UNIT 1 WHILE IN A REFUELIflG MODE Description of Circumstances:
On April 19, 1980, decay heat removal capability was lost at Davis-Besse Unit 1 for app'oximately two and one-half hours. At the time of the event, the unit was in a refueling mode (e.g., RCS temperature was 90F; decay heat was being removed by Decay Heat Loop No. 2; the vessel head was detensioned with bolts in place; the reactor coolant level was sli htly below the vessel head flanges; g
and the manway covers on top of the once through steam generators were removed).
(See Enclosure A, Status of Davis-Besse 1 Prior to Loss of Power to Busses E-2 and F-2 for additional details regarding this event.)
Since the plant was in a refueling mode, many systems or components were out of service for maintenance or testing purposes.
In addition, other systems and components were deactivated to preclude their inadvertent actuation while in a refueling mode.
Systems and components that were not in service or deactivated included:
Containnent Spray System; High Pressure Injection System; Source Range Channel 2; Decay Heat Loop fio. 1; Station Battery IP and 1N; Emergency Diesel-Generator No. 1; 4.16 KV Essential Switchgear Bus C1; and 13.8 KV Switchgear Bus A (this bus was energized but not aligned).
In brief, the event was due to the tripping of a non-safeguards feeder breaker in 13.8 KV Switchgear Bus 3. Because of the extensive maintenance and testing activities being) conducted at the time, Channels 1 and 3 of the Reactor Protec-tion System (RPS and Safety Features Actuation System (SFAS) were being ener-gi:ed from only one source, the source emanating from the tripped breaker.
Since the SFAS logic used at Davis-Besse is a two-out-of-four input scheme in which the loss (or actuation) of any two input signals results in the actuation of all four output channels (i.e., Channels 1 and 3, and Channels 2 and 4), the loss of power to Channels 1 and 3 bistab1m alen rae"1+ad 4a
'-+-+4-Channels 2 and 4.
The actuation of Decay Heat loop No. 2, the operatin Since the initiating event was a lo DUPLICATE DOCUMENT were actuated (i.e., Level 1 - High tion; Level 3 - Low Pressure Inject Entire document previously entered into system under: