O 800507o 7 (> 7 APPENDIX A NOTICE OF VIOLATION Carolina Power and Light Company License No. DPR-62 Brunswick Based on the NRC inspection January 2 - February 2,1980, certain of your activi-ties were apparently not conducted in full compliance with NRC requirements as indicated below. These items have be?n categorized as described in correspondence to you dated December 31, 1974.
As required by 10 CFR 50, Appendix B,Section V, activities affecting quality shall be prescribed by documented instructions and procedures of a type appropriate to the circumstances. ANSI.N18.7-1972, as committed to by the Carolina Power and Light Company Quality Assurance Program, requires in Section 5.2.7 that maintenance of equipment shall be performed in accordance with written procedures.
Contrary to the above, maintenance was performed on November 29, 1979 during which a flexible conduit to flow switch E11-FSL-N021A was replaced without an adequate procedure. During the replacement a disconnected energized lead came in contact with the switch case resulting in a power failure to Division "H" of RHR logic.
This is an Infraction.