l l
l l
l l
(PLEASE PRINT ALL RtCUtRED INFCRM AT*C.
{
1 6
i
[
~
AME UCENSE NUMBER PE (J l FlL l ClR lP l3 l l0 l0 l-l0 l 0 l 0 l 0 l 0 l-l 0 l 0 l l 4 l1 l1 l1 l 1l l0 l3 l
,7 89 14 15 25 26 30 31 32
" 7PE EVENT oATE REPORT CATE CATEcoRY T
E CoCKET NUMBER 0 1 CON'T l l _ l l Ll lo l5 l0 l-l0 l3 l0 l? l l0 l7 l0 l2 l7 l7l l 0 l 7 l2 l8 l7 l~,
7 8 57
$8 59 60 61 68 69 74 75 t
EVENT DESCRIPTION gg l In mode 2 operation while performing operability test of rod 3 group 6 API, the absolute j
7 89 t !
Ql position indication for all regulating rods was lost, creating a ec.2dition as defined 7 89 L
Ql by Tech Spec 3.0.3.
Redundancy was maintained with the relative position indication.
7 89 L l Ql This was a non-repetitive occurrence. Maintenance restored the API system operable 7 09 (LER 77-75)
E DE l within 8 minutes.
7 89 E,
m,,
EE CCCE COMpor4ENT CCCE ACT 4
VCLATCN Q lIl Dl lF l l Il Nl S l Tl Rl Ul lNl l Dl1 l 5 l 0 l g
7 89 10 11 12 17 43 44 47 48 CAUSE DESCRIPTION
'p
- ~
l The 15 volt power supplies for the API system crowbarred due to a spike of unknown e
7 89 6-0 l origin and were reset restoring system operability; f
6 9
E l
's'TE
% POWER oTHER STATUS
-Cr5 CVERY e6 COWRY CESCMT:CN Q
]
[0 l0 l0 l l NA l
l Al l
1A 70 9
10 12 13 44 45
'46 8.
ACTMTV CCATENT RELEASEO CF RELEASE l AMCUNT OF ACTMTV LOCAT:CN CF RELEASE y
NA l
l NA
]
1 7 8
.9 10 11 44 45 St PERSONNEL EXPOSURES NUMBER TYPE DESC341PTICN Q l0 l0 l0 l Wl NA 7 89 11 12 13 Es PERSONNEL INJUAIES NUMBER DESCRPTON E l0l0l0_l l
NA 7 89 11.12 SC OFFSITE CONSECUENCES
,Ql NA l
7 89 Bt LOSS OR OAMAGE TO FAC:UTY TYPE CESCRPTON bl NA 1
7 89 10 LC PUBUCITY l
17 l NA I
7 89 UC ADDITIONAL FACTORS
}l See attached Supplementary Information as89 8 0 02 280 fp 7 89 to NAME:
W. P. Stewart (813) 866-4159 PHONE:
_q,- l cPo one.ssT l
~
~
~
SUPPLDfENTARY INFORMATION
~,,..
N.
Report No.: 302/77-75 2.
Facility:
Crystal River Unit #3 4
3.
Report Date:
28 July 1977 4.
Occurrence Date:
2 July 1977 5.
Identification of Occurrence:
The loss of all absolute position indication resulted in a limiting condition for operation in excess of those addressed in the Specifications as defined by Technical Specification 3.0.3.
6.
Conditions Prior to Occurrence:
Mode 2 startup operation.
7.
Description of Occurrence:
At 0435 while performing operability test of the absolute position indication of rod 3 of group 6, the absolute position indication for all rods was lost. The Electrical Supervisor i was immediately notified and preparations were made to go to hot standby within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, as required by Technical Specifications. The v.ssolute position indication system was restored operable within 8 minutes.
Designation of Apparent Cause:
An apparent, spike from an unknown origin causet a crowbar of the API 15 alt power supplies. The power supplies were reset and th 1 API system restored operable.
9.
Analysis of Occurrence:
3 There were no safety implications as a result of this occurrence.
10.
Corrective Action:
No corrective action deemed necessary as normal maintenance restored system operability.
11.
Failure Data:
i This was not a repetitive occurrence.
-