@ CON'T l - l - l lLl lLl l0l5l0l-l0l3l0l2l l 0l 6l 1l 6 l7 l7 l l0 l 7l 0 l 8 l 7 l 7 l 7 0 57 50 59 60 61 68 69 74 75 00 EVEtjT DESCR:PTION o2 l Inoperability of one pair of Auxiliary Building exhaust fans contrary to Technical l
7 89 00 03 l Specification 3.7.8.#1.
Redundant fans were operable and available.
First occurrence l
7 89 00 04 l of this event.
Repairs to ductwork restored fans operable on 21 June 1977.
l 7 89 SO
@l l
7 09 80
@l I
7 03 PAME 60
'cEt C0SE
.(LER 77-64)
CCMPoNENT COCE U
t VOLADou h lAl Al d lZlZlZlZlZlZl
[d l Zl 9l 9 l9 l d
7 89 10 11 12 17 43 44 47 48 CAUSE DESCRIPTION O
~,
3C l Ductwork vibration caused a leak in duct between the fan exhaust and the discharee l
7 89 GO O9 l damper.
Leak was reoaired with a laminated catch 'to strenethen the ductwork and l
7 09 60 P'
preclude reoccurrence.
l 5 TUS
% POWER bfHERSTATUS D3COVERY OCCOVERY CESCRIPTON W
l 0l9 l5 l l NA l
lAl l
NA l
1 70 9
10 12 13 44 40 46 60 EASED OF ASE AMOUNT OF ACTMTY LOCATON OF AELEASE W
dl NA l
l 1
NA l
7 8 9
10 11 44' 45 00 PERSONNEL E\\'POSURES NUMBER TYPE DESCAiPTON 8 l 0 l 0 l 01
[Z_J l
NA l
7 89 11 12 13 60 PERSONNEL INJunlES NUMDER DESCRPTCN 8 10l0l01 I
NA l
7 09
.11 12 60 OFFSITE CONSEQUENCES 3D l
' NA l
7 0D 00 LOSS OR CAP.1AGF TO FAC!UTY TYPE DESCA:P'ON
@dl NA 7 89 10
_ l LO PUDLfCITY 8I NA l
/ 00 L:0 "GOITIONAL FACT 0nS
!1 See attached Supolementarv Information
,j,
800227o 73 3 l 8l I
l
' UU nu NAME:
N.
D.
S t e'm rt THONE: (813) 866-4159
/
cro a n i... r. T
k SUPPLEMENTARY INFORMATION 1.
Report No.:
50-302/77-64 2.
Facility:
Crystal River Unit #3 3.
Report Date:
8 July 1977 4.
Occurrence Date:
16 June 1977 5.
Identification of Occurrence:
Inoperability of one pair of Auxiliary Building erhaust fans contrary to Technical Specification 3.7.8.1.
6.
Conditions Prior to Occurrence:
Mode 1 power operation 7.
Description of occurrence:
s At 2120 the Auxiliary Building exhaust fans AHF 14A and AHF 14C were removed from service due to a duct leak located between the fans and the discharge damper. Entered a seven day Action Statement and the duct was repaired with a laminated patch. The system was restored operable on 21 June 1977.
8.
Designation of Apparent Cause:
The cause of this event was determined to be vibration of the system ductwork causing ' a hole between the fans and the discharge damper.
9.
Analysis of Occurrence:
There was no safety significance in that redundant buiiding exhaust system was available and operable.
10.
Corrective Action:
A laminated patch was installed and is expected to strengthen the ductwork to prevent reoccurrence.
11.
Failure Data:
This was the first occurrence of such an event.