RO-77-64:on 770616,auxiliary Bldg Exhaust Fans Ahf 14A & 14C Inoperable.Caused by Sys Ductwork Vibration Causing Hole Between Fans & Discharge Damper.Laminated Patch Installed to Strengthen Ductwork
ML19308D287
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 07/08/1977
From: Stewart W
FLORIDA POWER CORP.
To:
Shared Package
ML19308D095 List:
References
NUDOCS 8002270733
Download: ML19308D287 (2)


Text

(])

UCENSEE EVENT REPOHT l

~

[(

CONTROL DLOCK:l t

l l

l l

l (PLEASE PRINT ALL ilEGUIRtD ifJFCRT.17.TlC.';;

.l 1

6 AME LCENSE NUMOER PE TYPE F l L l~ C'l R l P l 3 l l 0 l 0-l-l 0l 0 l 0 l 0 l 0 l-l 0 l 0 l l 4l 1l 1l 1l 1l l 0l 3l 7 89 14 15 25 26 30 31 32 T7PU S5 N CATECCRY COCKET NUMOER EVENT DATE AEPOAT CATE

@ CON'T l - l - l lLl lLl l0l5l0l-l0l3l0l2l l 0l 6l 1l 6 l7 l7 l l0 l 7l 0 l 8 l 7 l 7 l 7 0 57 50 59 60 61 68 69 74 75 00 EVEtjT DESCR:PTION o2 l Inoperability of one pair of Auxiliary Building exhaust fans contrary to Technical l

7 89 00 03 l Specification 3.7.8.#1.

Redundant fans were operable and available.

First occurrence l

7 89 00 04 l of this event.

Repairs to ductwork restored fans operable on 21 June 1977.

l 7 89 SO

@l l

7 09 80

@l I

7 03 PAME 60

'cEt C0SE

.(LER 77-64)

CCMPoNENT COCE U

t VOLADou h lAl Al d lZlZlZlZlZlZl

[d l Zl 9l 9 l9 l d

7 89 10 11 12 17 43 44 47 48 CAUSE DESCRIPTION O

~,

3C l Ductwork vibration caused a leak in duct between the fan exhaust and the discharee l

7 89 GO O9 l damper.

Leak was reoaired with a laminated catch 'to strenethen the ductwork and l

7 09 60 P'

preclude reoccurrence.

l 5 TUS

% POWER bfHERSTATUS D3COVERY OCCOVERY CESCRIPTON W

l 0l9 l5 l l NA l

lAl l

NA l

1 70 9

10 12 13 44 40 46 60 EASED OF ASE AMOUNT OF ACTMTY LOCATON OF AELEASE W

dl NA l

l 1

NA l

7 8 9

10 11 44' 45 00 PERSONNEL E\\'POSURES NUMBER TYPE DESCAiPTON 8 l 0 l 0 l 01

[Z_J l

NA l

7 89 11 12 13 60 PERSONNEL INJunlES NUMDER DESCRPTCN 8 10l0l01 I

NA l

7 09

.11 12 60 OFFSITE CONSEQUENCES 3D l

' NA l

7 0D 00 LOSS OR CAP.1AGF TO FAC!UTY TYPE DESCA:P'ON

@dl NA 7 89 10

_ l LO PUDLfCITY 8I NA l

/ 00 L:0 "GOITIONAL FACT 0nS

!1 See attached Supolementarv Information

,j,

800227o 73 3 l 8l I

l

' UU nu NAME:

N.

D.

S t e'm rt THONE: (813) 866-4159

/

cro a n i... r. T

k SUPPLEMENTARY INFORMATION 1.

Report No.:

50-302/77-64 2.

Facility:

Crystal River Unit #3 3.

Report Date:

8 July 1977 4.

Occurrence Date:

16 June 1977 5.

Identification of Occurrence:

Inoperability of one pair of Auxiliary Building erhaust fans contrary to Technical Specification 3.7.8.1.

6.

Conditions Prior to Occurrence:

Mode 1 power operation 7.

Description of occurrence:

s At 2120 the Auxiliary Building exhaust fans AHF 14A and AHF 14C were removed from service due to a duct leak located between the fans and the discharge damper. Entered a seven day Action Statement and the duct was repaired with a laminated patch. The system was restored operable on 21 June 1977.

8.

Designation of Apparent Cause:

The cause of this event was determined to be vibration of the system ductwork causing ' a hole between the fans and the discharge damper.

9.

Analysis of Occurrence:

There was no safety significance in that redundant buiiding exhaust system was available and operable.

10.

Corrective Action:

A laminated patch was installed and is expected to strengthen the ductwork to prevent reoccurrence.

11.

Failure Data:

This was the first occurrence of such an event.