m s

9 APPENDIX A NOTICE OF VIOLATION Virginia Electric and Power Company License No. DPR-32 Surry 1 Based on the NRC inspection November 1 - December 14, 1979, certain of your activities were apparently not conducted in full compliance with NRC require-ments as indicated below. These items have been categorized'as described in correspondence to you dated December 31, 1974.

As required by_ Technical Specification 6.4.A.7 and 6.4.D, the detailed written procedures provided for preventive or corrective maintenance optrations which would have an effect on the safety of the reactor must be

-followed.

Contrary to the above, on November 20, 1979, the inspector observed that the heat-traced Unit 1 emergency borate line (2" CH-42-152) was not properly insulated, indicating that corrective maintenance procedures EMP-C-HT-20 or MMP-C-G-017, which require reinsta11ation of the insulation removed, were not followed. The missing insulation may have led to or aggravated the plugged condition of the borate line.

This is an Infraction.

8003190$9h