cp ARKANSAS POWER & LIGHT COMPANY POST OFFICE BOX 551 LITTLE ROCK. ARKANSAS 72203 [501)371-4000 February 19, 1980 1-020-13 Director of Nuclear Reactor Regulation Attn: Mr. D.G. Eisenhut, Acting Director Division of Operating Reactors U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Subj ect : Arkansas Nuclear One - Unit 1 Docket No. 50-313 License No. DPR-51 Lessons Learned Implementation Item 2.1.6.a (File: 1510.3)

Gentlemen:

Pursuant to our January 31, 1980 letter, Arkansas Power 6 Light Company hereby provides the Icakage test data for Arkansas Nuclear One - Unit 1.

The methods used for determining system leakages are those described in our January 18, 1980 letter.

The results were as follows:

System Initial Leakage Rate Final Leakage Rate Makeup & Purification 9.176 cc/ min.

5.89 cc/ min.

Liquid Radwaste 0.13 cc/ min.

0.13 cc/ min.

Containment Spray 0.04 cc/ min.

0.04 cc/ min.

Decay Heat Removal 0.08 cc/ min.

0.08 cc/ min.

Waste Gas Unmeasurably high*

7.59 cfm**

  • Due to blown rupture disc in series with a leaking relief valve.
    • Isolated until a leaking water trap could be repaired.

Very truly yours, d A'Nd b 7 David C. Trimble Manager, Licensing DCT/DGM/hs e

W'