Notifies That Tech Spec Change Request 35 Incorporates Correct Nuclear Overpower Trip Setpoint & Employs Correct Valve for Total Actual Available Relieving Capacity for Each Steam Generator
ML19296B422
Person / Time
Site: Crystal River 
Issue date: 02/15/1980
From: Richard Bright
FLORIDA POWER CORP.
To: Fairtile M
Office of Nuclear Reactor Regulation
References
TAC-11945, NUDOCS 8002200539
Download: ML19296B422 (2)


Text

-

Florida POW 9T ieoruary 15,19c0 File:

3-0-3-e Mr. Morton D. Fairtile Project Manager Operating Reactors Brancn #4 Division of Ocerating Reactors U.S. Nuclear Regulatory Comission Washington, D.C. 20555

Subject:

Crystal River Unit 3 Docket No. 50-302 Operating License No. DPR-72 Technical Specification Change Request No. 35

Dear Mort,

In our discussion concerning Technical Specification Change Request No. 35, which entails revision to the maximum allowable Nuclear Overpower Trip Set-point based on the maximum number of inoperable steamline relief valves, the inconsistency between the numbers actually in the Technical Specifica-tion and the equation in the Bases that was supposed to be used to obtain these numbers was discussed.

If the correct numbers (submitted with TSCRN35) are input into the present bases equation, with the exception that the Nuclear Overpower Trip Setpoint of 105.5% be changed to 100.0%, the result is a reduced Nuclear Overpower Trip Setpoint of 85.75% for one inoperable safety valve.

This was apparently rounded down to an even 85%

for one safety valve and since this was a reduction of 15% in the Nuclear Overpower Trip Setpoint from 100%, which was used in the equation, the reduced Nuclear Overpower Trip Setpoint for two inoperable steamline relief valves became 70% and for three valves it became 55%.

Technical Specification Change Request No. 35 incorporates the correct nuclear overpower trip setpoint, which is specified in Technical Specifica-tion Tabl e 2.2-1, and it also employs the correct value for the total actual available relieving capacity for each steam generator.

The present Technical Specification only allcws for the relief capacity equivalent to 112% of Rated Thermal Power.

\\

D 8002200 General Office 3201 in.nyaounn saeer soun. p o so= uoe st o te swg Fo ca m33 813-see.stsi e

Mr. Morton D. Fairtile Page Two Feb ruary 15, 1980 Ir you require any further discussion on this subject, please ao not hesi-tate 00 CCntaCt.Te.

Very truly yours,

FLLRIDA r%ER CORPGRATION

/

s f i,1 /f (WM ' Gt j&y '

Ronald M. Bright Senior P,adiological Licensing Engineer RMBemhFcD70