Proposed Change to Page 194 of Tech Specs,Deleting Tech Spec 4.9.A.2.C. Re Testing of Emergency Diesel Generators
ML19290E123
Person / Time
Site: Cooper 
Issue date: 02/26/1980
From:
NEBRASKA PUBLIC POWER DISTRICT
To:
Shared Package
ML19290E119 List:
References
NUDOCS 8003040305
Download: ML19290E123 (1)


Text

'.

4 LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A 4.9. A.2 (cont 'd)

During the monthly generator test the diesel generator starting air compressor shall be checked for operation and its ability to recharge air receivers.

The operation of the diesel fuel oil transfer pumps and fuel oil day tank level switches shall be demonstrated, and the diesel starting time to reach rated voltage and frequency shall be logged.

b.

Once every 18 months the condition under which the diesel generator is required will be simulated and a test conducted to demonstrate that it will start and accept the emergency load within the specified time sequence. The results shall be logged.

c.

Specification 4.9.A.2.c deleted.

l d.

Once a month the quantity of diesel fuel available shall be logged.

Every three months and upon delivery a e.

sample of diesel fuel shall be checked for quality.

The quality shall be within the acceptable limits specified in Table 1 of ASTM D975-68 for Nos. ID or 2D and logged.

f.

Each diesel generator shall be given an annual inspection in accordance with instructions based on the manufacturer's recommendations.

3.

Unit Batteries a.

Every week the specific gravity, the voltage and temperature of the pilot 80 03 0 40 ]of

-194-