ML19290D508

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-05, Chloride Contamination of Safety-Related Piping & Components. No Written Response Required
ML19290D508
Person / Time
Site: Humboldt Bay, Diablo Canyon
Issue date: 02/08/1980
From: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To: Crane P
PACIFIC GAS & ELECTRIC CO.
References
NUDOCS 8002220078
Download: ML19290D508 (1)


Text

$

'o UNITED STATES E

).,, -

j NUCLEAR REGULATORY COMMISSION 3J\\

L C REGION V D,

i

[

1990 N. CALIFORNIA BOULEVARD

,d SUITE 202, WALNUT CREEK PLAZA

~.

February 8, 1980 Docket Nos. 50-133, 50-275 50-323 Pacific Gas and Electric Company 77 Beale Street San Francisco, California 94106 Attention: Mr. Philip A. Crane, Jr.

Assistant General Counsel Gentlemen:

The enclosed IE Information Notice is forwarded to you for information.

No written response to this Information Notice is required.

If you have any questions related to the subject, please contact this office.

Sincerely, fWmcG0 R. H. Engelken Director

Enclosure:

IE Information Notice No. 80-05 cc w/ enclosures:

W. Barr, PG&E W. Raymond, PG&E R. Ramsay, PG&E, Diablo Canyon E. Weeks, PG&E, Humboldt Bay J. Worthington, PG&E E. B. Langley, Jr., PG&E 8002220 k

4 SSINS No.: 6870 Accession No.:

UNITED STATES 7912190673 NUCLEAR REGULATORY COMMISSION 0FFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 7

3c3

    • J=J February 8, 1980 IE Information Notice No. 80-05 CHLORIDE CONTAMINATION OF SAFETY RELATED PIPING AND COMP 0NENTS A Bechtel Power Corporation Study at the Wolf Creek Project has revealed that a fire retardent coating is potentially corrosive in contact with stainless steel.

Albi "Duraspray" is a fire retardent coating which contains magnesium oxychloride, and is used for fireproofing of exposed structural steel in some Nuclear Power Plants. There appears to be no deleterious effect when it is applied over unprimed, inorganic zinc coated, or galvanized steel, however, it may be corrosive in contact with stainless steel, bare aluminum or copper.

Droppings or overspray of this material cannot be properly removed with water.

Diluted Nitric acid has been proven to be a useful cleanser, however, it presents a safety hazard.

Applicants and holders of construction permits and licensees of operating power reactors are advised to protect all stainless steel, copper and aluminum material from overspray and droppage of cementitious oxychloride materials and to remove accidently applied materials imediately and completely employing strict safety precautions d'uring the process.

Special attention should be given to weld areas in any removal procedures.

No written response to this information notice is required.

If you require additional information regarding this matter contact the Director of the appropriate NRC Regional Office.

a IE Information Notice No. 80-05 Enclosure February 8, 1980 RECENTLY ISSUED IE INFORf!ATION NOTICES Information Subject Date Issued To Notice No.

Issued 80-04 BWR Fuel Exposure in 2/4/80 All BWR's holding a Excess of Limits power reactor OL or CP 80-03 Main Turbine Electro-1/31/80 All holders of power Hydraulic Control System reactor OLs and cps 80-02 8X8R '4ater Rod Lower 1/25/80 All BWR Facilities End Plug Wear holder power reactor OLs or cps 80-01 Fuel Handling Events 1/4/80 All holders of power reactor OLs and cps 79-37 Cracking in Low Pressure 12/28/79 All power reactor OLs Turbine Discs and cps 79-36 Computer Code Defect in 12/31/79 All power reactor OLs Stress Analysis of Piping and cps Elbow 79-35 Control of Maintenance 12/31/79 All power reactor facilities and Essential Equipment with an CL or CP e

79-34 Inadequate Design of 12/27/79 All holders of power reactor Safety-Related Heat OLs and cps Exchangers 79-33 Improper Closure of 12/21/79 All power reactor facilities Prinary Containment holding OLs and cps Access Hatches 79-32 Separation of Electrical 12/21/79 All power reactor facilities Cables for HPCI and ADS holding OLs and cps 79-31 Use of Incorrect Amplified 12/13/79 All holders of power reactor Response Spectra (ARS)

OLs and cps 79-30 Reporting of Defects and 12/6/79 All power reactor facilities Noncompliance,10 CFR Part 21.

holding OLs and cps and vendors inspected by LCVIP 79-29 Loss of NonSafety-Related 11/16/79 All power reactor facilities Reactor Coolant System holding OLs or cps Instrumentation During Operation