ML19282B119

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 79-04, Degradation of Engineered Safety Features
ML19282B119
Person / Time
Site: River Bend  
Issue date: 02/16/1979
From: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: Humphreys L
GULF STATES UTILITIES CO.
References
NUDOCS 7903090039
Download: ML19282B119 (1)


Text

  • pn mec o

UNITED STATES o

NUCLEAR REGULATORY COMMISSION l*

o REClON IV 5

E 611 RYAN PLAZA DRIVE, SUITE 1000 c

AR LINGTON, TEXAS 76011 February 16,1979 In Reply Refer To:

RIV Docket Nos.

50-458/IE Information Notice flo. 79-04 50-459/IE Information flotice No. 79-04 Gulf States Utilities Attn:

Mr. L. L. Humphreys Senior Vice President, Energy Development Post Office Box 2951 Beaumont, Texas 77704 Gentlemen:

This Information Notice is provided as an early notificatiqn of a possibly significant matter.

It is expected that recipients will review the information for possible applicability to their facilities. No specific action or response is requested at this time.

If further NRC evaluations so indicate, an IE Circular, Bulletin or NRR Generic Letter will be issued to recommend or request specific licensee action.

If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

Sincerely, f

/
s

-- af 2,(

ll ktv{

c.m) 4 % i u

Karl V. Seyfrit Di rector

  • e

Enclosures:

1.

IE Information Notice No. 79-04 2.

List of IE Information Notices Issued in 1979 7903090039

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Information Notice No. 79-04 Date:

February 16, 1979 Page 1 of 5 DEGRADATION OF ENGINEERED SAFETY FEATURES Summary:

On September 16, 1978, an unusual sequence of events occurred at Arkansas Nuclear One, Units 1 and 2.

The events involved the electrical power sources and culminated in the spurious activation and degraded operation of Unit 2 Engineered Safety Features (ESF). Analysis of the course of the incident has identified three safety concerns in the electrical distribution system operation and design.

(1) The offsite power sup> y for ANO Unit 1 Engineered Safety Feature loads was deficient in that degraded voltage could have resulted in the unavailability of ESF equipment, if it were to be needed.

(2) The design of the ANO site electrical system that provides offsite power to Units 1 and 2 did not fully meet the Commission's Regula-tions,10 CFR 50, Appendix A, General Design Criterion 17, because in certain circumstances a loss of one of the two offsite power circuits would also re,sult in a loss of the other such circuit.

(3)

Deficiencies existed in the operation of the Unit 2 inverters that convert DC to AC power for the uninterruptable 120 volt vital AC buses.

Description of Circumstances:

Initially Unit 1 was operating at 100 percent power; Unit 2 was in hot standby oerforming hot functional testing in preparation for initial criticality and power operation if.

Unit 1 auxiliary electrical loads were being supplied from the Unit 1 main generator via the unit auxiliary transfomer.

Unit 2 auxiliary electrical _ loads were being fed from the offsite grid through Startup Transformer No. 3.

The normal operating status was interrupted by the failure of the Unit 1 Loop "A" Main Steam Line Isolation Valve (MSIV) air operator solenoid causing the MSIV to close as designed. The Unit 1 Reactor Protection System sensed conditions requiring reactor shutdown and tripped the reactor. The lf The Unit 2 Operating License did not permit criticality of power operation at the time of the incident.