Confirms Telcon of 790216 Re Defective Equipment Supplied to Texas Util Generating Co.Two AV Line Switchboards Were Shipped W/Incorrect Ammeters Installed.Incorrect Ammeters Were Removed & Correct Ammeters Installed
ML19281A545
Person / Time
Site: Comanche Peak  
Issue date: 02/16/1979
From: Yerrow R
GENERAL ELECTRIC CO.
To: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
REF-PT21-79-101-000 NUDOCS 7903210003
Download: ML19281A545 (2)


Text

,

~

79 - to t-m o C

G E N Ell A L hgr E LE CT R I C y

A S S E M BLIER D E P' A R T fA E N T GENERAL ELECTRIC COMPANY, 41 WOODFORD AVENUE, PLAINVILt.E. CONN. 0G062 Phone (203) 747 7 604 February 16, 1979

SUBJECT:

Report of Defect Under Regulation 10CFR Part 21 K. 7.

Seyfrit, Director, Region IV office of Inspection and Enforcement U.S.

Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 Dear Sir 6

On February 16, 1979, Mr.

W. Longstreet, Vice President and General Managar, Contractor Eqitipment Business Division of the General Electric Company received information indicating that certain equipment supplied to the Texas Utilitios Generating Company for use at the Comanche Peak Steam Electric St& tion, Glen Rose, Texas contained a defect reportable under Regulation 10CFR Part 21.

De-t allt., of this situation are as follows:

Equipment Identification:

Two General Electric "AV Line" Switchboards for Class lE service as follows:

a) Equipment Tag No. cpl-EPSWED-Ol, Bus No, LED 1 b) Equip: tant Tag No. cpl-EPSWED-02, Bus No. LED 2.

Nature of Defect:

Tne two switchboards identified above were shipped with in-correct ammeters installed in them. The a:: meters installed were G. E. Catalog No. 50-103121FMSN2KFM, Type DB-40, 200-0-60CA Scain fut use with 56 my snunt.

Since cach ammeter is connected to a 100 mV shunt, the ammeters would read double the actual current level.

The safety hazard which could be created by this defect is any unsafe action which a misreading of the meter might cause in carrying out operating routines based on such a meter reading.

Date of Discovery:

February 16, 1979.

/)70 h

/

GENER AL h ELECTRIC K. V. Seyfrit, Director, Region IV Page 2 February 16, 1979 Corrective Action:

On February 16, 1979, 50-103121HMSJ2KPN, Type DB 40, 200-0-600A S installed by Mr. David Doyle of General Electric Installation and Service En unt, were gineering.

This report confirms the report submitted by telephone [(817)

R. E. Hall, Chief, Engineering Support Section,

-334-2841] to Mr.

1979 at 3:45 P.M.

Beactor Construction Branch on February 16, Report submitted by S

LM %

R. L. Ye rw Manager-ity Control

.