I APPENDIX A I

NOTICE OF VIOLATION Metropolitan Edison Company P. O. Box 542 l

Reading, Pennsylvania 19603 i

Docket No. 50-289 i

License No. DPR-50 Based on the results of the NRC inspection of July 13-16, 1976, it appears certain of your activities were not conducted in full compliance l

with the conditions of your license as indicated below:

i i

Appendix B to Facility Operating License DPR-50, Environmental Technical Specifications, Sections 5.5.1h and i require procedures for the analysis of radioactive liquid and gaseous wartes. Three Mile Island Station Chemistry Procedure 1973, Verification of Sample Representativeness and Accuracy - Effluents, requires that:

blind duplicate samples of one evaporator condensate storage tank kq and one waste gas decay tank taken prior to the release of the tank i

shall be run each month to determine the reproduceability of sampling and analytical techniques; analysis of duplicate samples shall be per*ormed by different persons; and the results of the first analysis shall not be made available to the person performing the second analysis.

Contrary to the above requirement blind duplicate samples of the evaporator condensate storage tank and waste gas decay tank were not taken and analyzed for the months of February, thrch, April,

[

May, and June, 1976.

This is an infraction.

1413 132 1

g-7D10150

[

--