., - t ' NTA. n ' ~ C VIRGINIA ELECTRIC AND POWER COMPANY

~9 OCI I A 9 sept (mber as,1979 Mr. James P. O'Reilly, Director Serial No. 79' Office of Inspection & Enforcement PSE&C/JMD:adw:mc U.S. Nuclear Regul_atory Comission Region II Docket No. 339 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

On September 24, 1979, a report was made under the provisions of 10CFR50.55(e) concerning a potential unreviewed safety question based on Westinghouse information that the performance of non-safety grade equipment subjected to an adverse environment could impact the protect-tive functions perfomed by safety grade equipment.

In accordance with the reporting requirements of 10CFR21, the fol-lowing infomation is submitted:

A.

Name and address of reporting individual:

Mr. E. A. Baum, Executive Manager Licensing and Quality Assurance Virginia Electric and Power Company P. O. Box 26666 Richmond, Virginia 23261 B.

Facility, activity, and/or component affected:

North Anna Power Station, Unit 2 C.

Name of firm constructing the facility or supplying the component, activity or service:

Westinghouse Electric Corporation P. O. Box 355 Pittsburgh, Pennsylvania 15230 D.

Description of defect, deficiency, or failure to comply:

Westinghouse has informed Vepco that as part of a continuing review of the environmental qualifica-tions of Westinghouse supplied equipment, four (4) systems were identified which, if subjected to an adverse environment, could potentially lead to control system operation which may impact protec-tive functions. These systems are:

V QO 1179 001 h "903 W 9

~

'0" 7910190

Mr. James P. O'Reilly 2

1) Steam generator power operated relief valve control system
2) Pressurizer power operated relief valve control system
3) Main feedwater control system
4) Automatic rod control system E.

Date of determination of reportability:

September 24, 1979 F.

Similar components, activities, or services:

North Anna Unit 1 G.

Corrective action which has been, is being or will be taken, the in-dividual responsible and the length of time to complete the action:

Westinghouse has provided Vepco the information on the basis for these concerns and we are now reviewing these systems for North Anna Unit 2 to detemine if any unreviewed safety questions or deficiences exist. The review will be complete and the results available in our 30-day report.

H.

Other infomation:

None Any infomation not available at this time will be submitted in a follow-up letter as a 30-day report.

Should you require further infomation, please co act this of ce.

i uly d W n C. Brown, r.

ior Vice President-Po er Statio Engineering and onst uction cc: Director, Office of Inspection and Enforcement (3)

I