ML19275A364

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 79-23, Emergency Diesel Generator Lube Oil Coolers. No Action Required
ML19275A364
Person / Time
Site: Hatch, Vogtle  
Issue date: 09/26/1979
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: John Miller
GEORGIA POWER CO.
References
NUDOCS 7910040176
Download: ML19275A364 (2)


Text

Tl C

'o UNITED STATES 8

g g

NUCLEAR REGULATORY COMMISSION

.E a

REGION li

\\.....,o #

101 MARIETTA ST., N.W., SUITE 3100 ATLANTA, GEORGIA 30303 SEP 2 6 1979 In Reply Refer To:

RII:JPO 50-321,_50-366

[ 4T 50-42 Q Georgia Power Company Attn:

J. H. Miller, Jr.

Executive Vice President 270 Peachtree Street Atlanta, Georgia 30303 Gentlemen:

The enclosed Information Notice provides information with regard to failures of lube oil coolers for emergency diesel generators.

Sincerely, h

James P. O'Reilly Director

Enclosures:

1.

Information Notice 79-23 2.

List of IE Information Notices Issued in the Last Six Months

/

r 1100 125 8

7 910 0 4 9 / 7c

/

SEP 2 61979 Georgia Power Company.

cc w/ enc 1:

M. Manry, Plant Manager Post Office Box 442 Baxley, Georgia 31513 C. E. Belflower Site QA Supervisor Post Office Box 442 Baxley, Georgia 31513 K. M. Gillespie Construction Project Manager Post Office Box 282 Waynesboro, Georgia 30830 E. D. Groover QA Site Supervisor Post Office Box 282 Waynesboro, Georgia 30830 M

m W e g e e. ma w egg, A w

  • wme'N N'**N****6-*N--

P***N**

~

  • * ~ ~

Accession No:

7908220121 SSINS: 6870 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 September 26, 1979 IE Information Notice No. 79-23 EMERGENCY DIESEL GENERATOR LUBE OIL COOLERS Within a two week time span (August 27 to September 11, 1979), the tube sheets failed in the Arkansas Nuclear One (ANO) Unit 1 lube oil coolers for both of the Unit 1 Emergency Diesel Generators.

The introduction of water into the diesel lube oil system resulted in trips of both diesels during surveillance testing. The diesels were not considered capable of sustained operation.

Investigation by the licensee has indicated cracks around the outer periphery of the tube sheets. The exact failure mode has not been assessed; however, tbe licensee has replaced the Emergency Diesel lube oil coolers for both diesels with a cooler of different design. The original lube oil coolers had tube she:ets which were one-eighth (1/8) inch in thickness and the tubes were soldered in place.

Epoxy was also used as a sealer on the tube (water side) of the lube oil cooler.

The new coolers have one-half (1/2) inch tube sheets and the tubes are rolled.

The ANO, Unit 1 Emergency Diesel Generators were purchased in 1970 and were manufactured by the Electromotive Division of General Motors Corporation. The lube oil coolers (Model Number D-191700) were manufactured by Young Radiator Corporation.

This information is provided as an early notification of a possible significant matter.

It is expected that recipients will review the information for possible applicability to their facilities. No specific action or response is requested at this time.

If further NRC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request specific licensee actions.

If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.