05000334/LER-1977-006-01, /01T-1 on 770126:review of Pipe Stress Due to Feedwater Line Vibrations Noted Six Seismically Inadequate Snubbers on Feedwater Lines.Caused by Poor Design Verification During Plant Const

From kanterella
(Redirected from ML19274E232)
Jump to navigation Jump to search
/01T-1 on 770126:review of Pipe Stress Due to Feedwater Line Vibrations Noted Six Seismically Inadequate Snubbers on Feedwater Lines.Caused by Poor Design Verification During Plant Const
ML19274E232
Person / Time
Site: Beaver Valley
Issue date: 03/14/1979
From: Werling J
DUQUESNE LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19274E231 List:
References
LER-77-006-01T, LER-77-6-1T, NUDOCS 7903210005
Download: ML19274E232 (2)


LER-1977-006, /01T-1 on 770126:review of Pipe Stress Due to Feedwater Line Vibrations Noted Six Seismically Inadequate Snubbers on Feedwater Lines.Caused by Poor Design Verification During Plant Const
Event date:
Report date:
3341977006R01 - NRC Website

text

... ~

Update Report nac,ogu 3g, u NwAR REcutATORv Couusss ON

, t7 m Previous Report Date 2/9/77 LICENSEE EVENT REPORT CONTROL 8 LOCK: l l

l l

l l lh (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATIONI s

e l P l A l B lV l S l 1 Ql 0 l0 l-l 0 l0 l0 l0 l0 l-l0 l0 l@l4 l1 il l1 l1 l@l l

l@

o i 8

8 9 UCENSEE CODE I4 16 UCENSE NuMdER 29 28 UCENSE TYPE 40 Si LAE W CON'T E

",] l L ]@l 0 l 5 l 0 l 0 l 0 l 31314 l@l 0 l 1l 2 l 6l 7l 7 j@l0 l 3 l 1 l 4 l 7 l 9 l@

$U I

S 60 61 QOCK ET NUMSER OS 63 EVENT CATC 74 7$

REPORT DATE 80 EVENT OESCalPTION ANO PROB ABLE CONSEQUENCES h o 2 l During a review of pipe stresses resulting from feedwater line vibrations, six l

o 3 I hydraulic snubbers installed on three feedwater lines were found not adequate for l

O 4 l seismic desien condition. An investiention of all Catecory T safety reinted I

lsni$bbersandhangerswasperformedtoverify their conformance to requirements.

l o s 0 6 i The investiRation TeVealed an additional tVenty-siX mechanical hancerR Which l

E I required modifications. The Onsite Safety Committee reviewed the incident and I

o e i found the modifications acceptable.

I

  • O 7

e, SYSTEM

CAUSE

CAUSE COMP.

VALVE g

COCE CODE SUSCODE COMPONENT CODE SUSCODE SusCOCE I C In l@ LB_J@ LA_J@ In l A l s i c i z i a lG W@ I z l O I

o 9 7

8 9

to II 12 33 18 19 20 SEQUENTIAL OCCURRENCE REPORT REVtSION LE R/Ro EVENT YEAR REPORT NO.

CODE TYPE NO.

8,aEg l217l 7l

(.--J l 0 10 l 6 l l/l 10 l 1 l W

l---j lJ_j t

V 22 23 24 26 27 28 29 30 31 32 KE AC N

ONP T

M TH HOURS See POR 8.

LE MANUP RER I F l@l Z I@

W@

W@

l0l0l0l0l l_Y_j @

[N_j@

W@

lG l2 l5 l5 l@

33 34 35 36 31 40 41 42 43 44 47 i

CAUSE OESCRIPTION ANO CORRECTIVE ACTIONS h i o l The incident resulted from breakdown of desien verification during plant I

i i i construction. nancer modifications rance from increased anchor bolt size en the I

I l addition of a new hanger at approximately the same location as an underdesigned l

, 7 g l hanger to carry some of the load.

In no case was any velding or other metallurgicall change to the pipine required to make these modifications.

I i 4 7

s,

so STA

% POWE R OTHER STATUS Dis O Y

OtSCoVERY DESCRIPTION Gl@ l 0l 0 0l@l N/A l

l C l@l Review of pipe stresses l

s s A TIVITY CO TENT RELEASED OP RELEASE AMOUNT OP ACTIVITY LOCATION OP RELEASE h l Zl l

N/A l

l N/A I

1 6 7

8 9 10 tt 44 45 80 PERSONNEL EXPOSURES NUMBE R TYPE DESCRIPTICN l0l0l0l@lZl@l N/A l

i 7 iES PERSONNELINJU oESCRiPTiON@

NUMeER ITITl l 0 010*@l N/A l

7 8 9 11 12 50 LOSS OP OR DAuAGE TO 8ACluTV TYPE C E SCRIPTION Lz_J@l n/^

I i 9 80 7

4 9 to

?

79032100os eunuciry NRC use ONLv oESCRiPTiON L-)

,$$UE o@l' N/A l

l l l l-l l l l l l l l l :I W

2 o 7

3 9 to 68 69 80 3

. e ng 412-643-1258 2

NAME OF PREPARER PHONE:

Attachment to LER 77-6/01T Boavar Valley Power Station Duquesne Light Company Docket No. 50-334 During a review by the Beaver Valley Architect / Engineer of pipe stresses resulting from feedwater line vibrations, it was discovered that six hydraulic snubbers installed on three feedwater lines inside containment are not adequate for seismic design condition. As a result of the discovery, an investigation was undertaken to review all Category I safety related snubbers and hangers to verify their conformance to requirements. The investigation revealed an additional twenty-six mechanical hangers whicn required modifications ranging from increasing the size of the anchor bolts to the addition of a new hanger at approximately the same location as an underdesigned hanger to carry some of the load.

In no case was any welding or other metallurgical change to the piping required to make these modifications.

The incident resulted from a breakdown in design verification procedures used during plant construction. Duquesne Light engineering personnel have reviewed the A/E calculational method for the redesigned hangers and have found them accepcable.

When the modifications were completed, the Onsite Safety Committee reviewed the incident and corrective actions and concurred that modifications were acceptable.