ML19270F931

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-02, Pipe Support Base Plate Designs Using Concrete Expansion Anchor Bolts
ML19270F931
Person / Time
Site: Beaver Valley
Issue date: 03/08/1979
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Woolever E
DUQUESNE LIGHT CO.
References
NUDOCS 7904040360
Download: ML19270F931 (1)


Text

TeRh

- - ~

[g* "8%g UNITED STATES g

NUCLEAR REGULATORY COMMISSION f

) PI REGION I o

E f

s.

V.

631 PARK AVENUE

,f MING OF PRUSSI A. PENNSYLVANI A 19406 March 8, 1979 Docket No. 50-412 Duquesne Light Company ATTN: Mr. E. J. Woolever Vice President 435 Sixth Avenue Pittsburgh, Pennsylvania 15219 Gentlemen:

The enclosed IE Bulletin No. 79-02 is forwarded to you for action.

A written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, o

Boyce H. Grier

~

Director

Enclosures:

1.

IE Bulletin No. 79-02 2.

Listing of IE Bulletins Issued in Last Twelve Months cc w/encls:

R. J. Washabaugh, Quality Assurance Manager 7s04040$(06

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Bulletin No. 79-02 Date: March 8, 1979 Page 1 of 3 PIPE SUPPORT BASE PLATE DESIGNS USING CONCRETE EXPANSION ANCHOR BOLTS Description of Circumstances:

While performing inservice inspections during a March-April 1978 refueling outage at Millstone Unit 1, structural failures of piping supports for safety equipment were observed by the licensee.

Subsequent licensee inspections of undamaged supports showed a large percentage of the concrete anchor bolts were not tightened properly.

Deficiency reports, in accordance with 10 CFR 50.55(e), filed by Long Island Lighting Company on Shoreham, indicate that design of base plates using rigid plate assumptions has resulted in underestimation of loads on some anchor bolts.

Initial investigation indicated that nearly fifty percent of the base plates could not be assumed to behave as rigid plates.

In addition, licensee inspection of anchor bolt installations at Shoreham has shown over fifty percent of the bolt installations to be deficient.

Vendor Inspection Audits by NRC at Architect Engineering firms have shown a wide range of design practices and installation procedures which have been employed for the use of concrete expansion anchors. The current trends in the industry are toward more rigorous controls and verification of the installation of the bolts.

The data available on dynamic testing of the concrete expansion anchors show fatigue failures can occur at loads substantially below the bolt static capacities due to material imperfections or notch type stress risers. The data also show low cycle dynamic failures at loads below the bolt static capacities due to joint slippage.

Action to be Taken by Licensees and Permit Holders:

For pipe support base plates that use concrete expansion anchor bolts in Seismic Category I systems as defined by Regulatory Guide 1.29, " Seismic Design Classification" Revision-1, dated August 1973 or as defined in the applicable FSAR.

1.

Verify that pipe support base plate flexibility was accounted for in the calculation of anchor bolt loads.

In lieu of supporting analysis justifying the assumption of rigidity, the base plates 7903140038 v