ML19270F834

From kanterella
Jump to navigation Jump to search
Ack Receipt of IE Insp Rept 50-395/79-02 on 790122-25. No Proprietary Info
ML19270F834
Person / Time
Site: Summer 
Issue date: 03/12/1979
From: Mary Johnson
SOUTH CAROLINA ELECTRIC & GAS CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19270F835 List:
References
NUDOCS 7903270594
Download: ML19270F834 (2)


Text

.

?

yQ -

=

g-Q ww

' '!9 N II

" P Gl A south CAROLINA ELECTRIC a gas COMPANY

.c.. o,,, c 2

1..

CotuMeiA.Sourn CAnoLIN A 29218

.-.........o....u...,,

i.u....,<.....r.c...~.

March 12, 1979 United States Nuclear Regulatory Commission ATTN:

Mr. James P. O'Reilly Director Marietta Building, 31st Floor 101 Marietta Street, NW Atlanta, Georgia 30303

Subject:

V. C. Summer Nuclear Station Unit #1 Response to NRC Audit Reports Q 5/79-p ated 2/22/79, 50-395/ 79-03 dated 2/20/79, and 50-395/79-04 dated 3/2/79 Gentlemen:

In response to the above captioned reports, we have reviewed the informa-tion contained there-in and find that they contain no proprietary information.

In addition, we have evaluated the circumstances relating to the item identified as 79-03-01 in report 50-395/79-03, which dealt with unapproved " duct" tape on stainless steel pipe.

Our evaluation has produced the following results:

1.

Catygg Three types of tape have been approved and used on the job site.

At the time of the inspection, one type tape was in stock on site.

This tape had been on site since 1975 and its adhesive qualities were significantly reduced. Therefore, the " duct" tape was being substituted without supervisor's knowledge or approval.

Although the paint craft had been instructed (NCN 0592) not to use " duct" tape,they did not comply with the instructions while working on "B" Loop Cold Leg, adjacent to FW22, which violates QCP-VII-05, Rev. 5.

2.

Immediate Corrective Steps Taken and Results The job site has received and released a new shipment of tape.

In addition, the use of " duct" tape has been restricted to areas outside the Reactor Building and use has been restricted on stainless 7s? sos ~J' 7903270 6h

~

Mr. Jameg. g O'Reilly Page 2 March 12, 1979 steel throughout the job site.

The " duct" tape has been removed from "B" Loop Cold Leg and the entire area thoroughly cleaned with approved alcohol.

3.

Corrective Steps Taken to Avoid Future Noncompliance An orientation session was held for all appropriate General Foremen and Foremen on March 5, 1979.

Indoctrination was held for the appropriate civil discipline (painters) as a group and verbally reinforced the areas where " duct" tape can be used to other appropriate civil disciplines (laborers, carpenters, cement finishers and iron workers). The Constructor QC Inspectors have increased their surveillance activities as regard the use of tapes.

In addition, a testing program has becninitiated on the

" duct" tape to assess any adverse impact this tape might have on stainless material and determine if it is possible to qualify it for this purpose.

4.

Fu_1,1 Compliance Date With the exception of the tape testing program, all actions identified were conpleted as of March 5, 1979.

We trust that you will find our actions to resolve this item appropriate and satisfactory.

Please feel free to contact us if we can provide additional information in relation to this item or the subject reports.

Very truly yours,

~

DAN /MCJ/jls ec: