Responds to NRC Re Deviations Noted in IE Insp Rept 50-338/78-32.Corrective Actions:Air Start Manual Isolation Valves & Control Room Selection Switch Checked Every 4 Hours.Contains No Proprietary Info
ML19263B329
Person / Time
Site: North Anna Dominion icon.png
Issue date: 12/11/1978
From: Stallings C
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19263B317 List:
References
677-112178, NUDOCS 7901180043
Download: ML19263B329 (2)


Text

..

VIItGINIA ELECTHIC AND I'CW H H CO M I% NY It acinwonx>,Vruonw ar unus:

December 11, 1978 Mr. James P. O'Reilly, Director Serial No. 677/112178 Office of Inspection and Enforcement P0/DLB:scj U. S. Nuclear Regulatory Commission Docket No. 50-338 Region II License No. NPF-4 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

ke have reviewe-your htter of November 21, 1978 in reference to the inspection conducted at North Anna Power Station on October 16-19, 1978 and reported in IE Inspection Report No. 50-338/78-32. Our response to the specific violatior is attached.

We have deterrined that no proprietary information is contained in the report. Accordingly, the Virginia Electric and Power Company inter-poses no objection to the inspection report being made a matter of public disclosure.

Very truly yours,

't A'Y>:..)/ntfr ataw

/

C. M. Stallings Vice President-Power Supply and Production Operations Attachment cc:

Mr. Albert Schveacer 79011800

/

~ l 'h

.s.

s.

RESPONSE TO VIOLATION LISTED IN INSPECTION REPORT NO. 50-338/78-32 NRC C0KMEtiT Baseo on the results of the NRC inspection conducted on October 16-19, 1978, certain of your activities appear to deviate from your coemitments to the Commission as indicated below.

In response to an inquiry made by the Of fice of Nuclear Reactor Regulation, a VEFC0 letter, serial no. 323/053178, dated July 7, 1978, stated that the air start manual isolation valves and the control room selector switch "...

are checked every four (4) hours and recorded in the Diesel Log by an Operator".

Contrary to the above, prior to October 18, 1978, the checks made of the diesel air start manual isolation valve or manual selector switch were not recorded.

RESPONSE

The deviation listed above was the result of an error in the initial lette.

(serial no. 323/053178, dated July 7, 1978) submitted to the Commission on the subject of diesel generator auto start functions. This item was subse-quently addressed in Vepco letter, serial no. 556/092578, dated October 31, 1978. The status of the air isolation valves is still pending further discussion between Vepco and the NRC.

The final resolution of these dio-cussions will determine the surveillance requirements needed for the air isolation valves.

Since the statement mentioned in the deviation was corrected by the response on October 31, 1973, full compliance has been achieved and no further corrective actiens are required.