Forwards LER 80-012/03L-0
Date released: 10/03/2019 Download: ML19262C613


LER 80-012/03L-0:on 800111,during Surveillance Testing, Emergency Diesel Generator a Tripped on Low Lube Oil Pressure.Caused by Partial Failure of Engine Immersion Heater Resulting in Cold Lube Oil.Heater Replaced