October 15, 1979
...+
Docket Nos. 50-325 and 50-??4 Mr. J. A. Jones Executive Vice President Carolina Power & Light Company 336 Fayetteville Street Raleigh, North Carolina 27602
Dear Mr. Jones:
Your letter dated May 16, 1977 provided information in response to our request dated March 29, 1977 concerning the diesel generator alarm and control circuitry at Brunswick 1 and 2.
We have completed our review of the hardware modifications which were installed to enhance the operator's awareness of the status of the diesel generators. These modifications included the addition of a separate control room alarm for low starting air pressure labeled "D.
G.
Abnortral Condition", and connecting the barring gear engaged con-tact into the "D.
G. Unavailable" annunciator. We understand that these modifications were completed in February of this year. We further verified by telephone that all shared annunciators for disabling conditions could not be cleared until all the abncrmal conditions are corrected.
We conclude that the Brunswick design is within the scope and intent of Regulatory Guide 1.47 " Bypassed and Inoperable Status Indication for Nuclear Power Plant Safety Systems," May 1973 and is acceptable.
Sincerely,
/
homa o
ief Operating Reactors Branch #3 Division of Operating Reactors cc: See page 2 l2l-
$7) 1
5 p
7910360
Carolina Power & Light Company cc: Richard E. Jones. Esquire Carolina Power & Light Company 336 Fayetteville Street Raleigh, North Carolina 27602 George F. Trowbridge, Esquire Shaw, Pittman, Potts & Trowbridge 1800 M Street, NW Washington, D. C.
20036 John J. Burney, Jr., Esquire Burney, Burney, Sperry & Barefoot 110 North Fifth Avenue Wilmington, North Carolina 28401 Southport - Brunswick County Library 109 W. Moore Street Southport, North Carolina 28461
.