05000250/LER-1979-016-03, /03L-0 on 790429:high Level Alarm Annunciated. Caused by Instrument Drift of Tech Spec Min & High Level Alarms & Digital Level Indicator Transducer.Instruments Recalibr

From kanterella
(Redirected from ML19259C111)
Jump to navigation Jump to search
/03L-0 on 790429:high Level Alarm Annunciated. Caused by Instrument Drift of Tech Spec Min & High Level Alarms & Digital Level Indicator Transducer.Instruments Recalibr
ML19259C111
Person / Time
Site: Turkey Point 
Issue date: 05/29/1979
From: Schoppman M
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19259C105 List:
References
LER-79-016-03L, LER-79-16-3L, NUDOCS 7906120363
Download: ML19259C111 (2)


LER-1979-016, /03L-0 on 790429:high Level Alarm Annunciated. Caused by Instrument Drift of Tech Spec Min & High Level Alarms & Digital Level Indicator Transducer.Instruments Recalibr
Event date:
Report date:
2501979016R03 - NRC Website

text

......

- ~.

=-

..=

~

I sRc nonu :s4 u. s. mectsam arcutaroav couusss:cu (7 77)

LICENSEE EVENT REPORT comrzet SL0cc i il l 1 l I@

tet Ass paimr ca rYPE ALL AEcViRED INFCaMADCN1 lo Ii lF l L I Tl PI Si3 I@l 010 1-10101010 101 10 f 0 !@l 411 1111 l 1 l@l

! a@

I s e i ca.uascac4

s
- cana es4=

a :.

wcA..sa tv.s

.4 s.

c0N"Y E io'@l01510 I Ot o i 21 510 Gio t 4 21917 i 9_'@l o f 51219 17 19 l@

oiil e

.i

oc,ar w ee4 a

sa os= roars 1.

. > caro.ra 4a avsur osscateries Amo eacs4sta consecutscas @

ii2 lDuring power operation, a hl.Th level RWST alarn annunciated. Evaluation i

32 trevealed the RWST level to be 315,328 gal., less than the TS 3.4.1.a.1 r

Iminimum, although the Control Room level indication showed margin I

3 4

a,.

iavailable. Concurrent with makeup, a unit shutdown was initiated.

Fifty I

a 4, ininutes later, the RWST volume was within specification. A sinilar event p

oi, iwas reported as LER 251-76-2.

i o,4i I

  • __)

w 04 CO a Sul0 E C08,MN(=, 0334

$4 Of 85

( I !F l@ [X_j@ Ly @ II I N IS I T l R I Ul@ @@ LZj @

3,3 7

4 9

t 'l it iJ i2

?&

6t D

u :m.,ri.s ocm.v.ca

...e.,

.<v a,

_ avt4,t1.A

  • t*C47 90 CODE vvat 40.

@ lgg g,.o 17 l 9 l L--j 1011161 M,

l oi31 LL_j L--j 0

g;;; _v n

n i.

1 u

u v

n

= ma cvis e.w

., n= =c. =.

.t..

>= st et 'v.

[X_j@L.E_jg 1,Blg O. @

l0 10 1 0 (O' I y@

l N J g g g l X Y lt"d 19 r t

m 2

v cAusa esscaisneN ANO CORR!CnVE ACrioNs h IThe root cause of the problems was instrument drift of TS minimum and high r i

a 11evel alarms, and the digital level indicator transducer. The instruments t i

a lwere recalibrated and the RWST required volume was reestablished. A design i

,,7 l review of RUST level indication has been initiated.

iI e

r so 5r

  • b70W44 Cri.f 4 SrA *kt 3i5 3 esc 0v tev ets:ssa?tCn i i s i ly@ ti 10 0 l@l NA l W@l Operator Observation I

'.c'rivir, ec'2ravr 83 awe.s=r on.criviry @ l ucario,o,=v.rasa@

atu.si3 en astrasr [Z_j @ dl@l NA sl NA l

15

' '...so J?

s vii,

.i,,eiev.,u u s:=>,r e=

,,il l 0 :0 l0 ' @ U @ l I

temd'm.'Au

'3 sasca.*'ve h 9 c,g a n i ta (O io 10 l@l NA qqne q-M I

.'ess as :. :l'..cth s.c:u,, @

LL04 L/p n

rvee sucai>ric=

i9lIl@{

NA I

o u
31[3@!""' f,',",.,, e, @

.uc us: :stv 1

NA t

Iier't'ilsir i tt,

.,4u g e,. 3,2 y,

M. A.

Schoonman 305/552-3802

. c.s 3

[

i 7906120 %3

REPORTABLE OCCURREI:CE 250-79-16 LICENSEE EVENT REPORT PACE TWO Additional Event Description At the time of the event, the level indications in the control Roon were 326,800 gallons (Digital meter LI-3-15450) and 325,000 gallons (gase LI-3-1545). Level was determined by a permanently installed precision local gage as being 315,323 gallons, which is less than the TS 3.4.1.a.1 minimum of 320,000 Gallons. Load was reduced during the occurrence from 100% to 84% reactor power before the RUST volume specification could be reestablished.

Additional Cause Description The calibration of the level transmitter and indicators was checked and adjusted as required. LI-3-1545 is a wide-range Bailey Type PM indicator sage.

Calibration verification revealed no error, and it is probable tint this ga6e was mis-read.

LI-3-1545D ic a digital meter with a P-I converter. Calibration verification revealed approximately 2.4% error in this vol6me range. Pressure switches PS-3-1585 (RWST hi-level alarm, setpoint: 330,000 gallons) and PS-3-1584 (RWST TS minimum level, setpoint: 322,200 gallons) were checked and it was noted that their sotpoints had drif ted low. Operators will be instructed to compara the weekly calibration check reading of RWST-1 (precision local gage) to the indication provided by LI *-1545 and LI *-1545D.

A design review of the RWST level indication has been initiated.

2284 279