Proposed Change No. 74 a
e a
\\
(RAIRE JUARHEE W L'lE.n G ""':
- TURNPlKE ROAD (RT. 9)
O.'17 ENGINEERING OFFICE WESTBOR O, M ASSACHUSETTS 01081 617-36G - 9011
-O PC 74-1 WMY 80-15 B.3 2.1 January 25, 1980 United States Nuclear Regulatory Commission Washington, DC 20555 Attention:
Office of Nuclear Reactor Regulation Robert W. Reid, Chief Operating Reactors Branch #4 Division of Operating Reactors
References:
(a) License No. DPR-36 (Docket No. 50-309)
(b) USNRC letter from R. W. Reid to R. H. Groce dated February 2, 1978;
Subject:
Amendment No. 35 to Facility Operating License (c) USNRC letter from R. W. Reid to R. n. Groce dated April 24, 1978;
Subject:
Amendment No. 37 to Facility Operating License
Dear Sir:
Subject:
Maine Yankee Fire Protection Technical Specifications Pursuant to Section 50.59 of the Commission's Rules and Regulations, Maine Yankee Atomic Power Company hereby proposes the following modifications to Appendix A of the Operating License.
PROPOSED CHANGE:
Reference is made to the Operating 'icense DPR-36 and the Technical Specifications contained in Appendix A issued to the Maine Yankee Atomic Power Company for the Maine Yankee Atomic Power Station.
We propose to make the following changes:
1.
Page 3-23-1, Section 3 23A, EXCEPTION Change first sentence to:
If the affected zone is either Zone 5 or Zone 28, the inspection required in A.1 above shall be perforraed at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
1840 099 8 001e9 0 D N f
United States Nuclear Regulatory Commission January 25, 1980 Attentio.1: Office of Nuclear Reactor Regulation Page 2 2.
Page 3-23-2, Section 3 23D Add the following to the section:
The following h<,se station shall be operable whenever the emergency panel and/or auxiliary charging pump are required to be operable:
PAB Elev.11 ft. Hose rack 3 The following hose stations sha'.1 be operable whenever the charging pumps are required to be operable:
PAB Elev. 21 ft. Hose racks 9 and 11 The following hose station shall be operable whenever the emergency feed pumps (electric) are required to be operable:
PAB Elev. 21 ft. Hose rack 11 The following hose stations shall be operable whenever equipment in the switchgear rooms or cable tray rooms is required to be operable:
TB Elev. 35 ft. and 45 ft. Hose racks 17 and 18 The following hose stations shall be operable whenever equipment in the containment motor control center is required to be operable:
Steam and Feedwater Valve Areas - Hose rack 21 The following hose stations shall be operable whenever the steam driven feed pump is required to be operable:
Steam and Feedwater Valve Area - Hose racks 20 and 21 The following hose stations shall be operable whenever the safeguards pumps are required to be operable:
Containment Spray Fump Building Hose racks 23 and 24 3
Page 3-23-2a, Section 3.23F a)
Revise the first list to read:
1.
Sprinkler System directly under Turbine Building 39 foot elevation 2.
Component Cooling Water Pump Sprinkler b)
Add the following:
The following spray and/or sprinkler systems shall be operable whenever the equipment in the protected area is required to be operable.
1.
Protected Cable Vault Sprinkler 2.
Containment Spray Pump Motor Area Sprinkler 1840 100
United States Nuclear Regulatory Commission January 25, 1980 Attention: Office of Nuclear Reactor Regulation Page 3 4.
Page 3-23-26 Add the following new Section, 3.23G G.
The following foam fire suppression systems shall be operable whenever the component cooling water system or service water system is required to be operable.
1.
Turbine Lube Oil Reservoir Foam System 2.
H drogen Seal Oil Foam System
/
The following foam fire suppression systems shall be operable whenever the protected diesel generator is required to be operable-1.
Diesel Generator Room A Foam System 2.
Diesel Generator Room B Foam System With one or more of the above required foam systems inoperable:
1.
Within one hour establish a fire watch patrol with backup fire supnrassion equipment for the unprotected area (s) to inspect tc.; unprotected area (s) at least once per hour.
2.
Restore the system (s) to operable status within 14 days or, in lieu of any other report required by Specification 5 9.1, prepare and submit a Soecial Report to the Commission within the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system (s) to operable status.
5.
Page 3-23-4, Table 3.23.1 Add the following smoke detector locations to the Table:
14 Containment Cable Trays Elev. 46 15 Containment Cable Trays Elev. 63 16 Containment Cable Trays Elev. 20 17 Personnel Air Lock Area 18 Containment Spray Pump Building 9
Steam and Feedwater Valve Area 20 Emergency Feed Pump Area 21 Aux. Chg. Pp. Emergency Shutdown Pnl.
22 Chg. Pp Cable Trays - Elev. 21 23 Charging Pump Cubicles 24 Compactor Area 25 Fuel Pool Area 26 Fire Pump House 27 Cable Trays, PCCW area 28 Cable Vault Vent. Intake 29 Cable Tray Room Duct Detector 1840 101 30 Control Room Vent. Intake 31 Control Room Cabinets 32 Cable Chase
United States Nuclear Regulatory Commission January 25, 1980 Attention: Office of Nuclear Reactor Regulation Page 4 REASON FOR CHANGES: Reference (b) above required Maine Yankee to propose revised Technical Specifications related to facility fire protection modifications. The present implementation date for the modifications listed herein is at the end of the refueling interval which is scheduled to start during January, 1980.
This submittal provides the requested Technical Specificaticn revisions.
SAFETY CONSIDERATIONS:
The revision of Technical Specifications which relate to fire protection systems and which are being submitted in response to a Commission request are not considered to endanger the health and safety of the public.
This proposed change has been reviewed by the Nuclear Safety Audit and Review Committee.
FEE DETERMINATION:
As previously determined by the NRC, no license amendment fee is required to accompany a proposal to add surveillance and other requirements for operable fire protection systems added at the NRC's request.
SCHEDULE OF CHANGE: These changes to the Maine Yankee Technical Specifications will be made upon completion of the systems changes and upon receipt of Commission approval.
Very truly yours, MAINE YANKEE ATOMIC POWER COMPANY b
D. E. Vandenburgh Vice President COMMONWEALTH OF MASSACHUSETTS)
)ss.
COUNTY OF WORCESTER
)
Then personally appeared before me, D. E. Vandenburgh, who, being duly sworn, did state that he is a Vice President of Maine Yankee Atomic Power Company, that he is duly authorized to file, execute and sign the foregoing amendment in the name and on the behalf of Maine Yankee Atomic Power Company, and that the statements in said application are true to the best of his knowledge and belief.
Q4(th~
Robert H. Groce Notary Public My Commission Expires September 14, 1984 EAS/fb Attachments